A correction gain associated with the sensor variable.
The value of gain is multiplied by the value from
Input Sensor Number 4 to obtain the value of
the Input4 variable. The gain variable is stored in
non-volatile memory.
Parsed from file Falconmib.txt
Company: None
Module: RLE-FALCON-MIB
A correction gain associated with the sensor variable.
The value of gain is multiplied by the value from
Input Sensor Number 4 to obtain the value of
the Input4 variable. The gain variable is stored in
non-volatile memory.
Parsed from file RLE-FALCON-MIB.mib
Module: RLE-FALCON-MIB
Vendor: Raymond and Lae Engineering, Inc.
Module: RLE-FALCON-MIB
[Automatically extracted from oidview.com]
FalconInput4Gain OBJECT-TYPE SYNTAX INTEGER (-2147483648..2147483647) ACCESS read-write STATUS mandatory DESCRIPTION "A correction gain associated with the sensor variable. The value of gain is multiplied by the value from Input Sensor Number 4 to obtain the value of the Input4 variable. The gain variable is stored in non-volatile memory." ::= { FalconInput4 3 }
falconInput4Gain OBJECT-TYPE SYNTAX INTEGER (-2147483648..2147483647) ACCESS read-write STATUS mandatory DESCRIPTION "A correction gain associated with the sensor variable. The value of gain is multiplied by the value from Input Sensor Number 4 to obtain the value of the Input4 variable. The gain variable is stored in non-volatile memory." ::= { falconInput4 3 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.3184.1.1.1.3.4.3.0 | 0 | 0 | 0 | FalconInput4Gain |
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.3184.1.1.1.3.4.1 | FalconInput4State | 1 | 1 | The state of use of Input Number 4. When a sensor is connected to Input 4 set State to installed(2) to indicate that the value of… |
1.3.6.1.4.1.3184.1.1.1.3.4.2 | FalconInput4Reading | 1 | 1 | The reading for sensor 4. If the input is digital, the reading will be 1 (active) or 0 (inactive) |
1.3.6.1.4.1.3184.1.1.1.3.4.4 | FalconInput4Offset | 1 | 1 | A correction Offset associated with the sensor variable. The value of Offset is added to the value from Input Sensor Number 4 to … |
1.3.6.1.4.1.3184.1.1.1.3.4.5 | FalconInput4Label | 1 | 1 | A user-defined text string associated with Input Number 4. The text string is stored in non-volatile memory. |
1.3.6.1.4.1.3184.1.1.1.3.4.6 | FalconInput4UOM | 1 | 1 | A user-defined text string associated with Input Number 4. The text string is stored in non-volatile memory. |
1.3.6.1.4.1.3184.1.1.1.3.4.7 | FalconInput4HighLimit2 | 1 | 1 | When input 4 reaches or exceeds this value a trap will be generated signifying a high alarm condition at sensor 4. The HighLimit v… |
1.3.6.1.4.1.3184.1.1.1.3.4.8 | FalconInput4HighLimit | 1 | 1 | When input 4 reaches or exceeds this value a trap will be generated signifying a high alarm condition at sensor 4. The HighLimit v… |
1.3.6.1.4.1.3184.1.1.1.3.4.9 | FalconInput4LowLimit | 1 | 1 | When input 4 reaches or goes below this value a trap will be generated signifying a low alarm condition at sensor 4. The LowLimit… |
1.3.6.1.4.1.3184.1.1.1.3.4.10 | FalconInput4LowLimit2 | 1 | 1 | When input 4 reaches or goes below this value a trap will be generated signifying a low alarm condition at sensor 4. The LowLimit… |
1.3.6.1.4.1.3184.1.1.1.3.4.11 | FalconInput4RlyControl | 1 | 1 | The control of the output relays. This is a binary setting with each bit representing an alarm state. To set K1 on a high alarm, … |
1.3.6.1.4.1.3184.1.1.1.3.4.12 | FalconInput4Delay | 1 | 1 | The number of seconds an alarm for this input must be present before annunication. The range of this setting is 0..600. This varia… |
1.3.6.1.4.1.3184.1.1.1.3.4.13 | FalconInput4Hysteresis | 1 | 1 | The value of alarm hysteresis for this input. The input reading must decrease or increase by this value before the alarm will cle… |