The calculated time remaining before bypass static switch shutdown due
to the present overload condition. If the bypass is not in an overload
condition, this object returns -1.
Parsed from file LIEBERT_GP_POWER.MIB.txt
Company: liebert
Module: LIEBERT-GP-POWER-MIB
Child arc 0 is used to translate between SNMPv1 and SNMPv2 notification parameters as explained in IETF RFC 2576, section 3.
lgpPwrBypassOverloadShutdownTime OBJECT-TYPE SYNTAX Integer32 UNITS "seconds" MAX-ACCESS read-only STATUS current DESCRIPTION "The calculated time remaining before bypass static switch shutdown due to the present overload condition. If the bypass is not in an overload condition, this object returns -1." ::= { lgpPwrStatus 29 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.476.1.42.3.5.3.29.0 | lgpPwrBypassOverloadShutdownTime | 0 | 0 | None |
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.476.1.42.3.5.3.1 | lgpPwrTransferCount | 1 | 1 | Number of times that the output load has been transferred between the available input sources. |
1.3.6.1.4.1.476.1.42.3.5.3.2 | lgpPwrAutoTransferTimer | 1 | 1 | The required wait time between output load auto transfer attempts between available input sources. |
1.3.6.1.4.1.476.1.42.3.5.3.3 | lgpPwrAutoReTransferEnabled | 1 | 1 | The ability to retransfer the output load automatically to the well known measurement source from the 'lgpPwrWellKnownMeasuremen… |
1.3.6.1.4.1.476.1.42.3.5.3.4 | lgpPwrSyncPhaseAngle | 1 | 1 | The phase angle difference of source 1 in relation to source 2. |
1.3.6.1.4.1.476.1.42.3.5.3.5 | lgpPwrParallelSystemOutputToLoadSource | 1 | 1 | The source supporting the parallel system's load. |
1.3.6.1.4.1.476.1.42.3.5.3.6 | lgpPwrDcToDcConverter | 1 | 1 | The state of the DC to DC converter. |
1.3.6.1.4.1.476.1.42.3.5.3.7 | lgpPwrOutputToLoadOnInverter | 1 | 1 | The present source of output power is the Inverter. |
1.3.6.1.4.1.476.1.42.3.5.3.8 | lgpPwrBatteryChargeCompensating | 1 | 1 | The system is adjusting the battery charging algorithm to accommodate for the battery temperature. |
1.3.6.1.4.1.476.1.42.3.5.3.9 | lgpPwrInverterReady | 1 | 1 | The ability of the inverter to support the output load of the system. |
1.3.6.1.4.1.476.1.42.3.5.3.10 | lgpPwrOutputToLoadOnBypass | 1 | 1 | The present source of output power is the Bypass. |
1.3.6.1.4.1.476.1.42.3.5.3.11 | lgpPwrBoost | 1 | 1 | The present state of the boost circuitry |
1.3.6.1.4.1.476.1.42.3.5.3.12 | lgpPwrBuck | 1 | 1 | The present state of the buck circuitry |
1.3.6.1.4.1.476.1.42.3.5.3.13 | lgpPwrShutdownOverTemperature | 1 | 1 | The system has previously shutdown due to an over temperature condition. |
1.3.6.1.4.1.476.1.42.3.5.3.14 | lgpPwrShutdownOverload | 1 | 1 | The system has previously shutdown due to an over load condition. |
1.3.6.1.4.1.476.1.42.3.5.3.15 | lgpPwrShutdownDcBusOverload | 1 | 1 | The system has previously shutdown due to a DC bus over load condition. |
1.3.6.1.4.1.476.1.42.3.5.3.16 | lgpPwrShutdownOutputShort | 1 | 1 | The system has previously shutdown due to an ouput short condition. |
1.3.6.1.4.1.476.1.42.3.5.3.17 | lgpPwrShutdownLineSwap | 1 | 1 | The system has previously shutdown due to a condition where the line and neutral were reversed. |
1.3.6.1.4.1.476.1.42.3.5.3.18 | lgpPwrShutdownLowBattery | 1 | 1 | The system has previously shutdown due to a low battery condition. |
1.3.6.1.4.1.476.1.42.3.5.3.19 | lgpPwrShutdownRemote | 1 | 1 | The system has previously shutdown due to a remote shutdown command. |
1.3.6.1.4.1.476.1.42.3.5.3.20 | lgpPwrShutdownInputUnderVoltage | 1 | 1 | The system has previously shutdown due to an under voltage condition during startup. |
1.3.6.1.4.1.476.1.42.3.5.3.21 | lgpPwrShutdownPowerFactorCorrectionFailure | 1 | 1 | The system has previously shutdown due to a power factor correction startup failure. |
1.3.6.1.4.1.476.1.42.3.5.3.22 | lgpPwrShutdownHardware | 1 | 1 | The system has previously shutdown due external shutdown signal. |
1.3.6.1.4.1.476.1.42.3.5.3.23 | lgpPwrRedundantSubModule | 1 | 1 | The system has a redundant battery module installed. |
1.3.6.1.4.1.476.1.42.3.5.3.24 | lgpPwrBypassReady | 1 | 1 | The ability of the bypass to support the output load of the system. If Yes, the bypass is available to transfer to. |
1.3.6.1.4.1.476.1.42.3.5.3.25 | lgpPwrGeneratorStatus | 1 | 1 | The state of the system generator. |
1.3.6.1.4.1.476.1.42.3.5.3.26 | lgpPwrRotaryBreakerStatus | 1 | 1 | The state of the system rotary breaker. |
1.3.6.1.4.1.476.1.42.3.5.3.27 | lgpPwrPowerFactorCorrection | 1 | 1 | The state of the power factor correction circuitry of the system. |
1.3.6.1.4.1.476.1.42.3.5.3.28 | lgpPwrBypassSyncDiff | 1 | 1 | The phase angle difference between the inverter output and bypass source. A positive value means the inverter leads the bypass s… |
1.3.6.1.4.1.476.1.42.3.5.3.30 | lgpPwrInverterOverloadShutdownTime | 1 | 1 | The calculated time remaining before inverter shutdown. The calculated time of inverter operation remaining for the present over… |
1.3.6.1.4.1.476.1.42.3.5.3.31 | lgpPwrStateOutputSource | 1 | 1 | The UPS's output power source (inverter, bypass, or none). NOTE: It is possible that the load still has power from the Maintenanc… |
1.3.6.1.4.1.476.1.42.3.5.3.32 | lgpPwrStateInputSource | 1 | 1 | The system input power source (none, utility, generator). |
1.3.6.1.4.1.476.1.42.3.5.3.33 | lgpPwrStateInputQualification | 1 | 1 | The current state of the system input. The unit may or may not operate normally under 'marginalLow' and 'marginalHigh' states. |
1.3.6.1.4.1.476.1.42.3.5.3.34 | lgpPwrStateBypassStaticSwitchState | 1 | 1 | The current state of the bypass static switch. |
1.3.6.1.4.1.476.1.42.3.5.3.35 | lgpPwrStateBypassQualification | 1 | 1 | The current operational state of the bypass static switch. The unit may or may not operate normally under 'marginalLow' and 'mar… |
1.3.6.1.4.1.476.1.42.3.5.3.36 | lgpPwrStateDCBusQualification | 1 | 1 | The current operational state of the DC bus. The unit may or may not operate normally under 'marginalLow' and 'marginalHigh' sta… |
1.3.6.1.4.1.476.1.42.3.5.3.37 | lgpPwrStateOutQualification | 1 | 1 | The current operational state of the output. The unit may or may not operate normally under 'marginalLow' and 'marginalHigh' sta… |
1.3.6.1.4.1.476.1.42.3.5.3.38 | lgpPwrStateInverterQualification | 1 | 1 | The current operational state of the inverter. The unit may or may not operate normally under 'marginalLow' and 'marginalHigh' s… |
1.3.6.1.4.1.476.1.42.3.5.3.39 | lgpPwrStateInverterState | 1 | 1 | The current state of the inverter. |
1.3.6.1.4.1.476.1.42.3.5.3.40 | lgpPwrStateRectifierState | 1 | 1 | The current state of the rectifier. |
1.3.6.1.4.1.476.1.42.3.5.3.41 | lgpPwrStateModuleGroup | 2 | 4 | This group contains UPS module information. |
1.3.6.1.4.1.476.1.42.3.5.3.42 | lgpPwrStateBackfeedBrkrState | 1 | 1 | The state of the Static Bypass Switch Line Disconnect Breaker. |
1.3.6.1.4.1.476.1.42.3.5.3.43 | lgpPwrStateLoadDisconnectState | 1 | 1 | The state of the Static Bypass Switch Load Disconnect Breaker. |
1.3.6.1.4.1.476.1.42.3.5.3.44 | lgpPwrStateInputBrkrState | 1 | 1 | The state of the Input Disconnect Breaker. |
1.3.6.1.4.1.476.1.42.3.5.3.45 | lgpPwrStateTrapFilterBrkrState | 1 | 1 | The state of the Trap Filter Disconnect Breaker. |
1.3.6.1.4.1.476.1.42.3.5.3.46 | lgpPwrStateInvOutputBrkrState | 1 | 1 | The state of the Inverter Output Disconnect Breaker. |
1.3.6.1.4.1.476.1.42.3.5.3.47 | lgpPwrStateIntBypassBrkrState | 1 | 1 | The state of the Internal Bypass Breaker. |
1.3.6.1.4.1.476.1.42.3.5.3.48 | lgpPwrStateBypassIsolBrkrState | 1 | 1 | The state of the Bypass Isolation Breaker. |
1.3.6.1.4.1.476.1.42.3.5.3.49 | lgpPwrStateRectifierIsolBrkrState | 1 | 1 | The state of the Rectifier Isolation Breaker. |
1.3.6.1.4.1.476.1.42.3.5.3.50 | lgpPwrStateMaintBypassBrkrState | 1 | 1 | The state of the Maintenance Bypass Breaker. |
1.3.6.1.4.1.476.1.42.3.5.3.51 | lgpPwrStateMaintIsolBrkrState | 1 | 1 | The state of the Maintenance Isolation Breaker. |
1.3.6.1.4.1.476.1.42.3.5.3.52 | lgpPwrStateOutStaticSwState | 1 | 1 | The state of the Output Series Static Switch. |
1.3.6.1.4.1.476.1.42.3.5.3.53 | lgpPwrStateModuleOutBrkrState | 1 | 1 | The state of the Module Output Breaker. |
1.3.6.1.4.1.476.1.42.3.5.3.54 | lgpPwrBypassReXfrRemainTime | 1 | 1 | The time remaining before an inverter overload or inverter fault can be cleared and auto retransfer from the bypass to the inver… |
1.3.6.1.4.1.476.1.42.3.5.3.55 | lgpPwrStateUpsOutputSource | 1 | 1 | The present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no … |