Reference record for OID 1.3.6.1.4.1.318.1.1.26.4.4.1.4



parent
1.3.6.1.4.1.318.1.1.26.4.4.1 (rPDU2DeviceControlEntry)
node code
4
node name
rPDU2DeviceControlCommand
dot oid
1.3.6.1.4.1.318.1.1.26.4.4.1.4
type
OBJECT-TYPE
asn1 oid
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) rPDU2(26) rPDU2Device(4) rPDU2DeviceControlTable(4) rPDU2DeviceControlEntry(1) rPDU2DeviceControlCommand(4)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) rPDU2(26) rPDU2Device(4) rPDU2DeviceControlTable(4) rPDU2DeviceControlEntry(1) rPDU2DeviceControlCommand(4)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) rPDU2(26) rPDU2Device(4) rPDU2DeviceControlTable(4) rPDU2DeviceControlEntry(1) rPDU2DeviceControlCommand(4)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) rPDU2(26) rPDU2Device(4) rPDU2DeviceControlTable(4) rPDU2DeviceControlEntry(1) rPDU2DeviceControlCommand(4)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) rPDU2(26) rPDU2Device(4) rPDU2DeviceControlTable(4) rPDU2DeviceControlEntry(1) rPDU2DeviceControlCommand(4)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) rPDU2(26) rPDU2Device(4) rPDU2DeviceControlTable(4) rPDU2DeviceControlEntry(1) rPDU2DeviceControlCommand(4)}
  • iri oid
  • /iso/identified-organization/dod/internet/private/enterprise/apc/products/hardware/rPDU2/rPDU2Device/rPDU2DeviceControlTable/rPDU2DeviceControlEntry/rPDU2DeviceControlCommand
  • /iso/identified-organization/dod/internet/private/enterprises/apc/products/hardware/rPDU2/rPDU2Device/rPDU2DeviceControlTable/rPDU2DeviceControlEntry/rPDU2DeviceControlCommand
  • /iso/org/dod/internet/private/enterprise/apc/products/hardware/rPDU2/rPDU2Device/rPDU2DeviceControlTable/rPDU2DeviceControlEntry/rPDU2DeviceControlCommand
  • /iso/org/dod/internet/private/enterprises/apc/products/hardware/rPDU2/rPDU2Device/rPDU2DeviceControlTable/rPDU2DeviceControlEntry/rPDU2DeviceControlCommand
  • /iso/iso-identified-organization/dod/internet/private/enterprise/apc/products/hardware/rPDU2/rPDU2Device/rPDU2DeviceControlTable/rPDU2DeviceControlEntry/rPDU2DeviceControlCommand
  • /iso/iso-identified-organization/dod/internet/private/enterprises/apc/products/hardware/rPDU2/rPDU2Device/rPDU2DeviceControlTable/rPDU2DeviceControlEntry/rPDU2DeviceControlCommand
  • iri by oid_info
    /ISO/Identified-Organization/6/1/4/1/318/1/1/26/4/4/1/4

    Description by mibdepot

    Setting this OID to immediateAllOn (1) will turn all outlets
    on immediately.

    Setting this OID to delayedAllOn (2) will turn all outlets on as
    defined by each outlet's rPDU2OutletSwitchedConfigPowerOnTime
    OID value.

    Setting this OID to immediateAllOff (3) will turn all outlets
    off immediately.

    Setting this OID to immediateAllReboot (4) will cause an immediateAllOff
    command to be performed. Once all outlets are off, the
    Switched Rack PDU will then delay the
    rPDU2OutletSwitchedConfigRebootDuration OID time, and then perform an
    immediateAllOn command.

    Setting this OID to delayedAllReboot (5) will cause a
    delayedAllOff command to be performed. Once all outlets are off,
    the Switched Rack PDU will then delay the largest
    rPDU2OutletSwitchedConfigRebootDuration OID time, and then perform a
    delayedAllOn command.

    Setting this OID to noCommandAll (6) will have no effect.

    Setting this OID to delayedAllOff (7) will turn all outlets off
    as defined by each outlet's rPDU2OutletSwitchedConfigPowerOffTime
    OID value.

    Setting this OID to cancelAllPendingCommands (8) will cause all pending
    commands on the Switched Rack PDU to be cancelled.

    Getting this OID will return the noCommandAll (6)
    value.

    Parsed from file powernet.mib.txt
    Company: None
    Module: PowerNet-MIB

    Description by circitor

    Setting this OID to immediateAllOn (1) will turn all outlets
    on immediately.

    Setting this OID to delayedAllOn (2) will turn all outlets on as
    defined by each outlet's rPDU2OutletSwitchedConfigPowerOnTime
    OID value.

    Setting this OID to immediateAllOff (3) will turn all outlets
    off immediately.

    Setting this OID to immediateAllReboot (4) will cause an immediateAllOff
    command to be performed. Once all outlets are off, the
    Switched Rack PDU will then delay the
    rPDU2OutletSwitchedConfigRebootDuration OID time, and then perform an
    immediateAllOn command.

    Setting this OID to delayedAllReboot (5) will cause a
    delayedAllOff command to be performed. Once all outlets are off,
    the Switched Rack PDU will then delay the largest
    rPDU2OutletSwitchedConfigRebootDuration OID time, and then perform a
    delayedAllOn command.

    Setting this OID to noCommandAll (6) will have no effect.

    Setting this OID to delayedAllOff (7) will turn all outlets off
    as defined by each outlet's rPDU2OutletSwitchedConfigPowerOffTime
    OID value.

    Setting this OID to cancelAllPendingCommands (8) will cause all pending
    commands on the Switched Rack PDU to be cancelled.

    Getting this OID will return the noCommandAll (6)
    value.

    Parsed from file PowerNet-MIB.mib
    Module: PowerNet-MIB

    Information by mibdepot

    rPDU2DeviceControlCommand OBJECT-TYPE SYNTAX INTEGER { immediateAllOn (1), delayedAllOn (2), immediateAllOff (3), immediateAllReboot (4), delayedAllReboot (5), noCommandAll (6), delayedAllOff (7), cancelAllPendingCommands (8) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this OID to immediateAllOn (1) will turn all outlets on immediately. Setting this OID to delayedAllOn (2) will turn all outlets on as defined by each outlet's rPDU2OutletSwitchedConfigPowerOnTime OID value. Setting this OID to immediateAllOff (3) will turn all outlets off immediately. Setting this OID to immediateAllReboot (4) will cause an immediateAllOff command to be performed. Once all outlets are off, the Switched Rack PDU will then delay the rPDU2OutletSwitchedConfigRebootDuration OID time, and then perform an immediateAllOn command. Setting this OID to delayedAllReboot (5) will cause a delayedAllOff command to be performed. Once all outlets are off, the Switched Rack PDU will then delay the largest rPDU2OutletSwitchedConfigRebootDuration OID time, and then perform a delayedAllOn command. Setting this OID to noCommandAll (6) will have no effect. Setting this OID to delayedAllOff (7) will turn all outlets off as defined by each outlet's rPDU2OutletSwitchedConfigPowerOffTime OID value. Setting this OID to cancelAllPendingCommands (8) will cause all pending commands on the Switched Rack PDU to be cancelled. Getting this OID will return the noCommandAll (6) value." ::= { rPDU2DeviceControlEntry 4 }

    Information by oid_info

    Vendor: APC
    Module: PowerNet-MIB (powernet401.mib)
    Type: TABULAR
    Access: read-write
    Syntax: INTEGER

    Automatically extracted from www.mibdepot.com

    Information by circitor

    rPDU2DeviceControlCommand OBJECT-TYPE SYNTAX INTEGER { immediateAllOn (1), delayedAllOn (2), immediateAllOff (3), immediateAllReboot (4), delayedAllReboot (5), noCommandAll (6), delayedAllOff (7), cancelAllPendingCommands (8) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this OID to immediateAllOn (1) will turn all outlets on immediately. Setting this OID to delayedAllOn (2) will turn all outlets on as defined by each outlet's rPDU2OutletSwitchedConfigPowerOnTime OID value. Setting this OID to immediateAllOff (3) will turn all outlets off immediately. Setting this OID to immediateAllReboot (4) will cause an immediateAllOff command to be performed. Once all outlets are off, the Switched Rack PDU will then delay the rPDU2OutletSwitchedConfigRebootDuration OID time, and then perform an immediateAllOn command. Setting this OID to delayedAllReboot (5) will cause a delayedAllOff command to be performed. Once all outlets are off, the Switched Rack PDU will then delay the largest rPDU2OutletSwitchedConfigRebootDuration OID time, and then perform a delayedAllOn command. Setting this OID to noCommandAll (6) will have no effect. Setting this OID to delayedAllOff (7) will turn all outlets off as defined by each outlet's rPDU2OutletSwitchedConfigPowerOffTime OID value. Setting this OID to cancelAllPendingCommands (8) will cause all pending commands on the Switched Rack PDU to be cancelled. Getting this OID will return the noCommandAll (6) value." ::= { rPDU2DeviceControlEntry 4 }

    First Registration Authority (recovered by parent 1.3.6.1.4.1.318)

    Yoest Peter C.

    Brothers (3)

    OIDNameSub childrenSub Nodes TotalDescription
    1.3.6.1.4.1.318.1.1.26.4.4.1.1 rPDU2DeviceControlIndex 0 0 The index to the Rack PDU control table entry
    1.3.6.1.4.1.318.1.1.26.4.4.1.2 rPDU2DeviceControlModule 0 0 The user-defined Rack PDU numeric ID
    1.3.6.1.4.1.318.1.1.26.4.4.1.3 rPDU2DeviceControlName 0 0 A user-defined string identifying the Rack PDU