The number of cells per battery (1, 2, 4 or 6 for lead-acid, 1 or 2 for NiCd.
Parsed from file powernet.mib.txt
Company: None
Module: PowerNet-MIB
The number of cells per battery (1 - 6 for lead-acid, 1 - 2 for NiCd.
Parsed from file PowerNet-MIB.mib
Module: PowerNet-MIB
battManConfigCellsperBattery OBJECT-TYPE SYNTAX INTEGER { oneCell (1), twoCells (2), fourCells (4), sixCells (6) } ACCESS read-write STATUS mandatory DESCRIPTION "The number of cells per battery (1, 2, 4 or 6 for lead-acid, 1 or 2 for NiCd." ::= { battManConfig 6 }
Vendor: American Power Conversion Corp.
Module: PowerNet-MIB
[Automatically extracted from oidview.com]
battManConfigCellsperBattery OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The number of cells per battery (1 - 6 for lead-acid, 1 - 2 for NiCd." ::= { battManConfig 6 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.16.6.6.0 | battManConfigCellsperBattery | 0 | 0 | None |
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.16.6.1 | battManConfigApplication | 1 | 1 | This OID has been deprecated. |
1.3.6.1.4.1.318.1.1.16.6.2 | battManConfigBatteryChemistry | 1 | 1 | The battery chemistry of the monitored batteries: LeadAcid(1) Lead Acid or Nickel-Cadmium(2) Nickel-Cadmium. |
1.3.6.1.4.1.318.1.1.16.6.3 | battManConfigBatteryAHCapacity | 1 | 1 | The amp hour capacity of the monitored batteries 5-4000 AH. |
1.3.6.1.4.1.318.1.1.16.6.4 | battManConfigNumberofStrings | 1 | 1 | The number of strings in the battery manager system. |
1.3.6.1.4.1.318.1.1.16.6.5 | battManConfigBatteriesperString | 1 | 1 | The number of batteries per string. |
1.3.6.1.4.1.318.1.1.16.6.7 | battManConfigMinCellVoltage | 1 | 1 | The minimum battery cell voltage alarm limit in millivolts DC. |
1.3.6.1.4.1.318.1.1.16.6.8 | battManConfigMaxCellVoltage | 1 | 1 | The maximum battery cell voltage alarm limit in millivolts DC. |
1.3.6.1.4.1.318.1.1.16.6.9 | battManConfigMaxPilotTempF | 1 | 1 | The maximum pilot battery temperature alarm limit in tenths of degrees Fahrenheit. |
1.3.6.1.4.1.318.1.1.16.6.10 | battManConfigMaxPilotTempC | 1 | 1 | The maximum pilot battery temperature alarm limit in tenths of degrees Celsius. |
1.3.6.1.4.1.318.1.1.16.6.11 | battManConfigMaxAmbientTempF | 1 | 1 | The maximum ambient temperature alarm limit in tenths of degrees Fahrenheit. |
1.3.6.1.4.1.318.1.1.16.6.12 | battManConfigMaxAmbientTempC | 1 | 1 | The maximum ambient temperature alarm limit in tenths of degrees Celsius. |
1.3.6.1.4.1.318.1.1.16.6.13 | battManConfigMinAmbientTempF | 1 | 1 | The Minimum Ambient Temperature alarm limit in tenths of degrees Fahrenheit. |
1.3.6.1.4.1.318.1.1.16.6.14 | battManConfigMinAmbientTempC | 1 | 1 | The Minimum Ambient Temperature alarm limit in tenths of degrees Celsius. |
1.3.6.1.4.1.318.1.1.16.6.15 | battManConfigMaxRippleCurrent | 1 | 1 | The maximum ripple current alarm limit for the monitored battery strings in percent of AH capacity. |
1.3.6.1.4.1.318.1.1.16.6.16 | battManConfigMaxCurrentAcceptanceDeviation | 1 | 1 | The maximum current acceptance deviation alarm limit in percent. |
1.3.6.1.4.1.318.1.1.16.6.17 | battManConfigMonitorWireLength | 1 | 1 | The monitor wire length: fiftyFeetOrLess (1) indicates that the wire length is less than or equal to 50 feet. moreThanFiftyFeet (… |
1.3.6.1.4.1.318.1.1.16.6.18 | battManConfigDischargeVoltageAlarmLevel | 1 | 1 | The discharge voltage alarm level in percent. |
1.3.6.1.4.1.318.1.1.16.6.19 | battManConfigAutoAnnunciatorReset | 1 | 1 | The annunciator output signal reset method: disabled(1) means the annunciator signal output will be reset when the reset button … |
1.3.6.1.4.1.318.1.1.16.6.20 | battManConfigSuspendCellVoltage | 1 | 1 | This is used along with the number of cells per battery and the number of batteries per string to determine if a battery string h… |
1.3.6.1.4.1.318.1.1.16.6.21 | battManConfigOhmicTestWaitTime | 1 | 1 | The amount of time in seconds after a discharge event before data will be collected for the ohmic value calculation. |
1.3.6.1.4.1.318.1.1.16.6.22 | battManConfigNumberOfBoosts | 1 | 1 | The number of consecutive times the Battery Management System applies a charge to each battery during a boost cycle. Batteries w… |