Converter Fail Safe point. This OID represents the value sent to converter controllers
to use in the event of communications loss with the Master Controller or Master Controller
board failure.
Values are represented in thousandths of Volts (mV).
Attempts to set the value above or below the acceptable range of the powerplant
will cause the value to be set at the high or low point of the range respectively.
Parsed from file powernet.mib.txt
Company: None
Module: PowerNet-MIB
Converter Fail Safe point. This OID represents the value sent to converter controllers
to use in the event of communications loss with the Master Controller or Master Controller
board failure.
Values are represented in thousandths of Volts (mV).
Attempts to set the value above or below the acceptable range of the powerplant
will cause the value to be set at the high or low point of the range respectively.
Parsed from file PowerNet-MIB.mib
Module: PowerNet-MIB
dm3ConfigConvFailSafe OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Converter Fail Safe point. This OID represents the value sent to converter controllers to use in the event of communications loss with the Master Controller or Master Controller board failure. Values are represented in thousandths of Volts (mV). Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively." ::= { dm3ConfigConvThresh 3 }
Vendor: American Power Conversion Corp.
Module: PowerNet-MIB
[Automatically extracted from oidview.com]
dm3ConfigConvFailSafe OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Converter Fail Safe point. This OID represents the value sent to converter controllers to use in the event of communications loss with the Master Controller or Master Controller board failure. Values are represented in thousandths of Volts (mV). Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively." ::= { dm3ConfigConvThresh 3 }
| OID | Name | Sub children | Sub Nodes Total | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.318.1.1.7.2.4.2.1.3.0 | dm3ConfigConvFailSafe | 0 | 0 | None |
| OID | Name | Sub children | Sub Nodes Total | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.318.1.1.7.2.4.2.1.1 | dm3ConfigConvHighVoltThresh | 1 | 1 | Converter high voltage threshold. If converter voltage exceeds threshold a converter high voltage alarm will occur. Values are … |
| 1.3.6.1.4.1.318.1.1.7.2.4.2.1.2 | dm3ConfigConvLowVoltThresh | 1 | 1 | Converter low voltage threshold. If converter voltage exceeds threshold a converter low voltage alarm will occur. Values are re… |
| 1.3.6.1.4.1.318.1.1.7.2.4.2.1.4 | dm3ConfigConvSetPoint | 1 | 1 | Converter Set point. This OID represents the initial set point used in the voltage control loop. Units are thousandths of Volts… |
| 1.3.6.1.4.1.318.1.1.7.2.4.2.1.5 | dm3ConfigConvFailMax | 1 | 1 | Converter Fail Maximum limit. This OID represents the value sent to the converter controllers to define the maximum set point a… |
| 1.3.6.1.4.1.318.1.1.7.2.4.2.1.6 | dm3ConfigConvFailMin | 1 | 1 | Converter Fail Minimum limit. This OID represents the value sent to the converter controllers to define the minimum set point a… |
| 1.3.6.1.4.1.318.1.1.7.2.4.2.1.7 | dm3ConfigConvFailComm | 1 | 1 | Converter Communication Fail timeout. This OID represents the time interval in which there is no communication between the conv… |