upsSmartControlUpsSleep

1.3.6.1.4.1.935.1.1.1.6.2.3

Description

Setting this variable to putUpsToSleep(2) causes the UPS to go to sleep for the time specified by upsSmartConfigUpsSleepTime. When in sleep mode, the UPS will not provide output power regardless of the input line state. Once the specified time has elapsed, output power will be restored. Setting this value to noPutUpsT…

Full description and source information

Identification

Identifier and names

Parent
1.3.6.1.4.1.935.1.1.1.6.2 (upsSmartControl)
Node code
3
Node name
upsSmartControlUpsSleep
Category
SNMP management object
Numeric OID
1.3.6.1.4.1.935.1.1.1.6.2.3
URN notation
urn:oid:1.3.6.1.4.1.935.1.1.1.6.2.3
ASN.1, OID-IRI and named path variants
ASN.1 notation

{1 3 6 1 4 1 935 1 1 1 6 2 3}

  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) ppc(935) products(1) hardware(1) ups(1) upsControlp(6) upsSmartControl(2) upsSmartControlUpsSleep(3)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) ppc(935) products(1) hardware(1) ups(1) upsControl(6) upsSmartControl(2) upsSmartControlUpsSleep(3)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) ppc(935) products(1) hardware(1) ups(1) upsControlp(6) upsSmartControl(2) upsSmartControlUpsSleep(3)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) ppc(935) products(1) hardware(1) ups(1) upsControl(6) upsSmartControl(2) upsSmartControlUpsSleep(3)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) ppc(935) products(1) hardware(1) ups(1) upsControlp(6) upsSmartControl(2) upsSmartControlUpsSleep(3)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) ppc(935) products(1) hardware(1) ups(1) upsControl(6) upsSmartControl(2) upsSmartControlUpsSleep(3)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) vendor-objects(1) ppc(935) products(1) hardware(1) ups(1) upsControlp(6) upsSmartControl(2) upsSmartControlUpsSleep(3)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) vendor-objects(1) ppc(935) products(1) hardware(1) ups(1) upsControl(6) upsSmartControl(2) upsSmartControlUpsSleep(3)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprise(1) ppc(935) products(1) hardware(1) ups(1) upsControlp(6) upsSmartControl(2) upsSmartControlUpsSleep(3)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprise(1) ppc(935) products(1) hardware(1) ups(1) upsControl(6) upsSmartControl(2) upsSmartControlUpsSleep(3)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) ppc(935) products(1) hardware(1) ups(1) upsControlp(6) upsSmartControl(2) upsSmartControlUpsSleep(3)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) ppc(935) products(1) hardware(1) ups(1) upsControl(6) upsSmartControl(2) upsSmartControlUpsSleep(3)}
  • {iso(1) org(3) dod(6) internet(1) private(4) ldap-enterprise(1) ppc(935) products(1) hardware(1) ups(1) upsControlp(6) upsSmartControl(2) upsSmartControlUpsSleep(3)}
  • {iso(1) org(3) dod(6) internet(1) private(4) ldap-enterprise(1) ppc(935) products(1) hardware(1) ups(1) upsControl(6) upsSmartControl(2) upsSmartControlUpsSleep(3)}
  • {iso(1) org(3) dod(6) internet(1) private(4) vendor-objects(1) ppc(935) products(1) hardware(1) ups(1) upsControlp(6) upsSmartControl(2) upsSmartControlUpsSleep(3)}
  • {iso(1) org(3) dod(6) internet(1) private(4) vendor-objects(1) ppc(935) products(1) hardware(1) ups(1) upsControl(6) upsSmartControl(2) upsSmartControlUpsSleep(3)}
  • Additional combinations skipped.
OID-IRI notation
  • /1/3/6/1/4/1/935/1/1/1/6/2/3
  • /ISO/Identified-Organization/6/1/4/1/935/1/1/1/6/2/3
  • /ISO/3/6/1/4/1/935/1/1/1/6/2/3
Named path variants
  • /iso/identified-organization/dod/internet/private/enterprise/935/1/hardware/ups/upsControlp/upsSmartControl/upsSmartControlUpsSleep
  • /iso/identified-organization/dod/internet/private/enterprise/935/1/hardware/ups/upsControl/upsSmartControl/upsSmartControlUpsSleep
  • /iso/identified-organization/dod/internet/private/enterprise/935/products/hardware/ups/upsControlp/upsSmartControl/upsSmartControlUpsSleep
  • /iso/identified-organization/dod/internet/private/enterprise/935/products/hardware/ups/upsControl/upsSmartControl/upsSmartControlUpsSleep
  • /iso/identified-organization/dod/internet/private/enterprise/ppc/1/hardware/ups/upsControlp/upsSmartControl/upsSmartControlUpsSleep
  • /iso/identified-organization/dod/internet/private/enterprise/ppc/1/hardware/ups/upsControl/upsSmartControl/upsSmartControlUpsSleep
  • /iso/identified-organization/dod/internet/private/enterprise/ppc/products/hardware/ups/upsControlp/upsSmartControl/upsSmartControlUpsSleep
  • /iso/identified-organization/dod/internet/private/enterprise/ppc/products/hardware/ups/upsControl/upsSmartControl/upsSmartControlUpsSleep
  • /iso/identified-organization/dod/internet/private/enterprises/935/1/hardware/ups/upsControlp/upsSmartControl/upsSmartControlUpsSleep
  • /iso/identified-organization/dod/internet/private/enterprises/935/1/hardware/ups/upsControl/upsSmartControl/upsSmartControlUpsSleep
  • /iso/identified-organization/dod/internet/private/enterprises/935/products/hardware/ups/upsControlp/upsSmartControl/upsSmartControlUpsSleep
  • /iso/identified-organization/dod/internet/private/enterprises/935/products/hardware/ups/upsControl/upsSmartControl/upsSmartControlUpsSleep
  • /iso/identified-organization/dod/internet/private/enterprises/ppc/1/hardware/ups/upsControlp/upsSmartControl/upsSmartControlUpsSleep
  • /iso/identified-organization/dod/internet/private/enterprises/ppc/1/hardware/ups/upsControl/upsSmartControl/upsSmartControlUpsSleep
  • /iso/identified-organization/dod/internet/private/enterprises/ppc/products/hardware/ups/upsControlp/upsSmartControl/upsSmartControlUpsSleep
  • /iso/identified-organization/dod/internet/private/enterprises/ppc/products/hardware/ups/upsControl/upsSmartControl/upsSmartControlUpsSleep
  • Additional combinations skipped.

SNMP properties

Value type
INTEGER
Maximum access defined by MIB
read-write
Status in MIB
mandatory

Enumerated values

ValueName
1noPutUpsToSleep
2putUpsToSleep

Using this OID with SNMP

At least one MIB declaration places this object in a scalar group. A scalar instance uses the suffix .0.

snmpget [connection options] DEVICE .1.3.6.1.4.1.935.1.1.1.6.2.3.0

Replace the placeholders with your connection and authentication options. Available permissions and device support can differ from the MIB.

Properties come from available MIB definitions. Actual device support and access can differ. See source records below for original files and qualifications.

Available source records contain 2 distinct definitions; some records may not include a definition.

Show 2 published definitions

upsSmartControlUpsSleep · mandatory

upsSmartControlUpsSleep OBJECT-TYPE
        SYNTAX INTEGER {
                        noPutUpsToSleep(1),
                        putUpsToSleep(2) }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Setting this variable to putUpsToSleep(2) causes
                the UPS to go to sleep for the time specified by
                upsSmartConfigUpsSleepTime.
                                
                When in sleep mode, the UPS will not provide output
                power regardless of the input line state.  Once the
                specified time has elapsed, output power will be
                restored.
                                
                Setting this value to noPutUpsToSleep(1) has no
                effect.
                                
                The value noPutUpsToSleep(1) will always be returned
                when the variable is read."
   ::= { upsSmartControl 3 }

upsSmartControlUpsSleep · mandatory

upsSmartControlUpsSleep OBJECT-TYPE
	SYNTAX INTEGER  {
		noPutUpsToSleep(1),
		putUpsToSleep(2)
	}
	ACCESS read-write
	STATUS mandatory
	DESCRIPTION
		"Setting this variable to putUpsToSleep(2) causes
		 the UPS to go to sleep for the time specified by
		 upsSmartConfigUpsSleepTime.

		 When in sleep mode, the UPS will not provide output
		 power regardless of the input line state.  Once the
		 specified time has elapsed, output power will be
		 restored.

		 Setting this value to noPutUpsToSleep(1) has no
		 effect.

		 The value noPutUpsToSleep(1) will always be returned
		 when the variable is read."
	::= { upsSmartControl 3 }

Meaning

Descriptions

1 unique

Identical descriptions are grouped. Different wording and device-specific notes are retained.

Setting this variable to putUpsToSleep(2) causes the UPS to go to sleep for the time specified by upsSmartConfigUpsSleepTime. When in sleep mode, the UPS will not provide output power regardless of the input line state. Once the specified time has elapsed, output power will be restored. Setting this value to noPutUpsToSleep(1) has no effect. The value noPutUpsToSleep(1) will always be returned when the variable is read.

Sources for this description

Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)Reviewed vendor MIB copies in Fujitsu ServerViewCommon and standard MIB copies (LibreNMS/Observium Community)Netdisco MIB archive copies

See 1 matching source record

Evidence

Source records

1 records

Matching descriptions are grouped; representative source files are shown for each definition.

Records for description 1Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community), Reviewed vendor MIB copies in Fujitsu ServerView, and others1 record · 5 sources

Description 1

upsSmartControlUpsSleep · mandatoryMultiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community), Reviewed vendor MIB copies in Fujitsu ServerView, and others5 sources

Status in source: mandatory.

Names: upsSmartControlUpsSleep

Technical details
{
  "smi_kind": "OBJECT-TYPE",
  "definition": [
    "upsSmartControlUpsSleep",
    "OBJECT-TYPE",
    "SYNTAX",
    "INTEGER",
    "{",
    "noPutUpsToSleep",
    "(",
    "1",
    ")",
    ",",
    "putUpsToSleep",
    "(",
    "2",
    ")",
    "}",
    "ACCESS",
    "read-write",
    "STATUS",
    "mandatory",
    "DESCRIPTION",
    "\"Setting this variable to putUpsToSleep(2) causes the UPS to go to sleep for the time specified by upsSmartConfigUpsSleepTime. When in sleep mode, the UPS will not provide output power regardless of the input line state. Once the specified time has elapsed, output power will be restored. Setting this value to noPutUpsToSleep(1) has no effect. The value noPutUpsToSleep(1) will always be returned when the variable is read.\"",
    "::=",
    "{",
    "upsSmartControl",
    "3",
    "}"
  ],
  "syntax_tree": [
    [
      "SimpleSyntax",
      "INTEGER",
      [
        "enumSpec",
        [
          [
            "noPutUpsToSleep",
            1
          ],
          [
            "putUpsToSleep",
            2
          ]
        ]
      ]
    ],
    null,
    [
      "MaxAccessPart",
      "read-write"
    ],
    [
      "Status",
      "mandatory"
    ],
    [
      "DESCRIPTION",
      "Setting this variable to putUpsToSleep(2) causes the UPS to go to sleep for the time specified by upsSmartConfigUpsSleepTime. When in sleep mode, the UPS will not provide output power regardless of the input line state. Once the specified time has elapsed, output power will be restored. Setting this value to noPutUpsToSleep(1) has no effect. The value noPutUpsToSleep(1) will always be returned when the variable is read."
    ],
    null,
    null,
    null,
    null
  ]
}

Registration

Registration authorities

First Registration Authority (inferred from ancestor 1.3.6.1.4.1.935)

An-Hsiang Tu

Siblings (5)

OIDNameDirect childrenDescendantsDescription
1.3.6.1.4.1.935.1.1.1.6.2.1 upsSmartControlUpsOff00
1.3.6.1.4.1.935.1.1.1.6.2.2 upsSmartControlRebootUps00
1.3.6.1.4.1.935.1.1.1.6.2.4 upsSmartControlSimulatePowerFail00
1.3.6.1.4.1.935.1.1.1.6.2.5 upsSmartControlFlashAndBeep00
1.3.6.1.4.1.935.1.1.1.6.2.6 upsSmartControlTurnOnUpsLoad00