nvramEnvAlert

1.3.6.1.4.1.19746.2.0.6505

Description

Description: The temperature sensor on the NVRAM card or the remote battery detected a temperature that is higher than the warning threshold. If there are other environmental alerts, this may indicate a cooling problem where the system is installed. If there are no other environmental alerts, this may indicate a probl…

Full description and source information

Identification

Identifier and names

Parent
1.3.6.1.4.1.19746.2.0 (dataDomainMibTraps)
Node code
6505
Node name
nvramEnvAlert
Category
SNMP notification
Numeric OID
1.3.6.1.4.1.19746.2.0.6505
URN notation
urn:oid:1.3.6.1.4.1.19746.2.0.6505
ASN.1, OID-IRI and named path variants
ASN.1 notation

{1 3 6 1 4 1 19746 2 0 6505}

  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) dataDomainMib(19746) dataDomainMibNotifications(2) dataDomainMibTraps(0) nvramEnvAlert(6505)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) dataDomainMib(19746) dataDomainMibNotifications(2) dataDomainMibTraps(0) nvramEnvAlert(6505)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) dataDomainMib(19746) dataDomainMibNotifications(2) dataDomainMibTraps(0) nvramEnvAlert(6505)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) vendor-objects(1) dataDomainMib(19746) dataDomainMibNotifications(2) dataDomainMibTraps(0) nvramEnvAlert(6505)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprise(1) dataDomainMib(19746) dataDomainMibNotifications(2) dataDomainMibTraps(0) nvramEnvAlert(6505)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) dataDomainMib(19746) dataDomainMibNotifications(2) dataDomainMibTraps(0) nvramEnvAlert(6505)}
  • {iso(1) org(3) dod(6) internet(1) private(4) ldap-enterprise(1) dataDomainMib(19746) dataDomainMibNotifications(2) dataDomainMibTraps(0) nvramEnvAlert(6505)}
  • {iso(1) org(3) dod(6) internet(1) private(4) vendor-objects(1) dataDomainMib(19746) dataDomainMibNotifications(2) dataDomainMibTraps(0) nvramEnvAlert(6505)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprise(1) dataDomainMib(19746) dataDomainMibNotifications(2) dataDomainMibTraps(0) nvramEnvAlert(6505)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprises(1) dataDomainMib(19746) dataDomainMibNotifications(2) dataDomainMibTraps(0) nvramEnvAlert(6505)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) dataDomainMib(19746) dataDomainMibNotifications(2) dataDomainMibTraps(0) nvramEnvAlert(6505)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) vendor-objects(1) dataDomainMib(19746) dataDomainMibNotifications(2) dataDomainMibTraps(0) nvramEnvAlert(6505)}
  • {iso(1) iso-organization(3) dod(6) internet(1) private(4) enterprise(1) dataDomainMib(19746) dataDomainMibNotifications(2) dataDomainMibTraps(0) nvramEnvAlert(6505)}
  • {iso(1) iso-organization(3) dod(6) internet(1) private(4) enterprises(1) dataDomainMib(19746) dataDomainMibNotifications(2) dataDomainMibTraps(0) nvramEnvAlert(6505)}
  • {iso(1) iso-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) dataDomainMib(19746) dataDomainMibNotifications(2) dataDomainMibTraps(0) nvramEnvAlert(6505)}
  • {iso(1) iso-organization(3) dod(6) internet(1) private(4) vendor-objects(1) dataDomainMib(19746) dataDomainMibNotifications(2) dataDomainMibTraps(0) nvramEnvAlert(6505)}
OID-IRI notation
  • /1/3/6/1/4/1/19746/2/0/6505
  • /ISO/Identified-Organization/6/1/4/1/19746/2/0/6505
  • /ISO/3/6/1/4/1/19746/2/0/6505
Named path variants
  • /iso/identified-organization/dod/internet/private/enterprise/dataDomainMib/dataDomainMibNotifications/dataDomainMibTraps/nvramEnvAlert
  • /iso/identified-organization/dod/internet/private/enterprises/dataDomainMib/dataDomainMibNotifications/dataDomainMibTraps/nvramEnvAlert
  • /iso/identified-organization/dod/internet/private/ldap-enterprise/dataDomainMib/dataDomainMibNotifications/dataDomainMibTraps/nvramEnvAlert
  • /iso/identified-organization/dod/internet/private/vendor-objects/dataDomainMib/dataDomainMibNotifications/dataDomainMibTraps/nvramEnvAlert
  • /iso/org/dod/internet/private/enterprise/dataDomainMib/dataDomainMibNotifications/dataDomainMibTraps/nvramEnvAlert
  • /iso/org/dod/internet/private/enterprises/dataDomainMib/dataDomainMibNotifications/dataDomainMibTraps/nvramEnvAlert
  • /iso/org/dod/internet/private/ldap-enterprise/dataDomainMib/dataDomainMibNotifications/dataDomainMibTraps/nvramEnvAlert
  • /iso/org/dod/internet/private/vendor-objects/dataDomainMib/dataDomainMibNotifications/dataDomainMibTraps/nvramEnvAlert
  • /iso/iso-identified-organization/dod/internet/private/enterprise/dataDomainMib/dataDomainMibNotifications/dataDomainMibTraps/nvramEnvAlert
  • /iso/iso-identified-organization/dod/internet/private/enterprises/dataDomainMib/dataDomainMibNotifications/dataDomainMibTraps/nvramEnvAlert
  • /iso/iso-identified-organization/dod/internet/private/ldap-enterprise/dataDomainMib/dataDomainMibNotifications/dataDomainMibTraps/nvramEnvAlert
  • /iso/iso-identified-organization/dod/internet/private/vendor-objects/dataDomainMib/dataDomainMibNotifications/dataDomainMibTraps/nvramEnvAlert
  • /iso/iso-organization/dod/internet/private/enterprise/dataDomainMib/dataDomainMibNotifications/dataDomainMibTraps/nvramEnvAlert
  • /iso/iso-organization/dod/internet/private/enterprises/dataDomainMib/dataDomainMibNotifications/dataDomainMibTraps/nvramEnvAlert
  • /iso/iso-organization/dod/internet/private/ldap-enterprise/dataDomainMib/dataDomainMibNotifications/dataDomainMibTraps/nvramEnvAlert
  • /iso/iso-organization/dod/internet/private/vendor-objects/dataDomainMib/dataDomainMibNotifications/dataDomainMibTraps/nvramEnvAlert

The displayed source records contain one distinct definition. Compare its source records.

nvramEnvAlert NOTIFICATION-TYPE
   OBJECTS { systemSerialNumber, alertInfoDescription }
STATUS current
   DESCRIPTION
   "Description: 
	The temperature sensor on the NVRAM card or the remote battery detected a temperature 
        that is higher than the warning threshold.  If there are other environmental alerts, 
        this may indicate a cooling problem where the system is installed.  
        If there are no other environmental alerts, this may indicate a problem with this component.  
        When the temperature is reduced, this alert will clear.
    
   Action: 
        Check cooling and airflow around the system unit.  Remove any blockage, or ensure 
        the environmental systems are operating correctly, and the environment is at a normal 
        temperature.  If there is no problem in the environment, or if only the NVRAM or 
        remote battery are reporting this problem, contact your contracted support provider or visit us online at https://support.emc.com.
    "
::= { dataDomainMibTraps 6505 }

Meaning

Descriptions

1 unique

Identical descriptions are grouped. Different wording and device-specific notes are retained.

Description: The temperature sensor on the NVRAM card or the remote battery detected a temperature that is higher than the warning threshold. If there are other environmental alerts, this may indicate a cooling problem where the system is installed. If there are no other environmental alerts, this may indicate a problem with this component. When the temperature is reduced, this alert will clear. Action: Check cooling and airflow around the system unit. Remove any blockage, or ensure the environmental systems are operating correctly, and the environment is at a normal temperature. If there is no problem in the environment, or if only the NVRAM or remote battery are reporting this problem, contact your contracted support provider or visit us online at https://support.emc.com.

Sources for this description

Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)

See 1 matching source record

Evidence

Source records

1 records

Matching descriptions are grouped; open a group to compare definitions and supporting files.

Records for description 1Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)1 record · 2 sources

Description 1

nvramEnvAlert · currentMultiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)2 sources

Status in source: current.

Names: nvramEnvAlert

Technical details
{
  "smi_kind": "NOTIFICATION-TYPE",
  "definition": [
    "nvramEnvAlert",
    "NOTIFICATION-TYPE",
    "OBJECTS",
    "{",
    "systemSerialNumber",
    ",",
    "alertInfoDescription",
    "}",
    "STATUS",
    "current",
    "DESCRIPTION",
    "\"Description: The temperature sensor on the NVRAM card or the remote battery detected a temperature that is higher than the warning threshold. If there are other environmental alerts, this may indicate a cooling problem where the system is installed. If there are no other environmental alerts, this may indicate a problem with this component. When the temperature is reduced, this alert will clear. Action: Check cooling and airflow around the system unit. Remove any blockage, or ensure the environmental systems are operating correctly, and the environment is at a normal temperature. If there is no problem in the environment, or if only the NVRAM or remote battery are reporting this problem, contact your contracted support provider or visit us online at https://support.emc.com. \"",
    "::=",
    "{",
    "dataDomainMibTraps",
    "6505",
    "}"
  ],
  "syntax_tree": [
    [
      "Objects",
      [
        "systemSerialNumber",
        "alertInfoDescription"
      ]
    ],
    [
      "Status",
      "current"
    ],
    [
      "DESCRIPTION",
      "Description: The temperature sensor on the NVRAM card or the remote battery detected a temperature that is higher than the warning threshold. If there are other environmental alerts, this may indicate a cooling problem where the system is installed. If there are no other environmental alerts, this may indicate a problem with this component. When the temperature is reduced, this alert will clear. Action: Check cooling and airflow around the system unit. Remove any blockage, or ensure the environmental systems are operating correctly, and the environment is at a normal temperature. If there is no problem in the environment, or if only the NVRAM or remote battery are reporting this problem, contact your contracted support provider or visit us online at https://support.emc.com."
    ],
    null
  ]
}

Registration

Registration authorities

First Registration Authority (inferred from ancestor 1.3.6.1.4.1.19746)

Haile J. Mitchell

Siblings (246)

OIDNameDirect childrenDescendantsDescription
1.3.6.1.4.1.19746.2.0.5079 coredumpDisabled00
1.3.6.1.4.1.19746.2.0.5080 spaceOver80Percent00
1.3.6.1.4.1.19746.2.0.5081 spaceOver90Percent00
1.3.6.1.4.1.19746.2.0.5082 diskAccessError00
1.3.6.1.4.1.19746.2.0.5083 diskFailure00
1.3.6.1.4.1.19746.2.0.5084 diskTemperatureWarning00
1.3.6.1.4.1.19746.2.0.5085 diskTemperatureShutdown00
1.3.6.1.4.1.19746.2.0.5086 unsupportedHardwareSpareSize00
1.3.6.1.4.1.19746.2.0.5087 missingDiskGroup00
1.3.6.1.4.1.19746.2.0.5088 diskGroupReconstructionNoProgress00
1.3.6.1.4.1.19746.2.0.5089 diskGroupReconstruction00
1.3.6.1.4.1.19746.2.0.5090 diskGroupReconstructionShutdown00
1.3.6.1.4.1.19746.2.0.5091 diskGroupReconstructionCritical00
1.3.6.1.4.1.19746.2.0.5092 diskUnknown00
1.3.6.1.4.1.19746.2.0.5094 lowSpares00
1.3.6.1.4.1.19746.2.0.5095 unsupportedConfigurationROL00
1.3.6.1.4.1.19746.2.0.5500 cpismissing00
1.3.6.1.4.1.19746.2.0.5501 containerMarkedInvalid00
1.3.6.1.4.1.19746.2.0.5502 smiMrc00
1.3.6.1.4.1.19746.2.0.5508 nvramBatteryLowChargeAlert00
1.3.6.1.4.1.19746.2.0.5527 ext3NvlogDisabled00
1.3.6.1.4.1.19746.2.0.5528 enclosureMixType00
1.3.6.1.4.1.19746.2.0.5531 replPathTooLong00
1.3.6.1.4.1.19746.2.0.6001 compromisedEncryptionKeys00
1.3.6.1.4.1.19746.2.0.6002 newEncryptionKey00
1.3.6.1.4.1.19746.2.0.6003 encryptionKeyTableFull00
1.3.6.1.4.1.19746.2.0.6004 uncertifiedFirmware00
1.3.6.1.4.1.19746.2.0.6005 filesystemNVRAMDataLoss00
1.3.6.1.4.1.19746.2.0.6007 mtreeQuotaSoftLimit00
1.3.6.1.4.1.19746.2.0.6008 mtreeQuotaHardLimit00
1.3.6.1.4.1.19746.2.0.6009 interfaceConnectivityDown00
1.3.6.1.4.1.19746.2.0.6010 interfaceConnectivityIntermittent00
1.3.6.1.4.1.19746.2.0.6011 interfaceMisconfiguration00
1.3.6.1.4.1.19746.2.0.6013 recoverFromNVRAMFailed00
1.3.6.1.4.1.19746.2.0.6014 cleaningError00
1.3.6.1.4.1.19746.2.0.6015 bMCPartialHang00
1.3.6.1.4.1.19746.2.0.6016 fileMigrationError00
1.3.6.1.4.1.19746.2.0.6017 unusableHostCertificate00
1.3.6.1.4.1.19746.2.0.6018 missingHostCertificate00
1.3.6.1.4.1.19746.2.0.6019 foreignEnclosure00
1.3.6.1.4.1.19746.2.0.6020 interfaceConnectivityUpAndRunning00
1.3.6.1.4.1.19746.2.0.6101 tcpZeroWindowAlert00
1.3.6.1.4.1.19746.2.0.6102 insecureEncryptedReplication00
1.3.6.1.4.1.19746.2.0.6504 nvramHWAlert00
1.3.6.1.4.1.19746.2.0.6506 nvramEventHWAlert00
1.3.6.1.4.1.19746.2.0.6507 nvramBattAlert00
1.3.6.1.4.1.19746.2.0.6508 nvramCondAlert00
1.3.6.1.4.1.19746.2.0.6509 upgradeFailure00
1.3.6.1.4.1.19746.2.0.6510 upgradeCompleted00
1.3.6.1.4.1.19746.2.0.6511 mailserverError00