OID reference

mtrapinfoBmEventId

1.3.6.1.4.1.3808.2.2.6

Description

Allow CPS traps with an integer argument for providing detail information about Battery Manager specific event identifier. Not being defined in the MIB, only reply 0. Known Specific Event ID: Battery Manager 0 - not used 1 - Alarm: The battery manager system fault. 2 - Info: Device configuration changed. 3 - Alarm: Pr…

Full description and source information

Identification

Identifier and names

Parent
1.3.6.1.4.1.3808.2.2 (mtrapinfo)
Node code
6
Node name
mtrapinfoBmEventId
Category
SNMP management object
Numeric OID
1.3.6.1.4.1.3808.2.2.6
URN notation
urn:oid:1.3.6.1.4.1.3808.2.2.6
ASN.1, OID-IRI and named path variants
ASN.1 notation

{1 3 6 1 4 1 3808 2 2 6}

  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) cps(3808) cpsmgmt(2) mtrapinfo(2) mtrapinfoBmEventId(6)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) cps(3808) cpsmgmt(2) mtrapinfo(2) mtrapinfoBmEventId(6)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) cps(3808) cpsmgmt(2) mtrapinfo(2) mtrapinfoBmEventId(6)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) vendor-objects(1) cps(3808) cpsmgmt(2) mtrapinfo(2) mtrapinfoBmEventId(6)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprise(1) cps(3808) cpsmgmt(2) mtrapinfo(2) mtrapinfoBmEventId(6)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) cps(3808) cpsmgmt(2) mtrapinfo(2) mtrapinfoBmEventId(6)}
  • {iso(1) org(3) dod(6) internet(1) private(4) ldap-enterprise(1) cps(3808) cpsmgmt(2) mtrapinfo(2) mtrapinfoBmEventId(6)}
  • {iso(1) org(3) dod(6) internet(1) private(4) vendor-objects(1) cps(3808) cpsmgmt(2) mtrapinfo(2) mtrapinfoBmEventId(6)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprise(1) cps(3808) cpsmgmt(2) mtrapinfo(2) mtrapinfoBmEventId(6)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprises(1) cps(3808) cpsmgmt(2) mtrapinfo(2) mtrapinfoBmEventId(6)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) cps(3808) cpsmgmt(2) mtrapinfo(2) mtrapinfoBmEventId(6)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) vendor-objects(1) cps(3808) cpsmgmt(2) mtrapinfo(2) mtrapinfoBmEventId(6)}
  • {iso(1) iso-organization(3) dod(6) internet(1) private(4) enterprise(1) cps(3808) cpsmgmt(2) mtrapinfo(2) mtrapinfoBmEventId(6)}
  • {iso(1) iso-organization(3) dod(6) internet(1) private(4) enterprises(1) cps(3808) cpsmgmt(2) mtrapinfo(2) mtrapinfoBmEventId(6)}
  • {iso(1) iso-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) cps(3808) cpsmgmt(2) mtrapinfo(2) mtrapinfoBmEventId(6)}
  • {iso(1) iso-organization(3) dod(6) internet(1) private(4) vendor-objects(1) cps(3808) cpsmgmt(2) mtrapinfo(2) mtrapinfoBmEventId(6)}
OID-IRI notation
  • /1/3/6/1/4/1/3808/2/2/6
  • /ISO/Identified-Organization/6/1/4/1/3808/2/2/6
  • /ISO/3/6/1/4/1/3808/2/2/6
Named path variants
  • /iso/identified-organization/dod/internet/private/enterprise/3808/cpsmgmt/mtrapinfo/mtrapinfoBmEventId
  • /iso/identified-organization/dod/internet/private/enterprise/cps/cpsmgmt/mtrapinfo/mtrapinfoBmEventId
  • /iso/identified-organization/dod/internet/private/enterprises/3808/cpsmgmt/mtrapinfo/mtrapinfoBmEventId
  • /iso/identified-organization/dod/internet/private/enterprises/cps/cpsmgmt/mtrapinfo/mtrapinfoBmEventId
  • /iso/identified-organization/dod/internet/private/ldap-enterprise/3808/cpsmgmt/mtrapinfo/mtrapinfoBmEventId
  • /iso/identified-organization/dod/internet/private/ldap-enterprise/cps/cpsmgmt/mtrapinfo/mtrapinfoBmEventId
  • /iso/identified-organization/dod/internet/private/vendor-objects/3808/cpsmgmt/mtrapinfo/mtrapinfoBmEventId
  • /iso/identified-organization/dod/internet/private/vendor-objects/cps/cpsmgmt/mtrapinfo/mtrapinfoBmEventId
  • /iso/org/dod/internet/private/enterprise/3808/cpsmgmt/mtrapinfo/mtrapinfoBmEventId
  • /iso/org/dod/internet/private/enterprise/cps/cpsmgmt/mtrapinfo/mtrapinfoBmEventId
  • /iso/org/dod/internet/private/enterprises/3808/cpsmgmt/mtrapinfo/mtrapinfoBmEventId
  • /iso/org/dod/internet/private/enterprises/cps/cpsmgmt/mtrapinfo/mtrapinfoBmEventId
  • /iso/org/dod/internet/private/ldap-enterprise/3808/cpsmgmt/mtrapinfo/mtrapinfoBmEventId
  • /iso/org/dod/internet/private/ldap-enterprise/cps/cpsmgmt/mtrapinfo/mtrapinfoBmEventId
  • /iso/org/dod/internet/private/vendor-objects/3808/cpsmgmt/mtrapinfo/mtrapinfoBmEventId
  • /iso/org/dod/internet/private/vendor-objects/cps/cpsmgmt/mtrapinfo/mtrapinfoBmEventId
  • Additional combinations skipped.

SNMP properties

Value type
INTEGER
Maximum access defined by MIB
read-only
Status in MIB
mandatory

Using this OID with SNMP

At least one MIB declaration places this object in a scalar group. A scalar instance uses the suffix .0.

snmpget [connection options] DEVICE .1.3.6.1.4.1.3808.2.2.6.0

Replace the placeholders with your connection and authentication options. Available permissions and device support can differ from the MIB.

Properties come from available MIB definitions. Actual device support and access can differ. See source records below for original files and qualifications.

Available source records contain 2 distinct definitions; some records may not include a definition.

Show 2 published definitions

mtrapinfoBmEventId · mandatory

mtrapinfoBmEventId OBJECT-TYPE
   SYNTAX INTEGER
   ACCESS read-only
   STATUS mandatory
   DESCRIPTION
      "Allow CPS traps with an integer argument for providing detail
       information about Battery Manager specific event identifier. 
       Not being defined in the MIB, only reply 0.
       
       Known Specific Event ID: Battery Manager
         0 - not used
         1 - Alarm: The battery manager system fault. 
         2 - Info: Device configuration changed. 
         3 - Alarm: Probe configuration mismatched. 
         4 - Info: Probe configuration matched. 
         5 - Alarm: Communication with battery manager has been lost. 
         6 - Info: Communication with battery manager has been restored. 
         7 - Alarm: Communication with LCD has been lost. 
         8 - Info: Communication with LCD has been restored. 
         9 - Warning: Enter battery equalization active mode.
         10- Warning: Leave battery equalization active mode.
         11- Alarm: Battery equalizing has failed. 
         12- Info: Battery equalizing succeeds. 
         13- Warning: Enter BMS software operation mode. 
         14- Warning: Leave BMS software operatioin mode. 
         15- Warning: Authentication to the BMS software has been failed. 
         16- Alarm: Communication to the BMS software has been lost. 
         17- Info: Communication to the BMS software has restored. 
         18- Alarm: Communication with Wireless module has been lost. 
         19- Info: Communication with Wireless module has been restored. 
         
       Known Specific Event ID: Battery Probes
         101 - Alarm: Low battery voltage. 
         102 - Alarm: High battery voltage. 
         103 - Info: Battery voltage event has cleared. 
         104 - Alarm: Low battery temperature. 
         105 - Alarm: High battery temperature. 
         106 - Info: Battery temperature event has cleared. 
         107 - Alarm: Critical low battery resistance. 
         108 - Alarm: Critical high battery resistance. 
         109 - Warning: Low battery resistance. 
         110 - Warning: high battery resistance. 
         111 - Info: Battery resistance event has cleared. 
         112 - Alarm: Battery resistance health has crossed alarm threshold. 
         113 - Warning: Battery resistance health has crossed warning threshold. 
         114 - Info: Battery resistance health has returned to Normal.
         115 - Alarm: Battery voltage has under the shutdown threshold for a time. 
         116 - Info: Battery voltage has restored from the shutdown threshold. 
         117 - Alarm: Battery probes has been shut down. 
         118 - Alarm: Low battery soc. 
         119 - Warning: Low battery soc. 
         120 - Info: Battery soc event has cleared. 
		 
      Known Specific Event ID: BM String Voltage 
         201 - Alarm: Low string voltage. 
         202 - Alarm: High string voltage.
         203 - Warning: Low string voltage. 
         204 - Warning: High string voltage.  
         205 - Info: String voltage event has cleared.
         226 - Alarm: Low string soc. 
         207 - Warning: Low string soc. 
         208 - Info: String soc event has cleared. 
         
      Known Specific Event ID: BM Wireless
         301 - Warning: Wireless sensors may incomplete, searching wireless sensors. 
         302 - Info: Wireless sensor has left the network. 
         303 - Info: Wireless sensor has joined the network. 
         304 - Info: Wireless sensors complete and communication normally. 
         305 - Warning: Communication with the wireless sensor has been losted. 
         306 - Info: Communication with the wireless sensor has been restored. 
         307 - Warning: Restart/Reset wireless neetwork. 
         308 - Info: Wireless network configuration changed. "
   ::= { mtrapinfo 6 }

mtrapinfoBmEventId · mandatory

mtrapinfoBmEventId OBJECT-TYPE
   SYNTAX INTEGER
   ACCESS read-only
   STATUS mandatory
   DESCRIPTION
      "Allow CPS traps with an integer argument for providing detail
       information about Battery Manager specific event identifier. 
       Not being defined in the MIB, only reply 0.
       
       Known Specific Event ID: Battery Manager
         0 - not used
         1 - Alarm: The battery manager system fault. 
         2 - Info: Device configuration changed. 
         3 - Alarm: Probe configuration mismatched. 
         4 - Info: Probe configuration matched. 
         5 - Alarm: Communication with battery manager has been lost. 
         6 - Info: Communication with battery manager has been restored. 
         7 - Alarm: Communication with LCD has been lost. 
         8 - Info: Communication with LCD has been restored. 
         9 - Warning: Enter battery equalization active mode.
         10- Warning: Leave battery equalization active mode.
         11- Alarm: Battery equalizing has failed. 
         12- Info: Battery equalizing succeeds. 
         
       Known Specific Event ID: Battery Probes
         101 - Alarm: Low battery voltage. 
         102 - Alarm: High battery voltage. 
         103 - Info: Battery voltage event has cleared. 
         104 - Alarm: Low battery temperature. 
         105 - Alarm: High battery temperature. 
         106 - Info: Battery temperature event has cleared. 
         107 - Alarm: Critical low battery resistance. 
         108 - Alarm: Critical high battery resistance. 
         109 - Warning: Low battery resistance. 
         110 - Warning: high battery resistance. 
         111 - Info: Battery resistance event has cleared. 
         112 - Alarm: Battery resistance health has crossed alarm threshold. 
         113 - Warning: Battery resistance health has crossed warning threshold. 
         114 - Info: Battery resistance health has returned to Normal.
         115 - Alarm: Battery voltage has under the shutdown threshold for a time. 
         116 - Info: Battery voltage has restored from the shutdown threshold. 
         117 - Alarm: Battery probes has been shut down. 
         118 - Alarm: Low battery soc. 
         119 - Warning: Low battery soc. 
         120 - Info: Battery soc event has cleared. 
		 
      Known Specific Event ID: BM String Voltage 
         201 - Alarm: Low string voltage. 
         202 - Alarm: High string voltage.
         203 - Warning: Low string voltage. 
         204 - Warning: High string voltage.  
         205 - Info: String voltage event has cleared.
         226 - Alarm: Low string soc. 
         207 - Warning: Low string soc. 
         208 - Info: String soc event has cleared. "
   ::= { mtrapinfo 6 }

Meaning

Descriptions

2 unique

Identical descriptions are grouped. Different wording and device-specific notes are retained.

Description 1

Allow CPS traps with an integer argument for providing detail information about Battery Manager specific event identifier. Not being defined in the MIB, only reply 0. Known Specific Event ID: Battery Manager 0 - not used 1 - Alarm: The battery manager system fault. 2 - Info: Device configuration changed. 3 - Alarm: Probe configuration mismatched. 4 - Info: Probe configuration matched. 5 - Alarm: Communication with battery manager has been lost. 6 - Info: Communication with battery manager has been restored. 7 - Alarm: Communication with LCD has been lost. 8 - Info: Communication with LCD has been restored. 9 - Warning: Enter battery equalization active mode. 10- Warning: Leave battery equalization active mode. 11- Alarm: Battery equalizing has failed. 12- Info: Battery equalizing succeeds. 13- Warning: Enter BMS software operation mode. 14- Warning: Leave BMS software operatioin mode. 15- Warning: Authentication to the BMS software has been failed. 16- Alarm: Communication to the BMS software has been lost. 17- Info: Communication to the BMS software has restored. 18- Alarm: Communication with Wireless module has been lost. 19- Info: Communication with Wireless module has been restored. Known Specific Event ID: Battery Probes 101 - Alarm: Low battery voltage. 102 - Alarm: High battery voltage. 103 - Info: Battery voltage event has cleared. 104 - Alarm: Low battery temperature. 105 - Alarm: High battery temperature. 106 - Info: Battery temperature event has cleared. 107 - Alarm: Critical low battery resistance. 108 - Alarm: Critical high battery resistance. 109 - Warning: Low battery resistance. 110 - Warning: high battery resistance. 111 - Info: Battery resistance event has cleared. 112 - Alarm: Battery resistance health has crossed alarm threshold. 113 - Warning: Battery resistance health has crossed warning threshold. 114 - Info: Battery resistance health has returned to Normal. 115 - Alarm: Battery voltage has under the shutdown threshold for a time. 116 - Info: Battery voltage has restored from the shutdown threshold. 117 - Alarm: Battery probes has been shut down. 118 - Alarm: Low battery soc. 119 - Warning: Low battery soc. 120 - Info: Battery soc event has cleared. Known Specific Event ID: BM String Voltage 201 - Alarm: Low string voltage. 202 - Alarm: High string voltage. 203 - Warning: Low string voltage. 204 - Warning: High string voltage. 205 - Info: String voltage event has cleared. 226 - Alarm: Low string soc. 207 - Warning: Low string soc. 208 - Info: String soc event has cleared. Known Specific Event ID: BM Wireless 301 - Warning: Wireless sensors may incomplete, searching wireless sensors. 302 - Info: Wireless sensor has left the network. 303 - Info: Wireless sensor has joined the network. 304 - Info: Wireless sensors complete and communication normally. 305 - Warning: Communication with the wireless sensor has been losted. 306 - Info: Communication with the wireless sensor has been restored. 307 - Warning: Restart/Reset wireless neetwork. 308 - Info: Wireless network configuration changed.

Sources for this description

Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)

See 1 matching source record

Description 2

Allow CPS traps with an integer argument for providing detail information about Battery Manager specific event identifier. Not being defined in the MIB, only reply 0. Known Specific Event ID: Battery Manager 0 - not used 1 - Alarm: The battery manager system fault. 2 - Info: Device configuration changed. 3 - Alarm: Probe configuration mismatched. 4 - Info: Probe configuration matched. 5 - Alarm: Communication with battery manager has been lost. 6 - Info: Communication with battery manager has been restored. 7 - Alarm: Communication with LCD has been lost. 8 - Info: Communication with LCD has been restored. 9 - Warning: Enter battery equalization active mode. 10- Warning: Leave battery equalization active mode. 11- Alarm: Battery equalizing has failed. 12- Info: Battery equalizing succeeds. Known Specific Event ID: Battery Probes 101 - Alarm: Low battery voltage. 102 - Alarm: High battery voltage. 103 - Info: Battery voltage event has cleared. 104 - Alarm: Low battery temperature. 105 - Alarm: High battery temperature. 106 - Info: Battery temperature event has cleared. 107 - Alarm: Critical low battery resistance. 108 - Alarm: Critical high battery resistance. 109 - Warning: Low battery resistance. 110 - Warning: high battery resistance. 111 - Info: Battery resistance event has cleared. 112 - Alarm: Battery resistance health has crossed alarm threshold. 113 - Warning: Battery resistance health has crossed warning threshold. 114 - Info: Battery resistance health has returned to Normal. 115 - Alarm: Battery voltage has under the shutdown threshold for a time. 116 - Info: Battery voltage has restored from the shutdown threshold. 117 - Alarm: Battery probes has been shut down. 118 - Alarm: Low battery soc. 119 - Warning: Low battery soc. 120 - Info: Battery soc event has cleared. Known Specific Event ID: BM String Voltage 201 - Alarm: Low string voltage. 202 - Alarm: High string voltage. 203 - Warning: Low string voltage. 204 - Warning: High string voltage. 205 - Info: String voltage event has cleared. 226 - Alarm: Low string soc. 207 - Warning: Low string soc. 208 - Info: String soc event has cleared.

Sources for this description

Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)

See 1 matching source record

Evidence

Source records

2 records

Matching descriptions are grouped; open a group to compare definitions and supporting files.

Records for description 1Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)1 record · 1 source

Description 1

mtrapinfoBmEventId · mandatoryMultiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)1 source

Status in source: mandatory.

Names: mtrapinfoBmEventId

Technical details
{
  "smi_kind": "OBJECT-TYPE",
  "definition": [
    "mtrapinfoBmEventId",
    "OBJECT-TYPE",
    "SYNTAX",
    "INTEGER",
    "ACCESS",
    "read-only",
    "STATUS",
    "mandatory",
    "DESCRIPTION",
    "\"Allow CPS traps with an integer argument for providing detail information about Battery Manager specific event identifier. Not being defined in the MIB, only reply 0. Known Specific Event ID: Battery Manager 0 - not used 1 - Alarm: The battery manager system fault. 2 - Info: Device configuration changed. 3 - Alarm: Probe configuration mismatched. 4 - Info: Probe configuration matched. 5 - Alarm: Communication with battery manager has been lost. 6 - Info: Communication with battery manager has been restored. 7 - Alarm: Communication with LCD has been lost. 8 - Info: Communication with LCD has been restored. 9 - Warning: Enter battery equalization active mode. 10- Warning: Leave battery equalization active mode. 11- Alarm: Battery equalizing has failed. 12- Info: Battery equalizing succeeds. 13- Warning: Enter BMS software operation mode. 14- Warning: Leave BMS software operatioin mode. 15- Warning: Authentication to the BMS software has been failed. 16- Alarm: Communication to the BMS software has been lost. 17- Info: Communication to the BMS software has restored. 18- Alarm: Communication with Wireless module has been lost. 19- Info: Communication with Wireless module has been restored. Known Specific Event ID: Battery Probes 101 - Alarm: Low battery voltage. 102 - Alarm: High battery voltage. 103 - Info: Battery voltage event has cleared. 104 - Alarm: Low battery temperature. 105 - Alarm: High battery temperature. 106 - Info: Battery temperature event has cleared. 107 - Alarm: Critical low battery resistance. 108 - Alarm: Critical high battery resistance. 109 - Warning: Low battery resistance. 110 - Warning: high battery resistance. 111 - Info: Battery resistance event has cleared. 112 - Alarm: Battery resistance health has crossed alarm threshold. 113 - Warning: Battery resistance health has crossed warning threshold. 114 - Info: Battery resistance health has returned to Normal. 115 - Alarm: Battery voltage has under the shutdown threshold for a time. 116 - Info: Battery voltage has restored from the shutdown threshold. 117 - Alarm: Battery probes has been shut down. 118 - Alarm: Low battery soc. 119 - Warning: Low battery soc. 120 - Info: Battery soc event has cleared. Known Specific Event ID: BM String Voltage 201 - Alarm: Low string voltage. 202 - Alarm: High string voltage. 203 - Warning: Low string voltage. 204 - Warning: High string voltage. 205 - Info: String voltage event has cleared. 226 - Alarm: Low string soc. 207 - Warning: Low string soc. 208 - Info: String soc event has cleared. Known Specific Event ID: BM Wireless 301 - Warning: Wireless sensors may incomplete, searching wireless sensors. 302 - Info: Wireless sensor has left the network. 303 - Info: Wireless sensor has joined the network. 304 - Info: Wireless sensors complete and communication normally. 305 - Warning: Communication with the wireless sensor has been losted. 306 - Info: Communication with the wireless sensor has been restored. 307 - Warning: Restart/Reset wireless neetwork. 308 - Info: Wireless network configuration changed. \"",
    "::=",
    "{",
    "mtrapinfo",
    "6",
    "}"
  ],
  "syntax_tree": [
    [
      "SimpleSyntax",
      "INTEGER"
    ],
    null,
    [
      "MaxAccessPart",
      "read-only"
    ],
    [
      "Status",
      "mandatory"
    ],
    [
      "DESCRIPTION",
      "Allow CPS traps with an integer argument for providing detail information about Battery Manager specific event identifier. Not being defined in the MIB, only reply 0. Known Specific Event ID: Battery Manager 0 - not used 1 - Alarm: The battery manager system fault. 2 - Info: Device configuration changed. 3 - Alarm: Probe configuration mismatched. 4 - Info: Probe configuration matched. 5 - Alarm: Communication with battery manager has been lost. 6 - Info: Communication with battery manager has been restored. 7 - Alarm: Communication with LCD has been lost. 8 - Info: Communication with LCD has been restored. 9 - Warning: Enter battery equalization active mode. 10- Warning: Leave battery equalization active mode. 11- Alarm: Battery equalizing has failed. 12- Info: Battery equalizing succeeds. 13- Warning: Enter BMS software operation mode. 14- Warning: Leave BMS software operatioin mode. 15- Warning: Authentication to the BMS software has been failed. 16- Alarm: Communication to the BMS software has been lost. 17- Info: Communication to the BMS software has restored. 18- Alarm: Communication with Wireless module has been lost. 19- Info: Communication with Wireless module has been restored. Known Specific Event ID: Battery Probes 101 - Alarm: Low battery voltage. 102 - Alarm: High battery voltage. 103 - Info: Battery voltage event has cleared. 104 - Alarm: Low battery temperature. 105 - Alarm: High battery temperature. 106 - Info: Battery temperature event has cleared. 107 - Alarm: Critical low battery resistance. 108 - Alarm: Critical high battery resistance. 109 - Warning: Low battery resistance. 110 - Warning: high battery resistance. 111 - Info: Battery resistance event has cleared. 112 - Alarm: Battery resistance health has crossed alarm threshold. 113 - Warning: Battery resistance health has crossed warning threshold. 114 - Info: Battery resistance health has returned to Normal. 115 - Alarm: Battery voltage has under the shutdown threshold for a time. 116 - Info: Battery voltage has restored from the shutdown threshold. 117 - Alarm: Battery probes has been shut down. 118 - Alarm: Low battery soc. 119 - Warning: Low battery soc. 120 - Info: Battery soc event has cleared. Known Specific Event ID: BM String Voltage 201 - Alarm: Low string voltage. 202 - Alarm: High string voltage. 203 - Warning: Low string voltage. 204 - Warning: High string voltage. 205 - Info: String voltage event has cleared. 226 - Alarm: Low string soc. 207 - Warning: Low string soc. 208 - Info: String soc event has cleared. Known Specific Event ID: BM Wireless 301 - Warning: Wireless sensors may incomplete, searching wireless sensors. 302 - Info: Wireless sensor has left the network. 303 - Info: Wireless sensor has joined the network. 304 - Info: Wireless sensors complete and communication normally. 305 - Warning: Communication with the wireless sensor has been losted. 306 - Info: Communication with the wireless sensor has been restored. 307 - Warning: Restart/Reset wireless neetwork. 308 - Info: Wireless network configuration changed."
    ],
    null,
    null,
    null,
    null
  ]
}
Records for description 2Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)1 record · 1 source

Description 2

mtrapinfoBmEventId · mandatoryMultiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)1 source

Status in source: mandatory.

Names: mtrapinfoBmEventId

Technical details
{
  "smi_kind": "OBJECT-TYPE",
  "definition": [
    "mtrapinfoBmEventId",
    "OBJECT-TYPE",
    "SYNTAX",
    "INTEGER",
    "ACCESS",
    "read-only",
    "STATUS",
    "mandatory",
    "DESCRIPTION",
    "\"Allow CPS traps with an integer argument for providing detail information about Battery Manager specific event identifier. Not being defined in the MIB, only reply 0. Known Specific Event ID: Battery Manager 0 - not used 1 - Alarm: The battery manager system fault. 2 - Info: Device configuration changed. 3 - Alarm: Probe configuration mismatched. 4 - Info: Probe configuration matched. 5 - Alarm: Communication with battery manager has been lost. 6 - Info: Communication with battery manager has been restored. 7 - Alarm: Communication with LCD has been lost. 8 - Info: Communication with LCD has been restored. 9 - Warning: Enter battery equalization active mode. 10- Warning: Leave battery equalization active mode. 11- Alarm: Battery equalizing has failed. 12- Info: Battery equalizing succeeds. Known Specific Event ID: Battery Probes 101 - Alarm: Low battery voltage. 102 - Alarm: High battery voltage. 103 - Info: Battery voltage event has cleared. 104 - Alarm: Low battery temperature. 105 - Alarm: High battery temperature. 106 - Info: Battery temperature event has cleared. 107 - Alarm: Critical low battery resistance. 108 - Alarm: Critical high battery resistance. 109 - Warning: Low battery resistance. 110 - Warning: high battery resistance. 111 - Info: Battery resistance event has cleared. 112 - Alarm: Battery resistance health has crossed alarm threshold. 113 - Warning: Battery resistance health has crossed warning threshold. 114 - Info: Battery resistance health has returned to Normal. 115 - Alarm: Battery voltage has under the shutdown threshold for a time. 116 - Info: Battery voltage has restored from the shutdown threshold. 117 - Alarm: Battery probes has been shut down. 118 - Alarm: Low battery soc. 119 - Warning: Low battery soc. 120 - Info: Battery soc event has cleared. Known Specific Event ID: BM String Voltage 201 - Alarm: Low string voltage. 202 - Alarm: High string voltage. 203 - Warning: Low string voltage. 204 - Warning: High string voltage. 205 - Info: String voltage event has cleared. 226 - Alarm: Low string soc. 207 - Warning: Low string soc. 208 - Info: String soc event has cleared. \"",
    "::=",
    "{",
    "mtrapinfo",
    "6",
    "}"
  ],
  "syntax_tree": [
    [
      "SimpleSyntax",
      "INTEGER"
    ],
    null,
    [
      "MaxAccessPart",
      "read-only"
    ],
    [
      "Status",
      "mandatory"
    ],
    [
      "DESCRIPTION",
      "Allow CPS traps with an integer argument for providing detail information about Battery Manager specific event identifier. Not being defined in the MIB, only reply 0. Known Specific Event ID: Battery Manager 0 - not used 1 - Alarm: The battery manager system fault. 2 - Info: Device configuration changed. 3 - Alarm: Probe configuration mismatched. 4 - Info: Probe configuration matched. 5 - Alarm: Communication with battery manager has been lost. 6 - Info: Communication with battery manager has been restored. 7 - Alarm: Communication with LCD has been lost. 8 - Info: Communication with LCD has been restored. 9 - Warning: Enter battery equalization active mode. 10- Warning: Leave battery equalization active mode. 11- Alarm: Battery equalizing has failed. 12- Info: Battery equalizing succeeds. Known Specific Event ID: Battery Probes 101 - Alarm: Low battery voltage. 102 - Alarm: High battery voltage. 103 - Info: Battery voltage event has cleared. 104 - Alarm: Low battery temperature. 105 - Alarm: High battery temperature. 106 - Info: Battery temperature event has cleared. 107 - Alarm: Critical low battery resistance. 108 - Alarm: Critical high battery resistance. 109 - Warning: Low battery resistance. 110 - Warning: high battery resistance. 111 - Info: Battery resistance event has cleared. 112 - Alarm: Battery resistance health has crossed alarm threshold. 113 - Warning: Battery resistance health has crossed warning threshold. 114 - Info: Battery resistance health has returned to Normal. 115 - Alarm: Battery voltage has under the shutdown threshold for a time. 116 - Info: Battery voltage has restored from the shutdown threshold. 117 - Alarm: Battery probes has been shut down. 118 - Alarm: Low battery soc. 119 - Warning: Low battery soc. 120 - Info: Battery soc event has cleared. Known Specific Event ID: BM String Voltage 201 - Alarm: Low string voltage. 202 - Alarm: High string voltage. 203 - Warning: Low string voltage. 204 - Warning: High string voltage. 205 - Info: String voltage event has cleared. 226 - Alarm: Low string soc. 207 - Warning: Low string soc. 208 - Info: String soc event has cleared."
    ],
    null,
    null,
    null,
    null
  ]
}

Registration

Registration authorities

First Registration Authority (inferred from ancestor 1.3.6.1.4.1.3808)

Yeh Jackie

Siblings (6)

OIDNameDirect childrenDescendantsDescription
1.3.6.1.4.1.3808.2.2.1 mtrapinfoInteger00
1.3.6.1.4.1.3808.2.2.2 mtrapinfoIpAddress00
1.3.6.1.4.1.3808.2.2.3 mtrapinfoString00
1.3.6.1.4.1.3808.2.2.4 mtrapinfoGauge00
1.3.6.1.4.1.3808.2.2.5 mtrapinfoTimeTicks00
1.3.6.1.4.1.3808.2.2.7 mtrapinfoCpEventId00