setpoints OBJECT IDENTIFIER ::= { cmc 4 }
setpoints OBJECT IDENTIFIER ::= { cmc 4 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.2606.1.4.1 | setpointFan1 | 1 | 1 | Setpoint Fan 1 in C, Fan 1 will start if temperature 1 exceeds this value |
1.3.6.1.4.1.2606.1.4.2 | setpointFan2 | 1 | 1 | Setpoint Fan 2 in C, Fan 2 will start if temperature 2 exceeds this value |
1.3.6.1.4.1.2606.1.4.3 | setpointHeating | 1 | 1 | Setpoint heating in C, heating will start if lowest value of temperature 1 and 2 falls below this value |
1.3.6.1.4.1.2606.1.4.4 | setpointHighTemperature1 | 1 | 1 | setpointHightemperature1 |
1.3.6.1.4.1.2606.1.4.5 | setpointLowTemperature1 | 1 | 1 | Setpoint low value alarm temperature 1 |
1.3.6.1.4.1.2606.1.4.6 | setpointHighTemperature2 | 1 | 1 | setpointHightemperature2 |
1.3.6.1.4.1.2606.1.4.7 | setpointLowTemperature2 | 1 | 1 | Setpoint low value alarm temperature 2 |
1.3.6.1.4.1.2606.1.4.8 | setpointHighVoltage | 1 | 1 | Setpoint high value supply voltage alarm |
1.3.6.1.4.1.2606.1.4.9 | setpointLowVoltage | 1 | 1 | Setpoint low value supply voltage alarm |
1.3.6.1.4.1.2606.1.4.10 | setpointLowAux1 | 1 | 1 | Setpoint low value Aux input 1 alarm |
1.3.6.1.4.1.2606.1.4.11 | setpointHighAux1 | 1 | 1 | Setpoint high value Aux input 1 alarm |
1.3.6.1.4.1.2606.1.4.12 | setpointLowAux2 | 1 | 1 | Setpoint low value Aux input 2 alarm |
1.3.6.1.4.1.2606.1.4.13 | setpointHighAux2 | 1 | 1 | Setpoint high value Aux input alarm |
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.2606.1.1 | values | 6 | 21 | None |
1.3.6.1.4.1.2606.1.2 | status | 18 | 42 | None |
1.3.6.1.4.1.2606.1.3 | set | 6 | 18 | None |
1.3.6.1.4.1.2606.1.5 | trapControl | 4 | 14 | None |