upsAdvTest OBJECT IDENTIFIER ::= { upsTest 2 }
Vendor: American Power Conversion Corp.
Module: PowerNet-MIB
[Automatically extracted from oidview.com]
upsAdvTest OBJECT IDENTIFIER ::= { upsTest 2 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.1.7.2.1 | upsAdvTestDiagnosticSchedule | 1 | 1 | The UPS system's automatic battery test schedule. |
1.3.6.1.4.1.318.1.1.1.7.2.2 | upsAdvTestDiagnostics | 1 | 1 | Setting this variable to testDiagnostics(2) causes the UPS to perform a diagnostic self test. Setting this value to noTestDiagno… |
1.3.6.1.4.1.318.1.1.1.7.2.3 | upsAdvTestDiagnosticsResults | 1 | 1 | The results of the last UPS diagnostics test performed. |
1.3.6.1.4.1.318.1.1.1.7.2.4 | upsAdvTestLastDiagnosticsDate | 1 | 1 | The date the last UPS diagnostics test was performed in mm/dd/yy format. |
1.3.6.1.4.1.318.1.1.1.7.2.5 | upsAdvTestRuntimeCalibration | 1 | 1 | Setting this variable to performCalibration(2) causes the UPS to discharge to calibrate the UPS. The test will only start if the … |
1.3.6.1.4.1.318.1.1.1.7.2.6 | upsAdvTestCalibrationResults | 1 | 1 | The results of the last runtime calibration. Value ok(1) means a successful runtime calibration. Value invalidCalibration(2) in… |
1.3.6.1.4.1.318.1.1.1.7.2.7 | upsAdvTestCalibrationDate | 1 | 1 | The date the last UPS runtime calibration was performed in mm/dd/yy format. |
1.3.6.1.4.1.318.1.1.1.7.2.8 | upsAdvTestDiagnosticTime | 1 | 1 | The time of the day to perform automatic battery test. Expressed in 24 hour notation - hh:mm. |
1.3.6.1.4.1.318.1.1.1.7.2.9 | upsAdvTestDiagnosticDay | 1 | 1 | The day of the week to perform automatic battery test. |
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.1.7.1 | upsBasicTest | 0 | 0 | None |