When the line-to-neutral voltage of any phase drops below this value a critical alarm will exist.
Specified as a percent of the nominal voltage, isxModularDistSysOutputVoltageNominalLineToNeutral.
This value is returned as a positive number which represents a negative percentage.
A value of -1 indicates that the threshold is not available in the device.
Parsed from file powernet.mib.txt
Company: None
Module: PowerNet-MIB
When the line-to-neutral voltage of any phase drops below this value a critical alarm will exist.
Specified as a percent of the nominal voltage, isxModularDistSysOutputVoltageNominalLineToNeutral.
A value of -1 indicates that the threshold is not available in the device.
Parsed from file PowerNet-MIB.mib
Module: PowerNet-MIB
isxModularDistSysOutputVoltageThresholdMin OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "When the line-to-neutral voltage of any phase drops below this value a critical alarm will exist. Specified as a percent of the nominal voltage, isxModularDistSysOutputVoltageNominalLineToNeutral. This value is returned as a positive number which represents a negative percentage. A value of -1 indicates that the threshold is not available in the device." ::= { isxModularDistSysVoltage 6 }
Vendor: American Power Conversion Corp.
Module: PowerNet-MIB
[Automatically extracted from oidview.com]
isxModularDistSysOutputVoltageThresholdMin OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "When the line-to-neutral voltage of any phase drops below this value a critical alarm will exist. Specified as a percent of the nominal voltage, isxModularDistSysOutputVoltageNominalLineToNeutral. A value of -1 indicates that the threshold is not available in the device." ::= { isxModularDistSysVoltage 6 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.22.4.1.6.0 | isxModularDistSysOutputVoltageThresholdMin | 0 | 0 | None |
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.22.4.1.1 | isxModularDistSysOutputVoltageNominalLineToNeutral | 1 | 1 | The nominal line-to-neutral voltage available at the distribution panel. |
1.3.6.1.4.1.318.1.1.22.4.1.2 | isxModularDistSysOutputVoltageNominalLineToLine | 1 | 1 | The nominal line-to-line voltage available at the distribution panel. |
1.3.6.1.4.1.318.1.1.22.4.1.3 | isxModularDistSysOutputNominalFrequency | 1 | 1 | The nominal system output frequency. Measured in tenths of Hertz. |
1.3.6.1.4.1.318.1.1.22.4.1.4 | isxModularDistSysOutputFrequency | 1 | 1 | The system output frequency in tenths of Hertz. -1 if not available. |
1.3.6.1.4.1.318.1.1.22.4.1.5 | isxModularDistSysOutputVoltageMonitoring | 1 | 1 | Indicates whether or not output voltage alarm generation is present. |
1.3.6.1.4.1.318.1.1.22.4.1.7 | isxModularDistSysOutputVoltageThresholdLow | 1 | 1 | When the line-to-neutral voltage of any phase drops below this value a warning alarm will exist. Specified as a percent of the n… |
1.3.6.1.4.1.318.1.1.22.4.1.8 | isxModularDistSysOutputVoltageThresholdHigh | 1 | 1 | When the line-to-neutral voltage of any phase exceeds this value a warning alarm will exist. Specified as a percent of the nomin… |
1.3.6.1.4.1.318.1.1.22.4.1.9 | isxModularDistSysOutputVoltageThresholdMax | 1 | 1 | When the line-to-neutral voltage of any phase exceeds this value a critical alarm will exist. Specified as a percent of the nomi… |
1.3.6.1.4.1.318.1.1.22.4.1.10 | isxModularDistSysOutputVoltageAlarmMinEnable | 1 | 1 | Enable or disable minimum voltage alarm generation for the distribution panel. |
1.3.6.1.4.1.318.1.1.22.4.1.11 | isxModularDistSysOutputVoltageAlarmLowEnable | 1 | 1 | Enable or disable low voltage alarm generation for the distribution panel. |
1.3.6.1.4.1.318.1.1.22.4.1.12 | isxModularDistSysOutputVoltageAlarmHighEnable | 1 | 1 | Enable or disable high voltage alarm generation for the distribution panel. |
1.3.6.1.4.1.318.1.1.22.4.1.13 | isxModularDistSysOutputVoltageAlarmMaxEnable | 1 | 1 | Enable or disable maximum voltage alarm generation for the distribution panel. |
1.3.6.1.4.1.318.1.1.22.4.1.14 | isxModularDistSysOutputVoltageFrequencyTolerance | 1 | 1 | The circuit panel output frequency tolerance in Hertz. When the system output frequency deviates from the nominal by more than t… |
1.3.6.1.4.1.318.1.1.22.4.1.15 | isxModularDistSysVoltageTable | 1 | 5 | Allows for getting the system output voltage information. |