The input voltage orientation:
1: unknown for this Source
2: singlePhase - phase 1 voltage is between Phase 1
and Neutral.
3: splitPhase - phase 1 voltage is between Phase 1 and
Neutral; phase 2 voltage is between Phase 2 and Neutral;
phase 3 voltage is between Phase 1 and Phase 2.
4: threePhasePhaseToNeutral - phase 1 voltage is between
Phase 1 and Neutral; phase 2 voltage is between Phase 2
and Neutral; phase 3 voltage is between Phase 3 and
Neutral.
5: threePhasePhaseToPhase - phase 1 voltage is between
Phase 1 and Phase 2; phase 2 voltage is between Phase 2
and Phase 3; phase 3 voltage is between Phase 3 and
Phase 1.
Parsed from file powernet.mib.txt
Company: None
Module: PowerNet-MIB
The input voltage orientation:
1: unknown for this Source
2: singlePhase - phase 1 voltage is between Phase 1
and Neutral.
3: splitPhase - phase 1 voltage is between Phase 1 and
Neutral; phase 2 voltage is between Phase 2 and Neutral;
phase 3 voltage is between Phase 1 and Phase 2.
4: threePhasePhaseToNeutral - phase 1 voltage is between
Phase 1 and Neutral; phase 2 voltage is between Phase 2
and Neutral; phase 3 voltage is between Phase 3 and
Neutral.
5: threePhasePhaseToPhase - phase 1 voltage is between
Phase 1 and Phase 2; phase 2 voltage is between Phase 2
and Phase 3; phase 3 voltage is between Phase 3 and
Phase 1.
Parsed from file PowerNet-MIB.mib
Module: PowerNet-MIB
atsInputVoltageOrientation OBJECT-TYPE SYNTAX INTEGER { unknown(1), singlePhase(2), splitPhase(3), threePhasePhaseToNeutral(4), threePhasePhaseToPhase(5) } ACCESS read-only STATUS mandatory DESCRIPTION "The input voltage orientation: 1: unknown for this Source 2: singlePhase - phase 1 voltage is between Phase 1 and Neutral. 3: splitPhase - phase 1 voltage is between Phase 1 and Neutral; phase 2 voltage is between Phase 2 and Neutral; phase 3 voltage is between Phase 1 and Phase 2. 4: threePhasePhaseToNeutral - phase 1 voltage is between Phase 1 and Neutral; phase 2 voltage is between Phase 2 and Neutral; phase 3 voltage is between Phase 3 and Neutral. 5: threePhasePhaseToPhase - phase 1 voltage is between Phase 1 and Phase 2; phase 2 voltage is between Phase 2 and Phase 3; phase 3 voltage is between Phase 3 and Phase 1." ::= { atsInputEntry 3 }
Vendor: American Power Conversion Corp.
Module: PowerNet-MIB
[Automatically extracted from oidview.com]
atsInputVoltageOrientation OBJECT-TYPE SYNTAX INTEGER { unknown(1), singlePhase(2), splitPhase(3), threePhasePhaseToNeutral(4), threePhasePhaseToPhase(5) } ACCESS read-only STATUS mandatory DESCRIPTION "The input voltage orientation: 1: unknown for this Source 2: singlePhase - phase 1 voltage is between Phase 1 and Neutral. 3: splitPhase - phase 1 voltage is between Phase 1 and Neutral; phase 2 voltage is between Phase 2 and Neutral; phase 3 voltage is between Phase 1 and Phase 2. 4: threePhasePhaseToNeutral - phase 1 voltage is between Phase 1 and Neutral; phase 2 voltage is between Phase 2 and Neutral; phase 3 voltage is between Phase 3 and Neutral. 5: threePhasePhaseToPhase - phase 1 voltage is between Phase 1 and Phase 2; phase 2 voltage is between Phase 2 and Phase 3; phase 3 voltage is between Phase 3 and Phase 1." ::= { atsInputEntry 3 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.8.5.3.2.1.1 | atsInputTableIndex | 0 | 0 | The input identifier. |
1.3.6.1.4.1.318.1.1.8.5.3.2.1.2 | atsNumInputPhases | 0 | 0 | The number of input phases utilized in this device. The sum of all the atsNumInputPhases variable indicates the number of rows i… |
1.3.6.1.4.1.318.1.1.8.5.3.2.1.4 | atsInputFrequency | 0 | 0 | The input frequency in Hertz, or -1 if it's unsupported by this Source. |
1.3.6.1.4.1.318.1.1.8.5.3.2.1.5 | atsInputType | 0 | 0 | The input type. |
1.3.6.1.4.1.318.1.1.8.5.3.2.1.6 | atsInputName | 0 | 0 | A name given to a particular input. |