The state of use of Input Number 7. When a sensor is
connected to Input 7 set State to installed(2) to
indicate that the value of FalconReading4 is valid.
When no sensor is connected to Input 7 set
State to notInstalled(1) to indicate that the value of
FalconReading7 may not be valid.
This variable is stored in non-volatile memory.
Parsed from file Falconmib.txt
Company: None
Module: RLE-FALCON-MIB
The state of use of Input Number 7. When a sensor is
connected to Input 7 set State to installed(2) to
indicate that the value of falconReading4 is valid.
When no sensor is connected to Input 7 set
State to notInstalled(1) to indicate that the value of
falconReading7 may not be valid.
This variable is stored in non-volatile memory.
Parsed from file RLE-FALCON-MIB.mib
Module: RLE-FALCON-MIB
Vendor: Raymond and Lae Engineering, Inc.
Module: RLE-FALCON-MIB
[Automatically extracted from oidview.com]
FalconInput7State OBJECT-TYPE SYNTAX INTEGER { notInstalled(1), Analog_4to20_Installed(2), Digital_NO_Installed(3), Digital_NC_Installed(4) } ACCESS read-write STATUS mandatory DESCRIPTION "The state of use of Input Number 7. When a sensor is connected to Input 7 set State to installed(2) to indicate that the value of FalconReading4 is valid. When no sensor is connected to Input 7 set State to notInstalled(1) to indicate that the value of FalconReading7 may not be valid. This variable is stored in non-volatile memory." ::= { FalconInput7 1 }
falconInput7State OBJECT-TYPE SYNTAX INTEGER { notInstalled(1), analog-4to20-installed(2), digital-no-installed(3), digital-nc-installed(4) } ACCESS read-write STATUS mandatory DESCRIPTION "The state of use of Input Number 7. When a sensor is connected to Input 7 set State to installed(2) to indicate that the value of falconReading4 is valid. When no sensor is connected to Input 7 set State to notInstalled(1) to indicate that the value of falconReading7 may not be valid. This variable is stored in non-volatile memory." ::= { falconInput7 1 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.3184.1.1.1.3.7.1.0 | 0 | 0 | 0 | FalconInput7State |
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.3184.1.1.1.3.7.2 | FalconInput7Reading | 1 | 1 | The reading for sensor 7. If the input is digital, the reading will be 1 (active) or 0 (inactive) |
1.3.6.1.4.1.3184.1.1.1.3.7.3 | FalconInput7Gain | 1 | 1 | A correction gain associated with the sensor variable. The value of gain is multiplied by the value from Input Sensor Number 7 to… |
1.3.6.1.4.1.3184.1.1.1.3.7.4 | FalconInput7Offset | 1 | 1 | A correction Offset associated with the sensor variable. The value of Offset is added to the value from Input Sensor Number 7 to … |
1.3.6.1.4.1.3184.1.1.1.3.7.5 | FalconInput7Label | 1 | 1 | A user-defined text string associated with Input Number 7. The text string is stored in non-volatile memory. |
1.3.6.1.4.1.3184.1.1.1.3.7.6 | FalconInput7UOM | 1 | 1 | A user-defined text string associated with Input Number 7. The text string is stored in non-volatile memory. |
1.3.6.1.4.1.3184.1.1.1.3.7.7 | FalconInput7HighLimit2 | 1 | 1 | When input 7 reaches or exceeds this value a trap will be generated signifying a high alarm condition at sensor 7. The HighLimit v… |
1.3.6.1.4.1.3184.1.1.1.3.7.8 | FalconInput7HighLimit | 1 | 1 | When input 7 reaches or exceeds this value a trap will be generated signifying a high alarm condition at sensor 7. The HighLimit v… |
1.3.6.1.4.1.3184.1.1.1.3.7.9 | FalconInput7LowLimit | 1 | 1 | When input 7 reaches or goes below this value a trap will be generated signifying a low alarm condition at sensor 7. The LowLimit… |
1.3.6.1.4.1.3184.1.1.1.3.7.10 | FalconInput7LowLimit2 | 1 | 1 | When input 7 reaches or goes below this value a trap will be generated signifying a low alarm condition at sensor 7. The LowLimit… |
1.3.6.1.4.1.3184.1.1.1.3.7.11 | FalconInput7RlyControl | 1 | 1 | The control of the output relays. This is a binary setting with each bit representing an alarm state. To set K1 on a high alarm, … |
1.3.6.1.4.1.3184.1.1.1.3.7.12 | FalconInput7Delay | 1 | 1 | The number of seconds an alarm for this input must be present before annunication. The range of this setting is 0..600. This varia… |
1.3.6.1.4.1.3184.1.1.1.3.7.13 | FalconInput7Hysteresis | 1 | 1 | The value of alarm hysteresis for this input. The input reading must decrease or increase by this value before the alarm will cle… |