Setting this OID to immediateAllOn (1) will turn all outlets
on immediately.
Setting this OID to delayedAllOn (2) will turn all outlets on as
defined by each outlet's rPDU2OutletSwitchedConfigPowerOnTime
OID value.
Setting this OID to immediateAllOff (3) will turn all outlets
off immediately.
Setting this OID to immediateAllReboot (4) will cause an immediateAllOff
command to be performed. Once all outlets are off, the
Switched Rack PDU will then delay the
rPDU2OutletSwitchedConfigRebootDuration OID time, and then perform an
immediateAllOn command.
Setting this OID to delayedAllReboot (5) will cause a
delayedAllOff command to be performed. Once all outlets are off,
the Switched Rack PDU will then delay the largest
rPDU2OutletSwitchedConfigRebootDuration OID time, and then perform a
delayedAllOn command.
Setting this OID to noCommandAll (6) will have no effect.
Setting this OID to delayedAllOff (7) will turn all outlets off
as defined by each outlet's rPDU2OutletSwitchedConfigPowerOffTime
OID value.
Setting this OID to cancelAllPendingCommands (8) will cause all pending
commands on the Switched Rack PDU to be cancelled.
Getting this OID will return the noCommandAll (6)
value.
Parsed from file powernet.mib.txt
Company: None
Module: PowerNet-MIB
Setting this OID to immediateAllOn (1) will turn all outlets
on immediately.
Setting this OID to delayedAllOn (2) will turn all outlets on as
defined by each outlet's rPDU2OutletSwitchedConfigPowerOnTime
OID value.
Setting this OID to immediateAllOff (3) will turn all outlets
off immediately.
Setting this OID to immediateAllReboot (4) will cause an immediateAllOff
command to be performed. Once all outlets are off, the
Switched Rack PDU will then delay the
rPDU2OutletSwitchedConfigRebootDuration OID time, and then perform an
immediateAllOn command.
Setting this OID to delayedAllReboot (5) will cause a
delayedAllOff command to be performed. Once all outlets are off,
the Switched Rack PDU will then delay the largest
rPDU2OutletSwitchedConfigRebootDuration OID time, and then perform a
delayedAllOn command.
Setting this OID to noCommandAll (6) will have no effect.
Setting this OID to delayedAllOff (7) will turn all outlets off
as defined by each outlet's rPDU2OutletSwitchedConfigPowerOffTime
OID value.
Setting this OID to cancelAllPendingCommands (8) will cause all pending
commands on the Switched Rack PDU to be cancelled.
Getting this OID will return the noCommandAll (6)
value.
Parsed from file PowerNet-MIB.mib
Module: PowerNet-MIB
rPDU2DeviceControlCommand OBJECT-TYPE SYNTAX INTEGER { immediateAllOn (1), delayedAllOn (2), immediateAllOff (3), immediateAllReboot (4), delayedAllReboot (5), noCommandAll (6), delayedAllOff (7), cancelAllPendingCommands (8) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this OID to immediateAllOn (1) will turn all outlets on immediately. Setting this OID to delayedAllOn (2) will turn all outlets on as defined by each outlet's rPDU2OutletSwitchedConfigPowerOnTime OID value. Setting this OID to immediateAllOff (3) will turn all outlets off immediately. Setting this OID to immediateAllReboot (4) will cause an immediateAllOff command to be performed. Once all outlets are off, the Switched Rack PDU will then delay the rPDU2OutletSwitchedConfigRebootDuration OID time, and then perform an immediateAllOn command. Setting this OID to delayedAllReboot (5) will cause a delayedAllOff command to be performed. Once all outlets are off, the Switched Rack PDU will then delay the largest rPDU2OutletSwitchedConfigRebootDuration OID time, and then perform a delayedAllOn command. Setting this OID to noCommandAll (6) will have no effect. Setting this OID to delayedAllOff (7) will turn all outlets off as defined by each outlet's rPDU2OutletSwitchedConfigPowerOffTime OID value. Setting this OID to cancelAllPendingCommands (8) will cause all pending commands on the Switched Rack PDU to be cancelled. Getting this OID will return the noCommandAll (6) value." ::= { rPDU2DeviceControlEntry 4 }
Vendor: APC
Module: PowerNet-MIB (powernet401.mib)
Type: TABULAR
Access: read-write
Syntax: INTEGER
Automatically extracted from www.mibdepot.com
rPDU2DeviceControlCommand OBJECT-TYPE SYNTAX INTEGER { immediateAllOn (1), delayedAllOn (2), immediateAllOff (3), immediateAllReboot (4), delayedAllReboot (5), noCommandAll (6), delayedAllOff (7), cancelAllPendingCommands (8) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this OID to immediateAllOn (1) will turn all outlets on immediately. Setting this OID to delayedAllOn (2) will turn all outlets on as defined by each outlet's rPDU2OutletSwitchedConfigPowerOnTime OID value. Setting this OID to immediateAllOff (3) will turn all outlets off immediately. Setting this OID to immediateAllReboot (4) will cause an immediateAllOff command to be performed. Once all outlets are off, the Switched Rack PDU will then delay the rPDU2OutletSwitchedConfigRebootDuration OID time, and then perform an immediateAllOn command. Setting this OID to delayedAllReboot (5) will cause a delayedAllOff command to be performed. Once all outlets are off, the Switched Rack PDU will then delay the largest rPDU2OutletSwitchedConfigRebootDuration OID time, and then perform a delayedAllOn command. Setting this OID to noCommandAll (6) will have no effect. Setting this OID to delayedAllOff (7) will turn all outlets off as defined by each outlet's rPDU2OutletSwitchedConfigPowerOffTime OID value. Setting this OID to cancelAllPendingCommands (8) will cause all pending commands on the Switched Rack PDU to be cancelled. Getting this OID will return the noCommandAll (6) value." ::= { rPDU2DeviceControlEntry 4 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.26.4.4.1.1 | rPDU2DeviceControlIndex | 0 | 0 | The index to the Rack PDU control table entry |
1.3.6.1.4.1.318.1.1.26.4.4.1.2 | rPDU2DeviceControlModule | 0 | 0 | The user-defined Rack PDU numeric ID |
1.3.6.1.4.1.318.1.1.26.4.4.1.3 | rPDU2DeviceControlName | 0 | 0 | A user-defined string identifying the Rack PDU |