OID reference

lgpPduPsEntryWiringType

1.3.6.1.4.1.476.1.42.3.8.30.20.1.25

Description

The PDU's power supply physical wiring type. not-specified The type has not been specified/configured. The end_user must configure this object to specify the physical wiring type. single-phase-3-wire-L1-N-PE Single Phase input with 3 wires (Line 1, Neutral and Protective Earth). two-phase-3-wire-L1-L2-PE Two Phase inp…

Full description and source information

Identification

Identifier and names

Parent
1.3.6.1.4.1.476.1.42.3.8.30.20.1 (lgpPduPsEntry)
Node code
25
Node name
lgpPduPsEntryWiringType
Category
SNMP management object
Numeric OID
1.3.6.1.4.1.476.1.42.3.8.30.20.1.25
URN notation
urn:oid:1.3.6.1.4.1.476.1.42.3.8.30.20.1.25
Type
OBJECT-TYPE
ASN.1, OID-IRI and named path variants
ASN.1 notation

{1 3 6 1 4 1 476 1 42 3 8 30 20 1 25}

  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) emerson(476) liebertCorp(1) liebertGlobalProducts(42) lgpFoundation(3) lgpPdu(8) lgpPduPowerSource(30) lgpPduPsTable(20) lgpPduPsEntry(1) lgpPduPsEntryWiringType(25)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) vertiv(476) liebertCorp(1) liebertGlobalProducts(42) lgpFoundation(3) lgpPdu(8) lgpPduPowerSource(30) lgpPduPsTable(20) lgpPduPsEntry(1) lgpPduPsEntryWiringType(25)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) emerson(476) liebertCorp(1) liebertGlobalProducts(42) lgpFoundation(3) lgpPdu(8) lgpPduPowerSource(30) lgpPduPsTable(20) lgpPduPsEntry(1) lgpPduPsEntryWiringType(25)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) vertiv(476) liebertCorp(1) liebertGlobalProducts(42) lgpFoundation(3) lgpPdu(8) lgpPduPowerSource(30) lgpPduPsTable(20) lgpPduPsEntry(1) lgpPduPsEntryWiringType(25)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) emerson(476) liebertCorp(1) liebertGlobalProducts(42) lgpFoundation(3) lgpPdu(8) lgpPduPowerSource(30) lgpPduPsTable(20) lgpPduPsEntry(1) lgpPduPsEntryWiringType(25)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) vertiv(476) liebertCorp(1) liebertGlobalProducts(42) lgpFoundation(3) lgpPdu(8) lgpPduPowerSource(30) lgpPduPsTable(20) lgpPduPsEntry(1) lgpPduPsEntryWiringType(25)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) vendor-objects(1) emerson(476) liebertCorp(1) liebertGlobalProducts(42) lgpFoundation(3) lgpPdu(8) lgpPduPowerSource(30) lgpPduPsTable(20) lgpPduPsEntry(1) lgpPduPsEntryWiringType(25)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) vendor-objects(1) vertiv(476) liebertCorp(1) liebertGlobalProducts(42) lgpFoundation(3) lgpPdu(8) lgpPduPowerSource(30) lgpPduPsTable(20) lgpPduPsEntry(1) lgpPduPsEntryWiringType(25)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprise(1) emerson(476) liebertCorp(1) liebertGlobalProducts(42) lgpFoundation(3) lgpPdu(8) lgpPduPowerSource(30) lgpPduPsTable(20) lgpPduPsEntry(1) lgpPduPsEntryWiringType(25)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprise(1) vertiv(476) liebertCorp(1) liebertGlobalProducts(42) lgpFoundation(3) lgpPdu(8) lgpPduPowerSource(30) lgpPduPsTable(20) lgpPduPsEntry(1) lgpPduPsEntryWiringType(25)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) emerson(476) liebertCorp(1) liebertGlobalProducts(42) lgpFoundation(3) lgpPdu(8) lgpPduPowerSource(30) lgpPduPsTable(20) lgpPduPsEntry(1) lgpPduPsEntryWiringType(25)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) vertiv(476) liebertCorp(1) liebertGlobalProducts(42) lgpFoundation(3) lgpPdu(8) lgpPduPowerSource(30) lgpPduPsTable(20) lgpPduPsEntry(1) lgpPduPsEntryWiringType(25)}
  • {iso(1) org(3) dod(6) internet(1) private(4) ldap-enterprise(1) emerson(476) liebertCorp(1) liebertGlobalProducts(42) lgpFoundation(3) lgpPdu(8) lgpPduPowerSource(30) lgpPduPsTable(20) lgpPduPsEntry(1) lgpPduPsEntryWiringType(25)}
  • {iso(1) org(3) dod(6) internet(1) private(4) ldap-enterprise(1) vertiv(476) liebertCorp(1) liebertGlobalProducts(42) lgpFoundation(3) lgpPdu(8) lgpPduPowerSource(30) lgpPduPsTable(20) lgpPduPsEntry(1) lgpPduPsEntryWiringType(25)}
  • {iso(1) org(3) dod(6) internet(1) private(4) vendor-objects(1) emerson(476) liebertCorp(1) liebertGlobalProducts(42) lgpFoundation(3) lgpPdu(8) lgpPduPowerSource(30) lgpPduPsTable(20) lgpPduPsEntry(1) lgpPduPsEntryWiringType(25)}
  • {iso(1) org(3) dod(6) internet(1) private(4) vendor-objects(1) vertiv(476) liebertCorp(1) liebertGlobalProducts(42) lgpFoundation(3) lgpPdu(8) lgpPduPowerSource(30) lgpPduPsTable(20) lgpPduPsEntry(1) lgpPduPsEntryWiringType(25)}
  • Additional combinations skipped.
OID-IRI notation
  • /1/3/6/1/4/1/476/1/42/3/8/30/20/1/25
  • /ISO/Identified-Organization/6/1/4/1/476/1/42/3/8/30/20/1/25
  • /ISO/3/6/1/4/1/476/1/42/3/8/30/20/1/25
Named path variants
  • /iso/identified-organization/dod/internet/private/enterprise/emerson/liebertCorp/liebertGlobalProducts/lgpFoundation/lgpPdu/lgpPduPowerSource/lgpPduPsTable/lgpPduPsEntry/lgpPduPsEntryWiringType
  • /iso/identified-organization/dod/internet/private/enterprise/vertiv/liebertCorp/liebertGlobalProducts/lgpFoundation/lgpPdu/lgpPduPowerSource/lgpPduPsTable/lgpPduPsEntry/lgpPduPsEntryWiringType
  • /iso/identified-organization/dod/internet/private/enterprises/emerson/liebertCorp/liebertGlobalProducts/lgpFoundation/lgpPdu/lgpPduPowerSource/lgpPduPsTable/lgpPduPsEntry/lgpPduPsEntryWiringType
  • /iso/identified-organization/dod/internet/private/enterprises/vertiv/liebertCorp/liebertGlobalProducts/lgpFoundation/lgpPdu/lgpPduPowerSource/lgpPduPsTable/lgpPduPsEntry/lgpPduPsEntryWiringType
  • /iso/identified-organization/dod/internet/private/ldap-enterprise/emerson/liebertCorp/liebertGlobalProducts/lgpFoundation/lgpPdu/lgpPduPowerSource/lgpPduPsTable/lgpPduPsEntry/lgpPduPsEntryWiringType
  • /iso/identified-organization/dod/internet/private/ldap-enterprise/vertiv/liebertCorp/liebertGlobalProducts/lgpFoundation/lgpPdu/lgpPduPowerSource/lgpPduPsTable/lgpPduPsEntry/lgpPduPsEntryWiringType
  • /iso/identified-organization/dod/internet/private/vendor-objects/emerson/liebertCorp/liebertGlobalProducts/lgpFoundation/lgpPdu/lgpPduPowerSource/lgpPduPsTable/lgpPduPsEntry/lgpPduPsEntryWiringType
  • /iso/identified-organization/dod/internet/private/vendor-objects/vertiv/liebertCorp/liebertGlobalProducts/lgpFoundation/lgpPdu/lgpPduPowerSource/lgpPduPsTable/lgpPduPsEntry/lgpPduPsEntryWiringType
  • /iso/org/dod/internet/private/enterprise/emerson/liebertCorp/liebertGlobalProducts/lgpFoundation/lgpPdu/lgpPduPowerSource/lgpPduPsTable/lgpPduPsEntry/lgpPduPsEntryWiringType
  • /iso/org/dod/internet/private/enterprise/vertiv/liebertCorp/liebertGlobalProducts/lgpFoundation/lgpPdu/lgpPduPowerSource/lgpPduPsTable/lgpPduPsEntry/lgpPduPsEntryWiringType
  • /iso/org/dod/internet/private/enterprises/emerson/liebertCorp/liebertGlobalProducts/lgpFoundation/lgpPdu/lgpPduPowerSource/lgpPduPsTable/lgpPduPsEntry/lgpPduPsEntryWiringType
  • /iso/org/dod/internet/private/enterprises/vertiv/liebertCorp/liebertGlobalProducts/lgpFoundation/lgpPdu/lgpPduPowerSource/lgpPduPsTable/lgpPduPsEntry/lgpPduPsEntryWiringType
  • /iso/org/dod/internet/private/ldap-enterprise/emerson/liebertCorp/liebertGlobalProducts/lgpFoundation/lgpPdu/lgpPduPowerSource/lgpPduPsTable/lgpPduPsEntry/lgpPduPsEntryWiringType
  • /iso/org/dod/internet/private/ldap-enterprise/vertiv/liebertCorp/liebertGlobalProducts/lgpFoundation/lgpPdu/lgpPduPowerSource/lgpPduPsTable/lgpPduPsEntry/lgpPduPsEntryWiringType
  • /iso/org/dod/internet/private/vendor-objects/emerson/liebertCorp/liebertGlobalProducts/lgpFoundation/lgpPdu/lgpPduPowerSource/lgpPduPsTable/lgpPduPsEntry/lgpPduPsEntryWiringType
  • /iso/org/dod/internet/private/vendor-objects/vertiv/liebertCorp/liebertGlobalProducts/lgpFoundation/lgpPdu/lgpPduPowerSource/lgpPduPsTable/lgpPduPsEntry/lgpPduPsEntryWiringType
  • Additional combinations skipped.

SNMP properties

Value type
INTEGER
Maximum access defined by MIB
read-write
Status in MIB
current

Definitions may combine these properties differently.

Compare 2 source variants

Variant 1 — Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community), Netdisco MIB archive copies

Value type
INTEGER
Maximum access defined by MIB
read-write
Status in MIB
current

Variant 2 — MIBdepot

Value type
INTEGER
Maximum access defined by MIB
read-write
Status in MIB
current

Enumerated values

Numbers refer to source variants above. Each value is shown only for variants that define it.

ValueNameSource variants
0not-specified1, 2
1single-phase-3-wire-L1-N-PE1, 2
2two-phase-3-wire-L1-L2-PE1, 2
3three-phase-4-wire-L1-L2-L3-PE1, 2
4three-phase-5-wire-L1-L2-L3-N-PE1, 2
5two-phase-4-wire-L1-L2-N-PE1

Using this OID with SNMP

At least one MIB declaration places this object in a table row. A value belongs to a row instance; its suffix depends on the row's INDEX or AUGMENTS definition. The index encoding is not inferred here.

Published row index: lgpPduEntryIndex, lgpPduPsEntryIndex.

snmpwalk [connection options] DEVICE .1.3.6.1.4.1.476.1.42.3.8.30.20.1.25

Replace the placeholders with your connection and authentication options. Available permissions and device support can differ from the MIB.

Properties come from available MIB definitions. Actual device support and access can differ. See source records below for original files and qualifications.

Available source records contain 2 distinct definitions; some records may not include a definition.

Show 2 published definitions

lgpPduPsEntryWiringType · current

lgpPduPsEntryWiringType OBJECT-TYPE
        SYNTAX      INTEGER
        {
            not-specified(0),
            single-phase-3-wire-L1-N-PE(1),
            two-phase-3-wire-L1-L2-PE(2),
            three-phase-4-wire-L1-L2-L3-PE(3),
            three-phase-5-wire-L1-L2-L3-N-PE(4),
            two-phase-4-wire-L1-L2-N-PE(5)
        }
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The PDU's power supply physical wiring type.
                not-specified
                    The type has not been specified/configured.  The end_user
                    must configure this object to specify the physical wiring
                    type.
                single-phase-3-wire-L1-N-PE
                    Single Phase input with 3 wires (Line 1, Neutral and
                    Protective Earth).
                two-phase-3-wire-L1-L2-PE
                    Two Phase input with 3 wires (Line 1, Line 2, and
                    Protective Earth).
                three-phase-4-wire-L1-L2-L3-PE
                    Three Phase input with 4 wires (Line 1, Line 2, Line 3,
                    and Protective Earth).
                three-phase-5-wire-L1-L2-L3-N-PE
                    Three Phase input with 5 wires (Line 1, Line 2, Line 3,
                    Neutral and Protective Earth).
                two-phase-4-wire-L1-L2-N-PE
                    Two Phase input with 4 wires (Line 1, Line 2, Neutral,
                    and Protective Earth)."
        ::= { lgpPduPsEntry 25 }

lgpPduPsEntryWiringType · current

lgpPduPsEntryWiringType OBJECT-TYPE
        SYNTAX      INTEGER
        {
            not-specified(0),
            single-phase-3-wire-L1-N-PE(1),
            two-phase-3-wire-L1-L2-PE(2),
            three-phase-4-wire-L1-L2-L3-PE(3),
            three-phase-5-wire-L1-L2-L3-N-PE(4),
            two-phase-4-wire-L1-L2-N-PE(5)
        }
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The PDU's power supply physical wiring type.
                not-specified
                    The type has not been specified/configured.  The end_user
                    must configure this object to specify the physical wiring
                    type.
                single-phase-3-wire-L1-N-PE
                    Single Phase input with 3 wires (Line 1, Neutral and
                    Protective Earth).
                two-phase-3-wire-L1-L2-PE
                    Two Phase input with 3 wires (Line 1, Line 2, and
                    Protective Earth).
                three-phase-4-wire-L1-L2-L3-PE
                    Three Phase input with 4 wires (Line 1, Line 2, Line 3,
                    and Protective Earth).
                three-phase-5-wire-L1-L2-L3-N-PE
                    Three Phase input with 5 wires (Line 1, Line 2, Line 3,
                    Neutral and Protective Earth).
                two-phase-4-wire-L1-L2-N-PE
                    Two Phase input with 4 wires (Line 1, Line 2, Neutral,
                    and Protective Earth)."
        ::= { lgpPduPsEntry 25 }

Meaning

Descriptions

2 unique

Identical descriptions are grouped. Different wording and device-specific notes are retained.

Description 1

The PDU's power supply physical wiring type.
not-specified
The type has not been specified/configured. The end_user
must configure this object to specify the physical wiring
type.
single-phase-3-wire-L1-N-PE
Single Phase input with 3 wires (Line 1, Neutral and
Protective Earth).
two-phase-3-wire-L1-L2-PE
Two Phase input with 3 wires (Line 1, Line 2, Neutral and
Protective Earth).
three-phase-4-wire-L1-L2-L3-PE
Three Phase input with 4 wires (Line 1, Line 2, Line 3,
and Protective Earth).
three-phase-5-wire-L1-L2-L3-N-PE
Three Phase input with 5 wires (Line 1, Line 2, Line 3,
Neutral and Protective Earth).
Sources for this description

MIBdepot

Parsed from LIEBERT_GP_PDU.MIB.txt · liebert · LIEBERT-GP-PDU-MIB

Source file: Download LIEBERT_GP_PDU.MIB.txt

Description 2

The PDU's power supply physical wiring type. not-specified The type has not been specified/configured. The end_user must configure this object to specify the physical wiring type. single-phase-3-wire-L1-N-PE Single Phase input with 3 wires (Line 1, Neutral and Protective Earth). two-phase-3-wire-L1-L2-PE Two Phase input with 3 wires (Line 1, Line 2, and Protective Earth). three-phase-4-wire-L1-L2-L3-PE Three Phase input with 4 wires (Line 1, Line 2, Line 3, and Protective Earth). three-phase-5-wire-L1-L2-L3-N-PE Three Phase input with 5 wires (Line 1, Line 2, Line 3, Neutral and Protective Earth). two-phase-4-wire-L1-L2-N-PE Two Phase input with 4 wires (Line 1, Line 2, Neutral, and Protective Earth).

Sources for this description

Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)Netdisco MIB archive copies

See 1 matching source record

Evidence

Source records

1 records

Matching descriptions are grouped; representative source files are shown for each definition.

Records for description 2Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community), Netdisco MIB archive copies1 record · 3 sources

Description 2

lgpPduPsEntryWiringType · currentMultiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community), Netdisco MIB archive copies3 sources

Historical records

Additional source information

Information from OID Repository
Vendor: Liebert
Module: LIEBERT-GP-PDU-MIB (LIEBERT_GP_PDU.MIB)
Type: TABULAR
Access: read-write
Syntax: INTEGER

Automatically extracted from www.mibdepot.com
Information from MIBdepot
lgpPduPsEntryWiringType OBJECT-TYPE
        SYNTAX      INTEGER 
        {
            not-specified(0),
            single-phase-3-wire-L1-N-PE(1),
            two-phase-3-wire-L1-L2-PE(2),
            three-phase-4-wire-L1-L2-L3-PE(3),
            three-phase-5-wire-L1-L2-L3-N-PE(4) 
        }
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The PDU's power supply physical wiring type.
                not-specified
                    The type has not been specified/configured.  The end_user
                    must configure this object to specify the physical wiring
                    type.
                single-phase-3-wire-L1-N-PE
                    Single Phase input with 3 wires (Line 1, Neutral and
                    Protective Earth).
                two-phase-3-wire-L1-L2-PE
                    Two Phase input with 3 wires (Line 1, Line 2, Neutral and
                    Protective Earth).
                three-phase-4-wire-L1-L2-L3-PE
                    Three Phase input with 4 wires (Line 1, Line 2, Line 3,
                    and Protective Earth).
                three-phase-5-wire-L1-L2-L3-N-PE
                    Three Phase input with 5 wires (Line 1, Line 2, Line 3,
                    Neutral and Protective Earth)."
        ::= { lgpPduPsEntry 25 }

Registration

Registration authorities

First Registration Authority (inferred from ancestor 1.3.6.1.4.1.476)

rdraper@cerf.net

Siblings (19)

OIDNameDirect childrenDescendantsDescription
1.3.6.1.4.1.476.1.42.3.8.30.20.1.5 lgpPduPsEntryIndex00 This is the index that indicates the row of the 'lgpPduTable'
1.3.6.1.4.1.476.1.42.3.8.30.20.1.10 lgpPduPsEntryId00 This is a unique entry id representing a given PDU power source
for the PDU.
1.3.6.1.4.1.476.1.42.3.8.30.20.1.15 lgpPduPsEntrySysAssignLabel00 System assigned identifier for this power source. The value
is independent of any user assigned label or tag. The exact format
o…
1.3.6.1.4.1.476.1.42.3.8.30.20.1.20 lgpPduPsEntryModel00 This is the model name (identifier) of the power supply.
1.3.6.1.4.1.476.1.42.3.8.30.20.1.30 lgpPduPsEntryEpInputRated00 Rated Input Line Voltage for the power source (i.e. this is the
nominal line input voltage; it is NOT a measured voltage).

The va…
1.3.6.1.4.1.476.1.42.3.8.30.20.1.35 lgpPduPsEntryEcInputRated00 This is the rated input line current for the module
(it is NOT the measured current).
1.3.6.1.4.1.476.1.42.3.8.30.20.1.40 lgpPduPsEntryFreqRated00 Rated input line frequency for this power source
(i.e. This is the expected line frequency; it is NOT a
measured frequency; it is…
1.3.6.1.4.1.476.1.42.3.8.30.20.1.50 lgpPduPsEntryEnergyAccum00 Total accumulated energy, measured at the power source input, since
the last energy reset. Writing a value of 0 (zero) to this
ca…
1.3.6.1.4.1.476.1.42.3.8.30.20.1.55 lgpPduPsEntrySerialNum00 This is a unique serial number of the power supply. This number
is assigned to the power supply at the time of manufacture.
1.3.6.1.4.1.476.1.42.3.8.30.20.1.60 lgpPduPsEntryFirmwareVersion00 This is the version of the firmware installed on the PDU's
power supply.
1.3.6.1.4.1.476.1.42.3.8.30.20.1.65 lgpPduPsEntryPwrTotal00 Total input power for this power supply. This is the sum of the
power for all phases
1.3.6.1.4.1.476.1.42.3.8.30.20.1.70 lgpPduPsEntryEcNeutral00
1.3.6.1.4.1.476.1.42.3.8.30.20.1.75 lgpPduPsEntryEcNeutralThrshldOvrWarn00
1.3.6.1.4.1.476.1.42.3.8.30.20.1.80 lgpPduPsEntryEcNeutralThrshldOvrAlarm00
1.3.6.1.4.1.476.1.42.3.8.30.20.1.85 lgpPduPsEntryUnbalancedLoadThrshldAlarm00
1.3.6.1.4.1.476.1.42.3.8.30.20.1.90 lgpPduPsEntryApTotal00
1.3.6.1.4.1.476.1.42.3.8.30.20.1.95 lgpPduPsEntryPfTotal00
1.3.6.1.4.1.476.1.42.3.8.30.20.1.100 lgpPduPsEntryEcResidual00
1.3.6.1.4.1.476.1.42.3.8.30.20.1.105 lgpPduPsEntryEcResidualThrshldOvrAlarm00