Setting this object to 'on' will cause the UPS system
to restart after a shutdown if the shutdown occurred
during a power loss as a result of either a
upsShutdownAfterDelay or an internal battery depleted
condition. Setting this object to 'off' will prevent
the UPS system from restarting after a shutdown until
an operator manually or remotely explicitly restarts
it. If the UPS is in a startup or reboot countdown,
then the UPS will not restart until that delay has
been satisfied.(*)
Parsed from file GE_PARALLELUPS.mib.txt
Company: ge
Module: GE_PARALLELUPS
Vendor: IMV Victron bv
Module: GE_PARALLELUPS
[Automatically extracted from oidview.com]
upsAutoRestart_third OBJECT-TYPE SYNTAX Integer32 { on(1), off(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Setting this object to 'on' will cause the UPS system to restart after a shutdown if the shutdown occurred during a power loss as a result of either a upsShutdownAfterDelay or an internal battery depleted condition. Setting this object to 'off' will prevent the UPS system from restarting after a shutdown until an operator manually or remotely explicitly restarts it. If the UPS is in a startup or reboot countdown, then the UPS will not restart until that delay has been satisfied.(*)" ::= { upsControl_third 5 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.818.1.1.13.8.5.0 | 0 | 0 | 0 | upsAutoRestart_third |
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.818.1.1.13.8.1 | upsShutdownType_third | 1 | 1 | This object determines the nature of the action to be taken at the time when the countdown of the upsShutdownAfterDelay and upsRe… |
1.3.6.1.4.1.818.1.1.13.8.2 | upsShutdownAfterDelay_third | 1 | 1 | Setting this object will shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShut… |
1.3.6.1.4.1.818.1.1.13.8.3 | upsStartupAfterDelay_third | 1 | 1 | Setting this object will start the output after the indicated number of seconds, including starting the UPS, if necessary. Setti… |
1.3.6.1.4.1.818.1.1.13.8.4 | upsRebootWithDuration_third | 1 | 1 | Setting this object will immediately shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the valu… |
1.3.6.1.4.1.818.1.1.13.8.6 | upsReceptaclesNum_third | 1 | 1 | The number of receptacles utilized in this device. This entry indicates the number of rows in the receptacle table. |
1.3.6.1.4.1.818.1.1.13.8.7 | upsReceptacleTable_third | 1 | 3 | A list of receptacle table entries. The number of entries is given by the value of upsReceptacleNum. |
1.3.6.1.4.1.818.1.1.13.8.8 | upsUPSMode_third | 1 | 1 | The operation mode off the UPS. Off-line indicates a mode in which the input power is transferred to the output directly or via a… |
1.3.6.1.4.1.818.1.1.13.8.9 | upsRectifierOnOff_third | 1 | 1 | The present state of the rectifier. Setting this object to 'on' will cause the rectifier to be turned on. Setting this object to … |
1.3.6.1.4.1.818.1.1.13.8.10 | upsBatteryChargeMethod_third | 1 | 1 | The present state of the charge method. Setting this object to 'Normal charge' will cause the battery to be charged using the nor… |
1.3.6.1.4.1.818.1.1.13.8.11 | upsInverterOnOff_third | 1 | 1 | The present state of the inverter. Setting this object to 'on' will cause the inverter to be turned on. Setting this object to 'o… |
1.3.6.1.4.1.818.1.1.13.8.12 | upsBypassOnOff_third | 1 | 1 | The present state of the bypass. Setting this object to 'on' will cause the bypass to be activated. Setting this object to 'off' … |
1.3.6.1.4.1.818.1.1.13.8.13 | upsLoadSource_third | 1 | 1 | The present source of the load. Setting this object to 'On bypass' will cause the load to be supplied by the bypass. Setting this … |