Reference record for OID 1.3.6.1.4.1.318.1.1.6.2.2.1.3



parent
1.3.6.1.4.1.318.1.1.6.2.2.1 (sPDUMasterControlMSPEntry)
node code
3
node name
sPDUMasterControlMSPCommand
dot oid
1.3.6.1.4.1.318.1.1.6.2.2.1.3
type
OBJECT-TYPE
asn1 oid
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) masterswitchMSP(6) sPDUMasterControlMSP(2) sPDUMasterControlMSPTable(2) sPDUMasterControlMSPEntry(1) sPDUMasterControlMSPCommand(3)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) masterswitchMSP(6) sPDUMasterControlMSP(2) sPDUMasterControlMSPTable(2) sPDUMasterControlMSPEntry(1) sPDUMasterControlMSPCommand(3)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) masterswitchMSP(6) sPDUMasterControlMSP(2) sPDUMasterControlMSPTable(2) sPDUMasterControlMSPEntry(1) sPDUMasterControlMSPCommand(3)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) masterswitchMSP(6) sPDUMasterControlMSP(2) sPDUMasterControlMSPTable(2) sPDUMasterControlMSPEntry(1) sPDUMasterControlMSPCommand(3)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) masterswitchMSP(6) sPDUMasterControlMSP(2) sPDUMasterControlMSPTable(2) sPDUMasterControlMSPEntry(1) sPDUMasterControlMSPCommand(3)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) masterswitchMSP(6) sPDUMasterControlMSP(2) sPDUMasterControlMSPTable(2) sPDUMasterControlMSPEntry(1) sPDUMasterControlMSPCommand(3)}
  • iri oid
  • /iso/identified-organization/dod/internet/private/enterprise/apc/products/hardware/masterswitchMSP/sPDUMasterControlMSP/sPDUMasterControlMSPTable/sPDUMasterControlMSPEntry/sPDUMasterControlMSPCommand
  • /iso/identified-organization/dod/internet/private/enterprises/apc/products/hardware/masterswitchMSP/sPDUMasterControlMSP/sPDUMasterControlMSPTable/sPDUMasterControlMSPEntry/sPDUMasterControlMSPCommand
  • /iso/org/dod/internet/private/enterprise/apc/products/hardware/masterswitchMSP/sPDUMasterControlMSP/sPDUMasterControlMSPTable/sPDUMasterControlMSPEntry/sPDUMasterControlMSPCommand
  • /iso/org/dod/internet/private/enterprises/apc/products/hardware/masterswitchMSP/sPDUMasterControlMSP/sPDUMasterControlMSPTable/sPDUMasterControlMSPEntry/sPDUMasterControlMSPCommand
  • /iso/iso-identified-organization/dod/internet/private/enterprise/apc/products/hardware/masterswitchMSP/sPDUMasterControlMSP/sPDUMasterControlMSPTable/sPDUMasterControlMSPEntry/sPDUMasterControlMSPCommand
  • /iso/iso-identified-organization/dod/internet/private/enterprises/apc/products/hardware/masterswitchMSP/sPDUMasterControlMSP/sPDUMasterControlMSPTable/sPDUMasterControlMSPEntry/sPDUMasterControlMSPCommand
  • iri by oid_info
    /ISO/Identified-Organization/6/1/4/1/318/1/1/6/2/2/1/3

    Description by mibdepot

    Setting this OID to immediateAllOnMSP (2) will turn all outlets
    on immediately.

    Setting this OID to sequencedAllOnMSP (3) will turn all outlets
    on as defined by each outlet's sPDUOutletConfigMSPPowerOnDelay OID value.

    Setting this OID to immediateAllOffMSP (4) will turn all outlets
    off immediately.

    Setting this OID to gracefulAllRebootMSP (5) will reboot all outlets
    (after the device running PowerChute confirms shutdown) as defined
    by each outlet's sPDUOutletConfigMSPRebootDuration OID time value.

    Setting this OID to immediateAllRebootMSP (6) will reboot all outlets
    immediately.

    Setting this OID to gracefulAllShutdownMSP (7) will shutdown all outlets
    (after the device running PowerChute confirms shutdown) as defined
    by each outlet's sPDUOutletConfigMSPPowerOffDelay OID time value. Each
    outlet will then turn on after the sum of its
    sPDUOutletConfigMSPRestartDelay and sPDUOutletConfigMSPPowerOnDelay OID
    values.

    Setting this OID to overrideAllBatCapThreshMSP (8) will cause the
    outlet to ignore the Battery Capacity Threshold and proceed turning on
    the outlets as defined by each outlet's sPDUOutletConfigMSPPowerOnDelay
    OID value.

    Setting this OID to cancelAllPendingCommandsMSP (9) will cause all pending
    commands on the MasterSwitch plus to be canceled.

    Setting this OID to restoreFactoryDefaultsMSP (10) will cause the settings of
    the MasterSwitch plus to be restored to the factory defaults.

    Getting this OID will return the noCommandAllMSP (1) value.

    Parsed from file powernet.mib.txt
    Company: None
    Module: PowerNet-MIB

    Description by circitor

    Setting this OID to immediateAllOnMSP (2) will turn all outlets
    on immediately.

    Setting this OID to sequencedAllOnMSP (3) will turn all outlets
    on as defined by each outlet's sPDUOutletConfigMSPPowerOnDelay OID value.

    Setting this OID to immediateAllOffMSP (4) will turn all outlets
    off immediately.

    Setting this OID to gracefulAllRebootMSP (5) will reboot all outlets
    (after the device running PowerChute confirms shutdown) as defined
    by each outlet's sPDUOutletConfigMSPRebootDuration OID time value.

    Setting this OID to immediateAllRebootMSP (6) will reboot all outlets
    immediately.

    Setting this OID to gracefulAllShutdownMSP (7) will shutdown all outlets
    (after the device running PowerChute confirms shutdown) as defined
    by each outlet's sPDUOutletConfigMSPPowerOffDelay OID time value. Each
    outlet will then turn on after the sum of its
    sPDUOutletConfigMSPRestartDelay and sPDUOutletConfigMSPPowerOnDelay OID
    values.

    Setting this OID to overrideAllBatCapThreshMSP (8) will cause the
    outlet to ignore the Battery Capacity Threshold and proceed turning on
    the outlets as defined by each outlet's sPDUOutletConfigMSPPowerOnDelay
    OID value.

    Setting this OID to cancelAllPendingCommandsMSP (9) will cause all pending
    commands on the MasterSwitch plus to be canceled.

    Setting this OID to restoreFactoryDefaultsMSP (10) will cause the settings of
    the MasterSwitch plus to be restored to the factory defaults.

    Getting this OID will return the noCommandAllMSP (1) value.

    Parsed from file PowerNet-MIB.mib
    Module: PowerNet-MIB

    Information by mibdepot

    sPDUMasterControlMSPCommand OBJECT-TYPE SYNTAX INTEGER { noCommandAllMSP (1), immediateAllOnMSP (2), sequencedAllOnMSP (3), immediateAllOffMSP (4), gracefulAllRebootMSP (5), immediateAllRebootMSP (6), gracefulAllShutdownMSP (7), overrideAllBatCapThreshMSP (8), cancelAllPendingCommandsMSP (9), restoreFactoryDefaultsMSP (10) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this OID to immediateAllOnMSP (2) will turn all outlets on immediately. Setting this OID to sequencedAllOnMSP (3) will turn all outlets on as defined by each outlet's sPDUOutletConfigMSPPowerOnDelay OID value. Setting this OID to immediateAllOffMSP (4) will turn all outlets off immediately. Setting this OID to gracefulAllRebootMSP (5) will reboot all outlets (after the device running PowerChute confirms shutdown) as defined by each outlet's sPDUOutletConfigMSPRebootDuration OID time value. Setting this OID to immediateAllRebootMSP (6) will reboot all outlets immediately. Setting this OID to gracefulAllShutdownMSP (7) will shutdown all outlets (after the device running PowerChute confirms shutdown) as defined by each outlet's sPDUOutletConfigMSPPowerOffDelay OID time value. Each outlet will then turn on after the sum of its sPDUOutletConfigMSPRestartDelay and sPDUOutletConfigMSPPowerOnDelay OID values. Setting this OID to overrideAllBatCapThreshMSP (8) will cause the outlet to ignore the Battery Capacity Threshold and proceed turning on the outlets as defined by each outlet's sPDUOutletConfigMSPPowerOnDelay OID value. Setting this OID to cancelAllPendingCommandsMSP (9) will cause all pending commands on the MasterSwitch plus to be canceled. Setting this OID to restoreFactoryDefaultsMSP (10) will cause the settings of the MasterSwitch plus to be restored to the factory defaults. Getting this OID will return the noCommandAllMSP (1) value." ::= { sPDUMasterControlMSPEntry 3 }

    Information by oid_info

    Vendor: American Power Conversion Corp.
    Module: PowerNet-MIB

    [Automatically extracted from oidview.com]

    Information by circitor

    sPDUMasterControlMSPCommand OBJECT-TYPE SYNTAX INTEGER { noCommandAllMSP (1), immediateAllOnMSP (2), sequencedAllOnMSP (3), immediateAllOffMSP (4), gracefulAllRebootMSP (5), immediateAllRebootMSP (6), gracefulAllShutdownMSP (7), overrideAllBatCapThreshMSP (8), cancelAllPendingCommandsMSP (9), restoreFactoryDefaultsMSP (10) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this OID to immediateAllOnMSP (2) will turn all outlets on immediately. Setting this OID to sequencedAllOnMSP (3) will turn all outlets on as defined by each outlet's sPDUOutletConfigMSPPowerOnDelay OID value. Setting this OID to immediateAllOffMSP (4) will turn all outlets off immediately. Setting this OID to gracefulAllRebootMSP (5) will reboot all outlets (after the device running PowerChute confirms shutdown) as defined by each outlet's sPDUOutletConfigMSPRebootDuration OID time value. Setting this OID to immediateAllRebootMSP (6) will reboot all outlets immediately. Setting this OID to gracefulAllShutdownMSP (7) will shutdown all outlets (after the device running PowerChute confirms shutdown) as defined by each outlet's sPDUOutletConfigMSPPowerOffDelay OID time value. Each outlet will then turn on after the sum of its sPDUOutletConfigMSPRestartDelay and sPDUOutletConfigMSPPowerOnDelay OID values. Setting this OID to overrideAllBatCapThreshMSP (8) will cause the outlet to ignore the Battery Capacity Threshold and proceed turning on the outlets as defined by each outlet's sPDUOutletConfigMSPPowerOnDelay OID value. Setting this OID to cancelAllPendingCommandsMSP (9) will cause all pending commands on the MasterSwitch plus to be canceled. Setting this OID to restoreFactoryDefaultsMSP (10) will cause the settings of the MasterSwitch plus to be restored to the factory defaults. Getting this OID will return the noCommandAllMSP (1) value." ::= { sPDUMasterControlMSPEntry 3 }

    First Registration Authority (recovered by parent 1.3.6.1.4.1.318)

    Yoest Peter C.

    Brothers (2)

    OIDNameSub childrenSub Nodes TotalDescription
    1.3.6.1.4.1.318.1.1.6.2.2.1.1 sPDUMasterControlMSPIndex 0 0 The index to the MasterSwitch plus entry.
    1.3.6.1.4.1.318.1.1.6.2.2.1.2 sPDUMasterControlMSPName 0 0 The name of the MasterSwitch plus. The maximum
    value is 23 characters. The name is set by
    using the sPDUMasterConfigMSPName OID.