OID reference

resetStC2

1.3.6.1.4.1.9839.2.1.1.83

Description

Compressor 2 Starting Counter Reset

Full description and source information

Identification

Identifier and names

Parent
1.3.6.1.4.1.9839.2.1.1 (digitalObjects)
Node code
83
Node names
  • resetStC2
  • mal_lp2
  • mal_alco1_68_r
  • alarm_e10
  • mall_pres_hpres
Category
SNMP management object
Numeric OID
1.3.6.1.4.1.9839.2.1.1.83
URN notation
urn:oid:1.3.6.1.4.1.9839.2.1.1.83
ASN.1, OID-IRI and named path variants
ASN.1 notation

{1 3 6 1 4 1 9839 2 1 1 83}

  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) carel(9839) instruments(2) ug40cdzMIB(1) digitalObjects(1) resetStC2(83)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) carel(9839) instruments(2) kelvin-pCOWebMIB-Chiller(1) digitalObjects(1) resetStC2(83)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) carel(9839) instruments(2) dap4-alMIB(1) digitalObjects(1) resetStC2(83)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) carel(9839) instruments(2) uacMIB(1) digitalObjects(1) resetStC2(83)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) carel(9839) instruments(2) uncdz-MIB(1) digitalObjects(1) resetStC2(83)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) carel(9839) instruments(2) mcellaMIB(1) digitalObjects(1) resetStC2(83)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) carel(9839) instruments(2) mastercaseMIB(1) digitalObjects(1) resetStC2(83)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) carel(9839) instruments(2) mastercellasplitMIB(1) digitalObjects(1) resetStC2(83)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) carel(9839) instruments(2) wlprobeMIB(1) digitalObjects(1) resetStC2(83)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) carel(9839) instruments(2) insgrdMIB(1) digitalObjects(1) resetStC2(83)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) carel(9839) instruments(2) ariaMIB(1) digitalObjects(1) resetStC2(83)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) carel(9839) instruments(2) pluginMIB(1) digitalObjects(1) resetStC2(83)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) carel(9839) instruments(2) mioMIB(1) digitalObjects(1) resetStC2(83)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) carel(9839) instruments(2) powersplitMIB(1) digitalObjects(1) resetStC2(83)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) carel(9839) instruments(2) fcpMIB(1) digitalObjects(1) resetStC2(83)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) carel(9839) instruments(2) uchillerMIB(1) digitalObjects(1) resetStC2(83)}
  • Additional combinations skipped.
OID-IRI notation
  • /1/3/6/1/4/1/9839/2/1/1/83
  • /ISO/Identified-Organization/6/1/4/1/9839/2/1/1/83
  • /ISO/3/6/1/4/1/9839/2/1/1/83
Named path variants
  • /iso/identified-organization/dod/internet/private/enterprise/9839/instruments/ug40cdzMIB/digitalObjects/resetStC2
  • /iso/identified-organization/dod/internet/private/enterprise/9839/instruments/ug40cdzMIB/digitalObjects/mal_lp2
  • /iso/identified-organization/dod/internet/private/enterprise/9839/instruments/ug40cdzMIB/digitalObjects/mal_alco1_68_r
  • /iso/identified-organization/dod/internet/private/enterprise/9839/instruments/ug40cdzMIB/digitalObjects/alarm_e10
  • /iso/identified-organization/dod/internet/private/enterprise/9839/instruments/ug40cdzMIB/digitalObjects/mall_pres_hpres
  • /iso/identified-organization/dod/internet/private/enterprise/9839/instruments/kelvin-pCOWebMIB-Chiller/digitalObjects/resetStC2
  • /iso/identified-organization/dod/internet/private/enterprise/9839/instruments/kelvin-pCOWebMIB-Chiller/digitalObjects/mal_lp2
  • /iso/identified-organization/dod/internet/private/enterprise/9839/instruments/kelvin-pCOWebMIB-Chiller/digitalObjects/mal_alco1_68_r
  • /iso/identified-organization/dod/internet/private/enterprise/9839/instruments/kelvin-pCOWebMIB-Chiller/digitalObjects/alarm_e10
  • /iso/identified-organization/dod/internet/private/enterprise/9839/instruments/kelvin-pCOWebMIB-Chiller/digitalObjects/mall_pres_hpres
  • /iso/identified-organization/dod/internet/private/enterprise/9839/instruments/dap4-alMIB/digitalObjects/resetStC2
  • /iso/identified-organization/dod/internet/private/enterprise/9839/instruments/dap4-alMIB/digitalObjects/mal_lp2
  • /iso/identified-organization/dod/internet/private/enterprise/9839/instruments/dap4-alMIB/digitalObjects/mal_alco1_68_r
  • /iso/identified-organization/dod/internet/private/enterprise/9839/instruments/dap4-alMIB/digitalObjects/alarm_e10
  • /iso/identified-organization/dod/internet/private/enterprise/9839/instruments/dap4-alMIB/digitalObjects/mall_pres_hpres
  • /iso/identified-organization/dod/internet/private/enterprise/9839/instruments/uacMIB/digitalObjects/resetStC2
  • Additional combinations skipped.

SNMP properties

Value type
Integer32
Units
N/A
Maximum access defined by MIB
read-write, read-only
Status in MIB
current

Definitions may combine these properties differently.

Compare 2 source variants

Variant 1 — Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)

Value type
Integer32
Units
N/A
Maximum access defined by MIB
read-write
Status in MIB
current
Allowed ranges
0–1

Variant 2 — Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)

Value type
Integer32
Units
N/A
Maximum access defined by MIB
read-only
Status in MIB
current
Allowed ranges
0–1

Using this OID with SNMP

At least one MIB declaration places this object in a scalar group. A scalar instance uses the suffix .0.

snmpget [connection options] DEVICE .1.3.6.1.4.1.9839.2.1.1.83.0

Replace the placeholders with your connection and authentication options. Available permissions and device support can differ from the MIB.

Properties come from available MIB definitions. Actual device support and access can differ. See source records below for original files and qualifications.

Available source records contain 5 distinct definitions; some records may not include a definition.

Show 5 published definitions

resetStC2 · current

resetStC2 OBJECT-TYPE
                    SYNTAX Integer32 (0..1)
                    UNITS "N/A"
                    MAX-ACCESS read-write
                    STATUS current
                    DESCRIPTION "Compressor 2 Starting Counter Reset "
                    ::= { digitalObjects 83 }

mal_lp2 · current

mal_lp2 OBJECT-TYPE
                    SYNTAX Integer32 (0..1)
                    UNITS "N/A"
                    MAX-ACCESS read-only
                    STATUS current
                    DESCRIPTION "Circuit 2 low pressure alarm"
                    ::= { digitalObjects 83 }

mall_pres_hpres · current

mall_pres_hpres OBJECT-TYPE
                    SYNTAX Integer32 (0..1)
                    UNITS "N/A"
                    MAX-ACCESS read-only
                    STATUS current
                    DESCRIPTION "General high pressure switch alarm"
                    ::= { digitalObjects 83 }

alarm_e10 · current

alarm_e10 OBJECT-TYPE
                    SYNTAX Integer32 (0..1)
                    UNITS "N/A"
                    MAX-ACCESS read-only
                    STATUS current
                    DESCRIPTION "Alarm humidifier e10 lack of current"
                    ::= { digitalObjects 83 }

mal_alco1_68_r · current

mal_alco1_68_r OBJECT-TYPE
                    SYNTAX Integer32 (0..1)
                    UNITS "N/A"
                    MAX-ACCESS read-only
                    STATUS current
                    DESCRIPTION "Valve stepper motor error alarm"
                    ::= { digitalObjects 83 }

Meaning

Descriptions

5 unique

Identical descriptions are grouped. Different wording and device-specific notes are retained.

Description 1

Compressor 2 Starting Counter Reset
Original text from OID Repository
resetStC2 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Compressor 2 Starting Counter Reset "
Sources for this description

Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)

See 1 matching source record

OID Repository

View at oid-base.com

Description 2

Circuit 2 low pressure alarm

Sources for this description

Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)

See 1 matching source record

Description 3

General high pressure switch alarm

Sources for this description

Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)

See 1 matching source record

Description 4

Alarm humidifier e10 lack of current

Sources for this description

Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)

See 1 matching source record

Description 5

Valve stepper motor error alarm

Sources for this description

Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)

See 1 matching source record

Evidence

Source records

5 records

Matching descriptions are grouped; representative source files are shown for each definition.

Records for description 1Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)1 record · 1 source

Description 1

resetStC2 · currentMultiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)1 source

Status in source: current.

Names: resetStC2

Technical details
{
  "smi_kind": "OBJECT-TYPE",
  "definition": [
    "resetStC2",
    "OBJECT-TYPE",
    "SYNTAX",
    "Integer32",
    "(",
    "0",
    ".",
    ".",
    "1",
    ")",
    "UNITS",
    [
      "literal",
      "224e2f4122"
    ],
    "MAX-ACCESS",
    "read-write",
    "STATUS",
    "current",
    "DESCRIPTION",
    "\"Compressor 2 Starting Counter Reset \"",
    "::=",
    "{",
    "digitalObjects",
    "83",
    "}"
  ],
  "syntax_tree": [
    [
      "SimpleSyntax",
      "Integer32",
      [
        "integerSubType",
        [
          [
            0,
            1
          ]
        ]
      ]
    ],
    [
      "UNITS",
      "N/A"
    ],
    [
      "MaxAccessPart",
      "read-write"
    ],
    [
      "Status",
      "current"
    ],
    [
      "DESCRIPTION",
      "Compressor 2 Starting Counter Reset"
    ],
    null,
    null,
    null,
    null
  ]
}
Records for description 2Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)1 record · 1 source

Description 2

mal_lp2 · currentMultiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)1 source

Status in source: current.

Names: mal_lp2

Technical details
{
  "smi_kind": "OBJECT-TYPE",
  "definition": [
    "mal_lp2",
    "OBJECT-TYPE",
    "SYNTAX",
    "Integer32",
    "(",
    "0",
    ".",
    ".",
    "1",
    ")",
    "UNITS",
    [
      "literal",
      "224e2f4122"
    ],
    "MAX-ACCESS",
    "read-only",
    "STATUS",
    "current",
    "DESCRIPTION",
    "\"Circuit 2 low pressure alarm\"",
    "::=",
    "{",
    "digitalObjects",
    "83",
    "}"
  ],
  "syntax_tree": [
    [
      "SimpleSyntax",
      "Integer32",
      [
        "integerSubType",
        [
          [
            0,
            1
          ]
        ]
      ]
    ],
    [
      "UNITS",
      "N/A"
    ],
    [
      "MaxAccessPart",
      "read-only"
    ],
    [
      "Status",
      "current"
    ],
    [
      "DESCRIPTION",
      "Circuit 2 low pressure alarm"
    ],
    null,
    null,
    null,
    null
  ]
}
Records for description 3Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)1 record · 1 source

Description 3

mall_pres_hpres · currentMultiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)1 source

Status in source: current.

Names: mall_pres_hpres

Technical details
{
  "smi_kind": "OBJECT-TYPE",
  "definition": [
    "mall_pres_hpres",
    "OBJECT-TYPE",
    "SYNTAX",
    "Integer32",
    "(",
    "0",
    ".",
    ".",
    "1",
    ")",
    "UNITS",
    [
      "literal",
      "224e2f4122"
    ],
    "MAX-ACCESS",
    "read-only",
    "STATUS",
    "current",
    "DESCRIPTION",
    "\"General high pressure switch alarm\"",
    "::=",
    "{",
    "digitalObjects",
    "83",
    "}"
  ],
  "syntax_tree": [
    [
      "SimpleSyntax",
      "Integer32",
      [
        "integerSubType",
        [
          [
            0,
            1
          ]
        ]
      ]
    ],
    [
      "UNITS",
      "N/A"
    ],
    [
      "MaxAccessPart",
      "read-only"
    ],
    [
      "Status",
      "current"
    ],
    [
      "DESCRIPTION",
      "General high pressure switch alarm"
    ],
    null,
    null,
    null,
    null
  ]
}
Records for description 4Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)1 record · 1 source

Description 4

alarm_e10 · currentMultiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)1 source

Status in source: current.

Names: alarm_e10

Technical details
{
  "smi_kind": "OBJECT-TYPE",
  "definition": [
    "alarm_e10",
    "OBJECT-TYPE",
    "SYNTAX",
    "Integer32",
    "(",
    "0",
    ".",
    ".",
    "1",
    ")",
    "UNITS",
    [
      "literal",
      "224e2f4122"
    ],
    "MAX-ACCESS",
    "read-only",
    "STATUS",
    "current",
    "DESCRIPTION",
    "\"Alarm humidifier e10 lack of current\"",
    "::=",
    "{",
    "digitalObjects",
    "83",
    "}"
  ],
  "syntax_tree": [
    [
      "SimpleSyntax",
      "Integer32",
      [
        "integerSubType",
        [
          [
            0,
            1
          ]
        ]
      ]
    ],
    [
      "UNITS",
      "N/A"
    ],
    [
      "MaxAccessPart",
      "read-only"
    ],
    [
      "Status",
      "current"
    ],
    [
      "DESCRIPTION",
      "Alarm humidifier e10 lack of current"
    ],
    null,
    null,
    null,
    null
  ]
}
Records for description 5Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)1 record · 1 source

Description 5

mal_alco1_68_r · currentMultiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)1 source

Status in source: current.

Names: mal_alco1_68_r

Technical details
{
  "smi_kind": "OBJECT-TYPE",
  "definition": [
    "mal_alco1_68_r",
    "OBJECT-TYPE",
    "SYNTAX",
    "Integer32",
    "(",
    "0",
    ".",
    ".",
    "1",
    ")",
    "UNITS",
    [
      "literal",
      "224e2f4122"
    ],
    "MAX-ACCESS",
    "read-only",
    "STATUS",
    "current",
    "DESCRIPTION",
    "\"Valve stepper motor error alarm\"",
    "::=",
    "{",
    "digitalObjects",
    "83",
    "}"
  ],
  "syntax_tree": [
    [
      "SimpleSyntax",
      "Integer32",
      [
        "integerSubType",
        [
          [
            0,
            1
          ]
        ]
      ]
    ],
    [
      "UNITS",
      "N/A"
    ],
    [
      "MaxAccessPart",
      "read-only"
    ],
    [
      "Status",
      "current"
    ],
    [
      "DESCRIPTION",
      "Valve stepper motor error alarm"
    ],
    null,
    null,
    null,
    null
  ]
}

Registration

Registration authorities

First Registration Authority (inferred from ancestor 1.3.6.1.4.1.9839)

Fiorindo Sebastiano

Siblings (185)

OIDNameDirect childrenDescendantsDescription
1.3.6.1.4.1.9839.2.1.1.102 c13-on, mal_b600
1.3.6.1.4.1.9839.2.1.1.103 c21-on, en_high_refresh, mal_b700
1.3.6.1.4.1.9839.2.1.1.104 c22-on, mal_b800
1.3.6.1.4.1.9839.2.1.1.105 c23-on, mal_h_main_pump00
1.3.6.1.4.1.9839.2.1.1.106 pump1-on, mal_h_comp100
1.3.6.1.4.1.9839.2.1.1.107 pump2-on, mal_h_comp200
1.3.6.1.4.1.9839.2.1.1.108 on-fan-gr1, mal_h_comp300
1.3.6.1.4.1.9839.2.1.1.109 on-fan-gr2, mal_h_comp400
1.3.6.1.4.1.9839.2.1.1.110 fc-on, mal_clock3200
1.3.6.1.4.1.9839.2.1.1.112 en_off_supervisor00
1.3.6.1.4.1.9839.2.1.1.114 control_type1, fan500
1.3.6.1.4.1.9839.2.1.1.115 control_type2, mall_term_vent500
1.3.6.1.4.1.9839.2.1.1.116 en_inv_dev100
1.3.6.1.4.1.9839.2.1.1.117 en_rotation100
1.3.6.1.4.1.9839.2.1.1.118 en_rotation2, en_on_balck_out00
1.3.6.1.4.1.9839.2.1.1.119 on_off_boss, dout100
1.3.6.1.4.1.9839.2.1.1.120 cel_fahr, dout200
1.3.6.1.4.1.9839.2.1.1.121 en_air_temp, dout300
1.3.6.1.4.1.9839.2.1.1.122 dout400
1.3.6.1.4.1.9839.2.1.1.123 dout500
1.3.6.1.4.1.9839.2.1.1.124 bool_device11, dout600
1.3.6.1.4.1.9839.2.1.1.125 off_mode, dout700
1.3.6.1.4.1.9839.2.1.1.126 cool_heat, dout800
1.3.6.1.4.1.9839.2.1.1.127 dout900
1.3.6.1.4.1.9839.2.1.1.128 dout1000
1.3.6.1.4.1.9839.2.1.1.129 dout1100
1.3.6.1.4.1.9839.2.1.1.130 en-on-off-rem, dout1200
1.3.6.1.4.1.9839.2.1.1.131 unit-on, dout1300
1.3.6.1.4.1.9839.2.1.1.132 dout1400
1.3.6.1.4.1.9839.2.1.1.133 dout1500
1.3.6.1.4.1.9839.2.1.1.134 dout1600
1.3.6.1.4.1.9839.2.1.1.135 dout1700
1.3.6.1.4.1.9839.2.1.1.136 dout1800
1.3.6.1.4.1.9839.2.1.1.148 disch-alarm-scw-100
1.3.6.1.4.1.9839.2.1.1.149 disch-alarm-scw-200
1.3.6.1.4.1.9839.2.1.1.150 al-probe-inlet00
1.3.6.1.4.1.9839.2.1.1.151 al-probe-amb00
1.3.6.1.4.1.9839.2.1.1.152 al-frigo-fl100
1.3.6.1.4.1.9839.2.1.1.153 al-idro-pump100
1.3.6.1.4.1.9839.2.1.1.154 al-idro-pump200
1.3.6.1.4.1.9839.2.1.1.155 al-idro-fl100
1.3.6.1.4.1.9839.2.1.1.156 al-warning-fl100
1.3.6.1.4.1.9839.2.1.1.157 al-hi-water-temp00
1.3.6.1.4.1.9839.2.1.1.158 al-lo-water-temp00
1.3.6.1.4.1.9839.2.1.1.159 al-ta-probe100
1.3.6.1.4.1.9839.2.1.1.160 al-hi-press00
1.3.6.1.4.1.9839.2.1.1.161 al-lo-press00
1.3.6.1.4.1.9839.2.1.1.162 al-probe-evap-100
1.3.6.1.4.1.9839.2.1.1.163 al-probe-evap-200
1.3.6.1.4.1.9839.2.1.1.164 al-hi-press-100