This is a number in the range of 1..N, the number of branch circuits (channels) in the system. This is the sum of all circuits across all modules in the system. The total number of channels is related to module capacity vs. connected circuits. That is, if a module has 21 channels on it but only one channel is attached to a CT, the module will still report 21 channels (single phase branch circuits).
OID reference
seHdpmCircuitVoltsAmpsWattsCount
1.3.6.1.4.1.3833.1.6000.1.8.1.1
Description
This is a number in the range of 1..N, the number of branch circuits (channels) in the system. This is the sum of all circuits across all modules in the system. The total number of channels is related to module capacity vs. connected circuits. That is, if a module has 21 channels on it but only one channel is attached…
Identification
Identifier and names
- Parent
- 1.3.6.1.4.1.3833.1.6000.1.8.1 (seHdpmCircuitVoltsAmpsWatts)
- Node code
- 1
- Node name
- seHdpmCircuitVoltsAmpsWattsCount
- Category
- SNMP management object
- Numeric OID
- 1.3.6.1.4.1.3833.1.6000.1.8.1.1
- URN notation
- urn:oid:1.3.6.1.4.1.3833.1.6000.1.8.1.1
ASN.1, OID-IRI and named path variants
- ASN.1 notation
-
{1 3 6 1 4 1 3833 1 6000 1 8 1 1}
- {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) schneiderElectric(3833) transparentFactoryEthernet(1) hdpm(6000) schneiderHDPM(1) seHdpmVoltsAmpsWatts(8) seHdpmCircuitVoltsAmpsWatts(1) seHdpmCircuitVoltsAmpsWattsCount(1)}
- {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) schneiderElectric(3833) schneiderEnergy(1) hdpm(6000) schneiderHDPM(1) seHdpmVoltsAmpsWatts(8) seHdpmCircuitVoltsAmpsWatts(1) seHdpmCircuitVoltsAmpsWattsCount(1)}
- {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) groupeschneider(3833) transparentFactoryEthernet(1) hdpm(6000) schneiderHDPM(1) seHdpmVoltsAmpsWatts(8) seHdpmCircuitVoltsAmpsWatts(1) seHdpmCircuitVoltsAmpsWattsCount(1)}
- {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) groupeschneider(3833) schneiderEnergy(1) hdpm(6000) schneiderHDPM(1) seHdpmVoltsAmpsWatts(8) seHdpmCircuitVoltsAmpsWatts(1) seHdpmCircuitVoltsAmpsWattsCount(1)}
- {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) schneiderelectric(3833) transparentFactoryEthernet(1) hdpm(6000) schneiderHDPM(1) seHdpmVoltsAmpsWatts(8) seHdpmCircuitVoltsAmpsWatts(1) seHdpmCircuitVoltsAmpsWattsCount(1)}
- {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) schneiderelectric(3833) schneiderEnergy(1) hdpm(6000) schneiderHDPM(1) seHdpmVoltsAmpsWatts(8) seHdpmCircuitVoltsAmpsWatts(1) seHdpmCircuitVoltsAmpsWattsCount(1)}
- {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) schneiderElectric(3833) transparentFactoryEthernet(1) hdpm(6000) schneiderHDPM(1) seHdpmVoltsAmpsWatts(8) seHdpmCircuitVoltsAmpsWatts(1) seHdpmCircuitVoltsAmpsWattsCount(1)}
- {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) schneiderElectric(3833) schneiderEnergy(1) hdpm(6000) schneiderHDPM(1) seHdpmVoltsAmpsWatts(8) seHdpmCircuitVoltsAmpsWatts(1) seHdpmCircuitVoltsAmpsWattsCount(1)}
- {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) groupeschneider(3833) transparentFactoryEthernet(1) hdpm(6000) schneiderHDPM(1) seHdpmVoltsAmpsWatts(8) seHdpmCircuitVoltsAmpsWatts(1) seHdpmCircuitVoltsAmpsWattsCount(1)}
- {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) groupeschneider(3833) schneiderEnergy(1) hdpm(6000) schneiderHDPM(1) seHdpmVoltsAmpsWatts(8) seHdpmCircuitVoltsAmpsWatts(1) seHdpmCircuitVoltsAmpsWattsCount(1)}
- {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) schneiderelectric(3833) transparentFactoryEthernet(1) hdpm(6000) schneiderHDPM(1) seHdpmVoltsAmpsWatts(8) seHdpmCircuitVoltsAmpsWatts(1) seHdpmCircuitVoltsAmpsWattsCount(1)}
- {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) schneiderelectric(3833) schneiderEnergy(1) hdpm(6000) schneiderHDPM(1) seHdpmVoltsAmpsWatts(8) seHdpmCircuitVoltsAmpsWatts(1) seHdpmCircuitVoltsAmpsWattsCount(1)}
- {iso(1) identified-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) schneiderElectric(3833) transparentFactoryEthernet(1) hdpm(6000) schneiderHDPM(1) seHdpmVoltsAmpsWatts(8) seHdpmCircuitVoltsAmpsWatts(1) seHdpmCircuitVoltsAmpsWattsCount(1)}
- {iso(1) identified-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) schneiderElectric(3833) schneiderEnergy(1) hdpm(6000) schneiderHDPM(1) seHdpmVoltsAmpsWatts(8) seHdpmCircuitVoltsAmpsWatts(1) seHdpmCircuitVoltsAmpsWattsCount(1)}
- {iso(1) identified-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) groupeschneider(3833) transparentFactoryEthernet(1) hdpm(6000) schneiderHDPM(1) seHdpmVoltsAmpsWatts(8) seHdpmCircuitVoltsAmpsWatts(1) seHdpmCircuitVoltsAmpsWattsCount(1)}
- {iso(1) identified-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) groupeschneider(3833) schneiderEnergy(1) hdpm(6000) schneiderHDPM(1) seHdpmVoltsAmpsWatts(8) seHdpmCircuitVoltsAmpsWatts(1) seHdpmCircuitVoltsAmpsWattsCount(1)}
- Additional combinations skipped.
- OID-IRI notation
- /1/3/6/1/4/1/3833/1/6000/1/8/1/1
- /ISO/Identified-Organization/6/1/4/1/3833/1/6000/1/8/1/1
- /ISO/3/6/1/4/1/3833/1/6000/1/8/1/1
- Named path variants
- /iso/identified-organization/dod/internet/private/enterprise/schneiderElectric/transparentFactoryEthernet/hdpm/schneiderHDPM/seHdpmVoltsAmpsWatts/seHdpmCircuitVoltsAmpsWatts/seHdpmCircuitVoltsAmpsWattsCount
- /iso/identified-organization/dod/internet/private/enterprise/schneiderElectric/schneiderEnergy/hdpm/schneiderHDPM/seHdpmVoltsAmpsWatts/seHdpmCircuitVoltsAmpsWatts/seHdpmCircuitVoltsAmpsWattsCount
- /iso/identified-organization/dod/internet/private/enterprise/groupeschneider/transparentFactoryEthernet/hdpm/schneiderHDPM/seHdpmVoltsAmpsWatts/seHdpmCircuitVoltsAmpsWatts/seHdpmCircuitVoltsAmpsWattsCount
- /iso/identified-organization/dod/internet/private/enterprise/groupeschneider/schneiderEnergy/hdpm/schneiderHDPM/seHdpmVoltsAmpsWatts/seHdpmCircuitVoltsAmpsWatts/seHdpmCircuitVoltsAmpsWattsCount
- /iso/identified-organization/dod/internet/private/enterprise/schneiderelectric/transparentFactoryEthernet/hdpm/schneiderHDPM/seHdpmVoltsAmpsWatts/seHdpmCircuitVoltsAmpsWatts/seHdpmCircuitVoltsAmpsWattsCount
- /iso/identified-organization/dod/internet/private/enterprise/schneiderelectric/schneiderEnergy/hdpm/schneiderHDPM/seHdpmVoltsAmpsWatts/seHdpmCircuitVoltsAmpsWatts/seHdpmCircuitVoltsAmpsWattsCount
- /iso/identified-organization/dod/internet/private/enterprises/schneiderElectric/transparentFactoryEthernet/hdpm/schneiderHDPM/seHdpmVoltsAmpsWatts/seHdpmCircuitVoltsAmpsWatts/seHdpmCircuitVoltsAmpsWattsCount
- /iso/identified-organization/dod/internet/private/enterprises/schneiderElectric/schneiderEnergy/hdpm/schneiderHDPM/seHdpmVoltsAmpsWatts/seHdpmCircuitVoltsAmpsWatts/seHdpmCircuitVoltsAmpsWattsCount
- /iso/identified-organization/dod/internet/private/enterprises/groupeschneider/transparentFactoryEthernet/hdpm/schneiderHDPM/seHdpmVoltsAmpsWatts/seHdpmCircuitVoltsAmpsWatts/seHdpmCircuitVoltsAmpsWattsCount
- /iso/identified-organization/dod/internet/private/enterprises/groupeschneider/schneiderEnergy/hdpm/schneiderHDPM/seHdpmVoltsAmpsWatts/seHdpmCircuitVoltsAmpsWatts/seHdpmCircuitVoltsAmpsWattsCount
- /iso/identified-organization/dod/internet/private/enterprises/schneiderelectric/transparentFactoryEthernet/hdpm/schneiderHDPM/seHdpmVoltsAmpsWatts/seHdpmCircuitVoltsAmpsWatts/seHdpmCircuitVoltsAmpsWattsCount
- /iso/identified-organization/dod/internet/private/enterprises/schneiderelectric/schneiderEnergy/hdpm/schneiderHDPM/seHdpmVoltsAmpsWatts/seHdpmCircuitVoltsAmpsWatts/seHdpmCircuitVoltsAmpsWattsCount
- /iso/identified-organization/dod/internet/private/ldap-enterprise/schneiderElectric/transparentFactoryEthernet/hdpm/schneiderHDPM/seHdpmVoltsAmpsWatts/seHdpmCircuitVoltsAmpsWatts/seHdpmCircuitVoltsAmpsWattsCount
- /iso/identified-organization/dod/internet/private/ldap-enterprise/schneiderElectric/schneiderEnergy/hdpm/schneiderHDPM/seHdpmVoltsAmpsWatts/seHdpmCircuitVoltsAmpsWatts/seHdpmCircuitVoltsAmpsWattsCount
- /iso/identified-organization/dod/internet/private/ldap-enterprise/groupeschneider/transparentFactoryEthernet/hdpm/schneiderHDPM/seHdpmVoltsAmpsWatts/seHdpmCircuitVoltsAmpsWatts/seHdpmCircuitVoltsAmpsWattsCount
- /iso/identified-organization/dod/internet/private/ldap-enterprise/groupeschneider/schneiderEnergy/hdpm/schneiderHDPM/seHdpmVoltsAmpsWatts/seHdpmCircuitVoltsAmpsWatts/seHdpmCircuitVoltsAmpsWattsCount
- Additional combinations skipped.
SNMP properties
- Value type
- Integer32
- Maximum access defined by MIB
- read-only
- Status in MIB
- current
Using this OID with SNMP
At least one MIB declaration places this object in a scalar group. A scalar instance uses the suffix .0.
snmpget [connection options] DEVICE .1.3.6.1.4.1.3833.1.6000.1.8.1.1.0
Replace the placeholders with your connection and authentication options. Available permissions and device support can differ from the MIB.
Properties come from available MIB definitions. Actual device support and access can differ. See source records below for original files and qualifications.
Product context
Documented MIB packages
This OID is defined in a Schneider Electric HDPM6000 MIB distributed with these firmware packages:
- Firmware 0.62.11 · Download firmware package · Download MIB
- Firmware 0.64.2 · Download firmware package · Download MIB
- Firmware 0.66.0 · Download firmware package · Download MIB
A definition in a firmware package does not establish that every device implements it or permits access. Other firmware versions have not been verified here.
Published definition
The displayed source records contain one distinct definition. Compare its source records.
seHdpmCircuitVoltsAmpsWattsCount OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This is a number in the range of 1..N, the number of branch circuits
(channels) in the system. This is the sum of all circuits across all
modules in the system. The total number of channels is related to module
capacity vs. connected circuits. That is, if a module has 21 channels
on it but only one channel is attached to a CT, the module will
still report 21 channels (single phase branch circuits)."
::= { seHdpmCircuitVoltsAmpsWatts 1 }
Meaning
Descriptions
Identical descriptions are grouped. Different wording and device-specific notes are retained.
Evidence
Source records
Matching descriptions are grouped; open a group to compare definitions and supporting files.
Records for description 1Schneider Electric HDPM6000 official MIB
seHdpmCircuitVoltsAmpsWattsCount · currentSchneider Electric HDPM6000 official MIB
Status in source: current.
Names: seHdpmCircuitVoltsAmpsWattsCount
Technical details
{
"smi_kind": "OBJECT-TYPE",
"definition": [
"seHdpmCircuitVoltsAmpsWattsCount",
"OBJECT-TYPE",
"SYNTAX",
"Integer32",
"MAX-ACCESS",
"read-only",
"STATUS",
"current",
"DESCRIPTION",
"\"This is a number in the range of 1..N, the number of branch circuits (channels) in the system. This is the sum of all circuits across all modules in the system. The total number of channels is related to module capacity vs. connected circuits. That is, if a module has 21 channels on it but only one channel is attached to a CT, the module will still report 21 channels (single phase branch circuits).\"",
"::=",
"{",
"seHdpmCircuitVoltsAmpsWatts",
"1",
"}"
],
"syntax_tree": [
[
"SimpleSyntax",
"Integer32"
],
null,
[
"MaxAccessPart",
"read-only"
],
[
"Status",
"current"
],
[
"DESCRIPTION",
"This is a number in the range of 1..N, the number of branch circuits (channels) in the system. This is the sum of all circuits across all modules in the system. The total number of channels is related to module capacity vs. connected circuits. That is, if a module has 21 channels on it but only one channel is attached to a CT, the module will still report 21 channels (single phase branch circuits)."
],
null,
null,
null,
null
]
}- Schneider Electric HDPM6000 official MIB
· Publisher's source file: Schneider Electric HDPM6000 MIB — firmware 0.62.11, 0.64.2
Module: SCHNEIDER-ELECTRIC-HDPM
See published definition above
Module imports
{'SNMPv2-TC': ['TEXTUAL-CONVENTION', 'DateAndTime'], 'SNMPv2-SMI': ['MODULE-IDENTITY', 'OBJECT-TYPE', 'enterprises', 'Gauge32', 'Integer32', 'Unsigned32', 'Counter64', 'Counter32'], 'SNMPv2-CONF': ['OBJECT-GROUP']}Source data warning: Original Schneider Electric HDPM6000 MIB from firmware bundle version(s) 0.62.11, 0.64.2. Applicability to other firmware versions has not been independently confirmed.
· Download Schneider Electric HDPM6000 MIB — firmware 0.62.11, 0.64.2Related source files and packages:
- Schneider Electric HDPM6000 official MIB
· Publisher's source file: Schneider Electric HDPM6000 MIB — firmware 0.66.0
Module: SCHNEIDER-ELECTRIC-HDPM
Module imports
{'SNMPv2-TC': ['TEXTUAL-CONVENTION', 'DateAndTime'], 'SNMPv2-SMI': ['MODULE-IDENTITY', 'OBJECT-TYPE', 'enterprises', 'Gauge32', 'Integer32', 'Unsigned32', 'Counter64', 'Counter32'], 'SNMPv2-CONF': ['OBJECT-GROUP']}Source data warning: Original Schneider Electric HDPM6000 MIB from firmware bundle version(s) 0.66.0. Applicability to other firmware versions has not been independently confirmed.
· Download Schneider Electric HDPM6000 MIB — firmware 0.66.0Related source files and packages:
Registration
Registration authorities
First Registration Authority (inferred from ancestor 1.3.6.1.4.1.3833)
Siblings (1)
| OID | Name | Direct children | Descendants | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.3833.1.6000.1.8.1.2 | seHdpmCircuitVoltsAmpsWattsTable | 1 | 5 |