Configuration data from temperature-humidity sensor
being queried
Parsed from file powernet.mib.txt
Company: None
Module: PowerNet-MIB
Configuration data from temperature-humidity sensor
being queried
Parsed from file PowerNet-MIB.mib
Module: PowerNet-MIB
rPDU2SensorTempHumidityConfigEntry OBJECT-TYPE SYNTAX RPDU2SensorTempHumidityConfigEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Configuration data from temperature-humidity sensor being queried" INDEX { rPDU2SensorTempHumidityConfigIndex } ::= { rPDU2SensorTempHumidityConfigTable 1 }
Vendor: APC
Module: PowerNet-MIB (powernet401.mib)
Type: ENTRY
Access: not-accessible
Syntax: RPDU2SensorTempHumidityConfigEntry
Automatically extracted from www.mibdepot.com
rPDU2SensorTempHumidityConfigEntry OBJECT-TYPE SYNTAX RPDU2SensorTempHumidityConfigEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Configuration data from temperature-humidity sensor being queried" INDEX { rPDU2SensorTempHumidityConfigIndex } ::= { rPDU2SensorTempHumidityConfigTable 1 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.26.10.2.1.1.1 | rPDU2SensorTempHumidityConfigIndex | 0 | 0 | The index to the temperature-humidity sensor configuration data table entry |
1.3.6.1.4.1.318.1.1.26.10.2.1.1.2 | rPDU2SensorTempHumidityConfigModule | 0 | 0 | The user-defined Rack PDU numeric ID |
1.3.6.1.4.1.318.1.1.26.10.2.1.1.3 | rPDU2SensorTempHumidityConfigName | 0 | 0 | The user-defined temperature-humidity sensor ID string |
1.3.6.1.4.1.318.1.1.26.10.2.1.1.4 | rPDU2SensorTempHumidityConfigNumber | 0 | 0 | The temperature-humidity sensor numeric ID |
1.3.6.1.4.1.318.1.1.26.10.2.1.1.5 | rPDU2SensorTempHumidityConfigTemperatureAlarmEnable | 0 | 0 | Setting this OID enables or disables generation of sensor temperature alarm. Getting this OID returns the current value of the tem… |
1.3.6.1.4.1.318.1.1.26.10.2.1.1.6 | rPDU2SensorTempHumidityConfigHumidityAlarmEnable | 0 | 0 | Setting this OID enables or disables generation of sensor humidity alarm. Getting this OID returns the current value of the humidi… |
1.3.6.1.4.1.318.1.1.26.10.2.1.1.7 | rPDU2SensorTempHumidityConfigTempMaxThreshF | 0 | 0 | Sensor maximum temperature alarm threshold in Fahrenheit. Attempting to set this OID to a value less than or equal to that of rPDU… |
1.3.6.1.4.1.318.1.1.26.10.2.1.1.8 | rPDU2SensorTempHumidityConfigTempHighThreshF | 0 | 0 | rPDU2SensorTempHumidityConfigTempHighthreshF |
1.3.6.1.4.1.318.1.1.26.10.2.1.1.9 | rPDU2SensorTempHumidityConfigTempHysteresisF | 0 | 0 | Sensor temperature hysteresis setting in Fahrenheit |
1.3.6.1.4.1.318.1.1.26.10.2.1.1.10 | rPDU2SensorTempHumidityConfigTempMaxThreshC | 0 | 0 | Sensor maximum temperature alarm threshold in Celsius. Attempting to set this OID to a value less than or equal to that of rPDU2Se… |
1.3.6.1.4.1.318.1.1.26.10.2.1.1.11 | rPDU2SensorTempHumidityConfigTempHighThreshC | 0 | 0 | rPDU2SensorTempHumidityConfigTempHighthreshC |
1.3.6.1.4.1.318.1.1.26.10.2.1.1.12 | rPDU2SensorTempHumidityConfigTempHysteresisC | 0 | 0 | Sensor temperature hysteresis setting in Celsius |
1.3.6.1.4.1.318.1.1.26.10.2.1.1.13 | rPDU2SensorTempHumidityConfigHumidityLowThresh | 0 | 0 | Sensor low humidity warning alarm threshold in percent relative humidity. Attempting to set this OID to a value less than or equa… |
1.3.6.1.4.1.318.1.1.26.10.2.1.1.14 | rPDU2SensorTempHumidityConfigHumidityMinThresh | 0 | 0 | Sensor minimum humidity alarm threshold in percent relative humidity. Attempting to set this OID to a value greater than or equal… |
1.3.6.1.4.1.318.1.1.26.10.2.1.1.15 | rPDU2SensorTempHumidityConfigHumidityHysteresis | 0 | 0 | Sensor humidity hysteresis setting in percent relative humidity |