The control of the output relays. This is a binary
setting with each bit representing an alarm state.
To set K1 on a high alarm, set the 1st bit (1).
To set K2 on a high alarm, set the 2nd bit (2).
To set K1 on a low alarm, set the 3rd bit (4).
To set K2 on a low alarm, set the 4th bit (8).
To set K1 on a digital alarm, set the 1st bit (1).
To set K2 on a digital alarm, set the 2nd bit (2).
For no action. set this value to 0.
The range of this setting is 0..15.
This variable is stored in non-volatile memory.
Parsed from file Falconmib.txt
Company: None
Module: RLE-FALCON-MIB
The control of the output relays. This is a binary
setting with each bit representing an alarm state.
To set K1 on a high alarm, set the 1st bit (1).
To set K2 on a high alarm, set the 2nd bit (2).
To set K1 on a low alarm, set the 3rd bit (4).
To set K2 on a low alarm, set the 4th bit (8).
To set K1 on a digital alarm, set the 1st bit (1).
To set K2 on a digital alarm, set the 2nd bit (2).
For no action. set this value to 0.
The range of this setting is 0..15.
This variable is stored in non-volatile memory.
Parsed from file RLE-FALCON-MIB.mib
Module: RLE-FALCON-MIB
Vendor: Raymond and Lae Engineering, Inc.
Module: RLE-FALCON-MIB
[Automatically extracted from oidview.com]
FalconInput1RlyControl OBJECT-TYPE SYNTAX INTEGER (-2147483648..2147483647) ACCESS read-write STATUS mandatory DESCRIPTION "The control of the output relays. This is a binary setting with each bit representing an alarm state. To set K1 on a high alarm, set the 1st bit (1). To set K2 on a high alarm, set the 2nd bit (2). To set K1 on a low alarm, set the 3rd bit (4). To set K2 on a low alarm, set the 4th bit (8). To set K1 on a digital alarm, set the 1st bit (1). To set K2 on a digital alarm, set the 2nd bit (2). For no action. set this value to 0. The range of this setting is 0..15. This variable is stored in non-volatile memory." ::= { FalconInput1 11 }
falconInput1RlyControl OBJECT-TYPE SYNTAX INTEGER (-2147483648..2147483647) ACCESS read-write STATUS mandatory DESCRIPTION "The control of the output relays. This is a binary setting with each bit representing an alarm state. To set K1 on a high alarm, set the 1st bit (1). To set K2 on a high alarm, set the 2nd bit (2). To set K1 on a low alarm, set the 3rd bit (4). To set K2 on a low alarm, set the 4th bit (8). To set K1 on a digital alarm, set the 1st bit (1). To set K2 on a digital alarm, set the 2nd bit (2). For no action. set this value to 0. The range of this setting is 0..15. This variable is stored in non-volatile memory." ::= { falconInput1 11 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.3184.1.1.1.3.1.11.0 | 0 | 0 | 0 | FalconInput1RlyControl |
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.3184.1.1.1.3.1.1 | FalconInput1State | 1 | 1 | The state of use of Input Number 1. When a sensor is connected to Input 1 set State to installed(2) to indicate that the value of… |
1.3.6.1.4.1.3184.1.1.1.3.1.2 | FalconInput1Reading | 1 | 1 | The reading for sensor 1. If the input is digital, the reading will be 1 (active) or 0 (inactive) |
1.3.6.1.4.1.3184.1.1.1.3.1.3 | FalconInput1Gain | 1 | 1 | A correction gain associated with the sensor variable. The value of gain is multiplied by the value from Input Sensor Number 1 to… |
1.3.6.1.4.1.3184.1.1.1.3.1.4 | FalconInput1Offset | 1 | 1 | A correction Offset associated with the sensor variable. The value of Offset is added to the value from Input Sensor Number 1 to … |
1.3.6.1.4.1.3184.1.1.1.3.1.5 | FalconInput1Label | 1 | 1 | A user-defined text string associated with Input Number 1. The text string is stored in non-volatile memory. |
1.3.6.1.4.1.3184.1.1.1.3.1.6 | FalconInput1UOM | 1 | 1 | A user-defined text string associated with Input Number 1. The text string is stored in non-volatile memory. |
1.3.6.1.4.1.3184.1.1.1.3.1.7 | FalconInput1HighLimit2 | 1 | 1 | When input 1 reaches or exceeds this value a trap will be generated signifying a high alarm condition at sensor 1. The HighLimit2 … |
1.3.6.1.4.1.3184.1.1.1.3.1.8 | FalconInput1HighLimit | 1 | 1 | When input 1 reaches or exceeds this value a trap will be generated signifying a high alarm condition at sensor 1. The HighLimit v… |
1.3.6.1.4.1.3184.1.1.1.3.1.9 | FalconInput1LowLimit | 1 | 1 | When input 1 reaches or goes below this value a trap will be generated signifying a low alarm condition at sensor 1. The LowLimit… |
1.3.6.1.4.1.3184.1.1.1.3.1.10 | FalconInput1LowLimit2 | 1 | 1 | When input 1 reaches or goes below this value a trap will be generated signifying a low alarm condition at sensor 1. The LowLimit… |
1.3.6.1.4.1.3184.1.1.1.3.1.12 | FalconInput1Delay | 1 | 1 | The number of seconds an alarm for this input must be present before annunication. The range of this setting is 0..600. This varia… |
1.3.6.1.4.1.3184.1.1.1.3.1.13 | FalconInput1Hysteresis | 1 | 1 | The value of alarm hysteresis for this input. The input reading must decrease or increase by this value before the alarm will cle… |