OID reference

matDryContactString

1.3.6.1.4.1.935.10.2.1.4.2.1.2

Description

format: xx xx xx xx xx xx xx xx xx xx, xx: alarm code. If the configured alarm is less than 10, then fill the position with '--' to instead 'xx'. Alarm code: Inverter fault 0x01(for 3.5Kva system and 1.5Kva system), Inverter over load 0x02(for 3.5Kva system and 1.5Kva system), Inverter fan fault 0x03(for 3.5Kva system…

Full description and source information

Identification

Identifier and names

Parent
1.3.6.1.4.1.935.10.2.1.4.2.1 (matDryContactEntry)
Node code
2
Node name
matDryContactString
Category
SNMP management object
Numeric OID
1.3.6.1.4.1.935.10.2.1.4.2.1.2
URN notation
urn:oid:1.3.6.1.4.1.935.10.2.1.4.2.1.2
ASN.1, OID-IRI and named path variants
ASN.1 notation

{1 3 6 1 4 1 935 10 2 1 4 2 1 2}

  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) ppc(935) device(10) matAgent(2) matObjects(1) matDryContact(4) matDryContactTable(2) matDryContactEntry(1) matDryContactString(2)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) ppc(935) device(10) matAgent(2) matObjects(1) matDryContact(4) matDryContactTable(2) matDryContactEntry(1) matDryContactString(2)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) ppc(935) device(10) matAgent(2) matObjects(1) matDryContact(4) matDryContactTable(2) matDryContactEntry(1) matDryContactString(2)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) vendor-objects(1) ppc(935) device(10) matAgent(2) matObjects(1) matDryContact(4) matDryContactTable(2) matDryContactEntry(1) matDryContactString(2)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprise(1) ppc(935) device(10) matAgent(2) matObjects(1) matDryContact(4) matDryContactTable(2) matDryContactEntry(1) matDryContactString(2)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) ppc(935) device(10) matAgent(2) matObjects(1) matDryContact(4) matDryContactTable(2) matDryContactEntry(1) matDryContactString(2)}
  • {iso(1) org(3) dod(6) internet(1) private(4) ldap-enterprise(1) ppc(935) device(10) matAgent(2) matObjects(1) matDryContact(4) matDryContactTable(2) matDryContactEntry(1) matDryContactString(2)}
  • {iso(1) org(3) dod(6) internet(1) private(4) vendor-objects(1) ppc(935) device(10) matAgent(2) matObjects(1) matDryContact(4) matDryContactTable(2) matDryContactEntry(1) matDryContactString(2)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprise(1) ppc(935) device(10) matAgent(2) matObjects(1) matDryContact(4) matDryContactTable(2) matDryContactEntry(1) matDryContactString(2)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprises(1) ppc(935) device(10) matAgent(2) matObjects(1) matDryContact(4) matDryContactTable(2) matDryContactEntry(1) matDryContactString(2)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) ppc(935) device(10) matAgent(2) matObjects(1) matDryContact(4) matDryContactTable(2) matDryContactEntry(1) matDryContactString(2)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) vendor-objects(1) ppc(935) device(10) matAgent(2) matObjects(1) matDryContact(4) matDryContactTable(2) matDryContactEntry(1) matDryContactString(2)}
  • {iso(1) iso-organization(3) dod(6) internet(1) private(4) enterprise(1) ppc(935) device(10) matAgent(2) matObjects(1) matDryContact(4) matDryContactTable(2) matDryContactEntry(1) matDryContactString(2)}
  • {iso(1) iso-organization(3) dod(6) internet(1) private(4) enterprises(1) ppc(935) device(10) matAgent(2) matObjects(1) matDryContact(4) matDryContactTable(2) matDryContactEntry(1) matDryContactString(2)}
  • {iso(1) iso-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) ppc(935) device(10) matAgent(2) matObjects(1) matDryContact(4) matDryContactTable(2) matDryContactEntry(1) matDryContactString(2)}
  • {iso(1) iso-organization(3) dod(6) internet(1) private(4) vendor-objects(1) ppc(935) device(10) matAgent(2) matObjects(1) matDryContact(4) matDryContactTable(2) matDryContactEntry(1) matDryContactString(2)}
OID-IRI notation
  • /1/3/6/1/4/1/935/10/2/1/4/2/1/2
  • /ISO/Identified-Organization/6/1/4/1/935/10/2/1/4/2/1/2
  • /ISO/3/6/1/4/1/935/10/2/1/4/2/1/2
Named path variants
  • /iso/identified-organization/dod/internet/private/enterprise/935/device/matAgent/matObjects/matDryContact/matDryContactTable/matDryContactEntry/matDryContactString
  • /iso/identified-organization/dod/internet/private/enterprise/ppc/device/matAgent/matObjects/matDryContact/matDryContactTable/matDryContactEntry/matDryContactString
  • /iso/identified-organization/dod/internet/private/enterprises/935/device/matAgent/matObjects/matDryContact/matDryContactTable/matDryContactEntry/matDryContactString
  • /iso/identified-organization/dod/internet/private/enterprises/ppc/device/matAgent/matObjects/matDryContact/matDryContactTable/matDryContactEntry/matDryContactString
  • /iso/identified-organization/dod/internet/private/ldap-enterprise/935/device/matAgent/matObjects/matDryContact/matDryContactTable/matDryContactEntry/matDryContactString
  • /iso/identified-organization/dod/internet/private/ldap-enterprise/ppc/device/matAgent/matObjects/matDryContact/matDryContactTable/matDryContactEntry/matDryContactString
  • /iso/identified-organization/dod/internet/private/vendor-objects/935/device/matAgent/matObjects/matDryContact/matDryContactTable/matDryContactEntry/matDryContactString
  • /iso/identified-organization/dod/internet/private/vendor-objects/ppc/device/matAgent/matObjects/matDryContact/matDryContactTable/matDryContactEntry/matDryContactString
  • /iso/org/dod/internet/private/enterprise/935/device/matAgent/matObjects/matDryContact/matDryContactTable/matDryContactEntry/matDryContactString
  • /iso/org/dod/internet/private/enterprise/ppc/device/matAgent/matObjects/matDryContact/matDryContactTable/matDryContactEntry/matDryContactString
  • /iso/org/dod/internet/private/enterprises/935/device/matAgent/matObjects/matDryContact/matDryContactTable/matDryContactEntry/matDryContactString
  • /iso/org/dod/internet/private/enterprises/ppc/device/matAgent/matObjects/matDryContact/matDryContactTable/matDryContactEntry/matDryContactString
  • /iso/org/dod/internet/private/ldap-enterprise/935/device/matAgent/matObjects/matDryContact/matDryContactTable/matDryContactEntry/matDryContactString
  • /iso/org/dod/internet/private/ldap-enterprise/ppc/device/matAgent/matObjects/matDryContact/matDryContactTable/matDryContactEntry/matDryContactString
  • /iso/org/dod/internet/private/vendor-objects/935/device/matAgent/matObjects/matDryContact/matDryContactTable/matDryContactEntry/matDryContactString
  • /iso/org/dod/internet/private/vendor-objects/ppc/device/matAgent/matObjects/matDryContact/matDryContactTable/matDryContactEntry/matDryContactString
  • Additional combinations skipped.

SNMP properties

Value type
DisplayString
Maximum access defined by MIB
read-write
Status in MIB
mandatory
Allowed size (octets)
0–29

Using this OID with SNMP

At least one MIB declaration places this object in a table row. A value belongs to a row instance; its suffix depends on the row's INDEX or AUGMENTS definition. The index encoding is not inferred here.

Published row index: matDryContactIndex.

snmpwalk [connection options] DEVICE .1.3.6.1.4.1.935.10.2.1.4.2.1.2

Replace the placeholders with your connection and authentication options. Available permissions and device support can differ from the MIB.

Properties come from available MIB definitions. Actual device support and access can differ. See source records below for original files and qualifications.

The displayed source records contain one distinct definition. Compare its source records.

matDryContactString OBJECT-TYPE
SYNTAX DisplayString ( SIZE ( 0 .. 29 ) )
ACCESS read-write
STATUS mandatory
DESCRIPTION	"format: xx xx xx xx xx xx xx xx xx xx,
xx: alarm code. If the configured alarm is less than 10, then fill the position with '--' to instead 'xx'.
Alarm code:
Inverter fault	0x01(for 3.5Kva system and 1.5Kva system),
Inverter over load	0x02(for 3.5Kva system and 1.5Kva system),
Inverter fan fault	0x03(for 3.5Kva system and 1.5Kva system),
Inverter power limit	0x04(for 3.5Kva system and 1.5Kva system),
Inverter DC input Abnormal	0x05(for 3.5Kva system and 1.5Kva system),
Inverter low volt off	0x06(for 3.5Kva system and 1.5Kva system),
Inverter lost	0x07(for 3.5Kva system and 1.5Kva system),
Inverter Mains unavailable	0x19(for 3.5Kva system),
Inverter Maintenance Bypass	0x1A(for 3.5Kva system),
Inverter Output	0x1B(for 3.5Kva system),
STS Inv unavailable	0x2A(for 1.5Kva system),
STS Main unavailable	0x2B(for 1.5Kva system),
STS Output overload	0x2C(for 1.5Kva system),
STS OP Short circuit	0x2D(for 1.5Kva system),
STS K1 Relay open	0x23(for 1.5Kva system),
STS SCR1 short	0x24(for 1.5Kva system),
STS SCR2 short	0x25(for 1.5Kva system),
STS INV Bypass Mode	0x2F(for 1.5Kva system),
STS Over temperature	0x30(for 1.5Kva system),
STS MBS Abnormal	0x31(for 1.5Kva system),
STS Fan Lock	0x27(for 1.5Kva system),
STS Fault Mode	0x26(for 1.5Kva system),
STS Eeprom Fault	0x28(for 1.5Kva system),
SPS Power Fail	0x32(for 1.5Kva system),
STS Output abnormal	0x34(for 1.5Kva system),
STS Maintenance Bypass	0x35(for 1.5Kva system),
STS Output	0x36(for 1.5Kva system),
Controller temperature high	0x42(for 3.5Kva system and 1.5Kva system),
Controller eeprom fail	0x43(for 3.5Kva system and 1.5Kva system),
Controller CAN Bus Off	0x45(for 3.5Kva system and 1.5Kva system)"
::= { matDryContactEntry	2 }

Meaning

Descriptions

1 unique

Identical descriptions are grouped. Different wording and device-specific notes are retained.

format: xx xx xx xx xx xx xx xx xx xx, xx: alarm code. If the configured alarm is less than 10, then fill the position with '--' to instead 'xx'. Alarm code: Inverter fault 0x01(for 3.5Kva system and 1.5Kva system), Inverter over load 0x02(for 3.5Kva system and 1.5Kva system), Inverter fan fault 0x03(for 3.5Kva system and 1.5Kva system), Inverter power limit 0x04(for 3.5Kva system and 1.5Kva system), Inverter DC input Abnormal 0x05(for 3.5Kva system and 1.5Kva system), Inverter low volt off 0x06(for 3.5Kva system and 1.5Kva system), Inverter lost 0x07(for 3.5Kva system and 1.5Kva system), Inverter Mains unavailable 0x19(for 3.5Kva system), Inverter Maintenance Bypass 0x1A(for 3.5Kva system), Inverter Output 0x1B(for 3.5Kva system), STS Inv unavailable 0x2A(for 1.5Kva system), STS Main unavailable 0x2B(for 1.5Kva system), STS Output overload 0x2C(for 1.5Kva system), STS OP Short circuit 0x2D(for 1.5Kva system), STS K1 Relay open 0x23(for 1.5Kva system), STS SCR1 short 0x24(for 1.5Kva system), STS SCR2 short 0x25(for 1.5Kva system), STS INV Bypass Mode 0x2F(for 1.5Kva system), STS Over temperature 0x30(for 1.5Kva system), STS MBS Abnormal 0x31(for 1.5Kva system), STS Fan Lock 0x27(for 1.5Kva system), STS Fault Mode 0x26(for 1.5Kva system), STS Eeprom Fault 0x28(for 1.5Kva system), SPS Power Fail 0x32(for 1.5Kva system), STS Output abnormal 0x34(for 1.5Kva system), STS Maintenance Bypass 0x35(for 1.5Kva system), STS Output 0x36(for 1.5Kva system), Controller temperature high 0x42(for 3.5Kva system and 1.5Kva system), Controller eeprom fail 0x43(for 3.5Kva system and 1.5Kva system), Controller CAN Bus Off 0x45(for 3.5Kva system and 1.5Kva system)

Sources for this description

Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)

See 1 matching source record

Evidence

Source records

1 records

Matching descriptions are grouped; representative source files are shown for each definition.

Records for description 1Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)1 record · 1 source

Description 1

matDryContactString · mandatoryMultiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)1 source

Status in source: mandatory.

Names: matDryContactString

Technical details
{
  "smi_kind": "OBJECT-TYPE",
  "definition": [
    "matDryContactString",
    "OBJECT-TYPE",
    "SYNTAX",
    "DisplayString",
    "(",
    "SIZE",
    "(",
    "0",
    ".",
    ".",
    "29",
    ")",
    ")",
    "ACCESS",
    "read-write",
    "STATUS",
    "mandatory",
    "DESCRIPTION",
    "\"format: xx xx xx xx xx xx xx xx xx xx, xx: alarm code. If the configured alarm is less than 10, then fill the position with '--' to instead 'xx'. Alarm code: Inverter fault 0x01(for 3.5Kva system and 1.5Kva system), Inverter over load 0x02(for 3.5Kva system and 1.5Kva system), Inverter fan fault 0x03(for 3.5Kva system and 1.5Kva system), Inverter power limit 0x04(for 3.5Kva system and 1.5Kva system), Inverter DC input Abnormal 0x05(for 3.5Kva system and 1.5Kva system), Inverter low volt off 0x06(for 3.5Kva system and 1.5Kva system), Inverter lost 0x07(for 3.5Kva system and 1.5Kva system), Inverter Mains unavailable 0x19(for 3.5Kva system), Inverter Maintenance Bypass 0x1A(for 3.5Kva system), Inverter Output 0x1B(for 3.5Kva system), STS Inv unavailable 0x2A(for 1.5Kva system), STS Main unavailable 0x2B(for 1.5Kva system), STS Output overload 0x2C(for 1.5Kva system), STS OP Short circuit 0x2D(for 1.5Kva system), STS K1 Relay open 0x23(for 1.5Kva system), STS SCR1 short 0x24(for 1.5Kva system), STS SCR2 short 0x25(for 1.5Kva system), STS INV Bypass Mode 0x2F(for 1.5Kva system), STS Over temperature 0x30(for 1.5Kva system), STS MBS Abnormal 0x31(for 1.5Kva system), STS Fan Lock 0x27(for 1.5Kva system), STS Fault Mode 0x26(for 1.5Kva system), STS Eeprom Fault 0x28(for 1.5Kva system), SPS Power Fail 0x32(for 1.5Kva system), STS Output abnormal 0x34(for 1.5Kva system), STS Maintenance Bypass 0x35(for 1.5Kva system), STS Output 0x36(for 1.5Kva system), Controller temperature high 0x42(for 3.5Kva system and 1.5Kva system), Controller eeprom fail 0x43(for 3.5Kva system and 1.5Kva system), Controller CAN Bus Off 0x45(for 3.5Kva system and 1.5Kva system)\"",
    "::=",
    "{",
    "matDryContactEntry",
    "2",
    "}"
  ],
  "syntax_tree": [
    [
      "SimpleSyntax",
      "DisplayString",
      [
        "octetStringSubType",
        [
          [
            0,
            29
          ]
        ]
      ]
    ],
    null,
    [
      "MaxAccessPart",
      "read-write"
    ],
    [
      "Status",
      "mandatory"
    ],
    [
      "DESCRIPTION",
      "format: xx xx xx xx xx xx xx xx xx xx, xx: alarm code. If the configured alarm is less than 10, then fill the position with '--' to instead 'xx'. Alarm code: Inverter fault 0x01(for 3.5Kva system and 1.5Kva system), Inverter over load 0x02(for 3.5Kva system and 1.5Kva system), Inverter fan fault 0x03(for 3.5Kva system and 1.5Kva system), Inverter power limit 0x04(for 3.5Kva system and 1.5Kva system), Inverter DC input Abnormal 0x05(for 3.5Kva system and 1.5Kva system), Inverter low volt off 0x06(for 3.5Kva system and 1.5Kva system), Inverter lost 0x07(for 3.5Kva system and 1.5Kva system), Inverter Mains unavailable 0x19(for 3.5Kva system), Inverter Maintenance Bypass 0x1A(for 3.5Kva system), Inverter Output 0x1B(for 3.5Kva system), STS Inv unavailable 0x2A(for 1.5Kva system), STS Main unavailable 0x2B(for 1.5Kva system), STS Output overload 0x2C(for 1.5Kva system), STS OP Short circuit 0x2D(for 1.5Kva system), STS K1 Relay open 0x23(for 1.5Kva system), STS SCR1 short 0x24(for 1.5Kva system), STS SCR2 short 0x25(for 1.5Kva system), STS INV Bypass Mode 0x2F(for 1.5Kva system), STS Over temperature 0x30(for 1.5Kva system), STS MBS Abnormal 0x31(for 1.5Kva system), STS Fan Lock 0x27(for 1.5Kva system), STS Fault Mode 0x26(for 1.5Kva system), STS Eeprom Fault 0x28(for 1.5Kva system), SPS Power Fail 0x32(for 1.5Kva system), STS Output abnormal 0x34(for 1.5Kva system), STS Maintenance Bypass 0x35(for 1.5Kva system), STS Output 0x36(for 1.5Kva system), Controller temperature high 0x42(for 3.5Kva system and 1.5Kva system), Controller eeprom fail 0x43(for 3.5Kva system and 1.5Kva system), Controller CAN Bus Off 0x45(for 3.5Kva system and 1.5Kva system)"
    ],
    null,
    null,
    null,
    null
  ]
}

Registration

Registration authorities

First Registration Authority (inferred from ancestor 1.3.6.1.4.1.935)

An-Hsiang Tu

Siblings (1)

OIDNameDirect childrenDescendantsDescription
1.3.6.1.4.1.935.10.2.1.4.2.1.1 matDryContactIndex00