Vendor: IMV Victron bv
Module: GE_PARALLELUPS
[Automatically extracted from oidview.com]
upsControl_third OBJECT IDENTIFIER ::= { geThirdUPS 8 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.818.1.1.13.8.1 | upsShutdownType_third | 1 | 1 | This object determines the nature of the action to be taken at the time when the countdown of the upsShutdownAfterDelay and upsRe… |
1.3.6.1.4.1.818.1.1.13.8.2 | upsShutdownAfterDelay_third | 1 | 1 | Setting this object will shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShut… |
1.3.6.1.4.1.818.1.1.13.8.3 | upsStartupAfterDelay_third | 1 | 1 | Setting this object will start the output after the indicated number of seconds, including starting the UPS, if necessary. Setti… |
1.3.6.1.4.1.818.1.1.13.8.4 | upsRebootWithDuration_third | 1 | 1 | Setting this object will immediately shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the valu… |
1.3.6.1.4.1.818.1.1.13.8.5 | upsAutoRestart_third | 1 | 1 | Setting this object to 'on' will cause the UPS system to restart after a shutdown if the shutdown occurred during a power loss as… |
1.3.6.1.4.1.818.1.1.13.8.6 | upsReceptaclesNum_third | 1 | 1 | The number of receptacles utilized in this device. This entry indicates the number of rows in the receptacle table. |
1.3.6.1.4.1.818.1.1.13.8.7 | upsReceptacleTable_third | 1 | 3 | A list of receptacle table entries. The number of entries is given by the value of upsReceptacleNum. |
1.3.6.1.4.1.818.1.1.13.8.8 | upsUPSMode_third | 1 | 1 | The operation mode off the UPS. Off-line indicates a mode in which the input power is transferred to the output directly or via a… |
1.3.6.1.4.1.818.1.1.13.8.9 | upsRectifierOnOff_third | 1 | 1 | The present state of the rectifier. Setting this object to 'on' will cause the rectifier to be turned on. Setting this object to … |
1.3.6.1.4.1.818.1.1.13.8.10 | upsBatteryChargeMethod_third | 1 | 1 | The present state of the charge method. Setting this object to 'Normal charge' will cause the battery to be charged using the nor… |
1.3.6.1.4.1.818.1.1.13.8.11 | upsInverterOnOff_third | 1 | 1 | The present state of the inverter. Setting this object to 'on' will cause the inverter to be turned on. Setting this object to 'o… |
1.3.6.1.4.1.818.1.1.13.8.12 | upsBypassOnOff_third | 1 | 1 | The present state of the bypass. Setting this object to 'on' will cause the bypass to be activated. Setting this object to 'off' … |
1.3.6.1.4.1.818.1.1.13.8.13 | upsLoadSource_third | 1 | 1 | The present source of the load. Setting this object to 'On bypass' will cause the load to be supplied by the bypass. Setting this … |
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.818.1.1.13.1 | upsIdent_third | 9 | 18 | None |
1.3.6.1.4.1.818.1.1.13.2 | upsBattery_third | 7 | 14 | None |
1.3.6.1.4.1.818.1.1.13.3 | upsInput_third | 3 | 13 | None |
1.3.6.1.4.1.818.1.1.13.4 | upsOutput_third | 4 | 13 | None |
1.3.6.1.4.1.818.1.1.13.5 | upsBypass_third | 3 | 10 | None |
1.3.6.1.4.1.818.1.1.13.6 | upsAlarm_third | 4 | 35 | None |
1.3.6.1.4.1.818.1.1.13.7 | upsTest_third | 7 | 18 | None |
1.3.6.1.4.1.818.1.1.13.9 | upsConfig_third | 14 | 28 | None |
1.3.6.1.4.1.818.1.1.13.10 | upsGetSet_third | 24 | 54 | None |
1.3.6.1.4.1.818.1.1.13.11 | geUPSTraps_third | 51 | 51 | None |