Available source records contain 20 distinct definitions; some records may not include a definition.
Show 20 published definitions
differenz_all · current
differenz_all OBJECT-TYPE
SYNTAX Integer32 (-990..990)
UNITS "bar x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Alarm differential (absolute value)"
DEFVAL { 20 }
::= { analogObjects 11 }s_temp_setpoint · current
s_temp_setpoint OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Cooling set point (evaporator set point)"
DEFVAL { 120 }
::= { analogObjects 11 }comp_setp · current
comp_setp OBJECT-TYPE
SYNTAX Integer32 (-990..999)
UNITS "min x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Compensation setpoint"
DEFVAL { 250 }
::= { analogObjects 11 }ht-set · current
ht-set OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "deg.C"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Room High Temp. Alarm Threshold"
::= { analogObjects 11 }setpoint_night · current
setpoint_night OBJECT-TYPE
SYNTAX Integer32 (-200..200)
UNITS "°C/°F x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Automatic variation of night-time set point"
DEFVAL { 30 }
::= { analogObjects 11 }cw-ain-offs · current
cw-ain-offs OBJECT-TYPE
SYNTAX Integer32 (-32768..32767)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Chilled Water Temperature Sensor Calibration - Optional chilled water temperature sensor required (B10)"
DEFVAL { 0 }
::= { analogObjects 11 }setpoint-ASB-Inverter-pumps · current
setpoint-ASB-Inverter-pumps OBJECT-TYPE
SYNTAX Integer32 (-999..999)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Setpoint ASB Inverter pumps"
::= { analogObjects 11 }diff_estate · current
diff_estate OBJECT-TYPE
SYNTAX Integer32 (3..199)
UNITS "°C/°F x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Cooling differential"
DEFVAL { 30 }
::= { analogObjects 11 }max_assegnaz_consentita_utente · current
max_assegnaz_consentita_utente OBJECT-TYPE
SYNTAX Integer32 (-32767..990)
UNITS "°C x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Maximum set allowed to the user"
DEFVAL { 900 }
::= { analogObjects 11 }suctTemp2 · current
suctTemp2 OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "degrees C"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Circuit 2 Suction Temperature"
::= { analogObjects 11 }sum_setp_r1 · current
sum_setp_r1 OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "°C x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Temperature set point (cooling)"
DEFVAL { 200 }
::= { analogObjects 11 }dis_comp · current
dis_comp OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "OFF routine of the compressor"
::= { analogObjects 11 }s_temp_setpoint · current
s_temp_setpoint OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Cooling set point temperature"
::= { analogObjects 11 }sgl_alarl_max_rel · current
sgl_alarl_max_rel OBJECT-TYPE
SYNTAX Integer32 (0..1990)
UNITS "°C/°F x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "High temperature alarm"
DEFVAL { 0 }
::= { analogObjects 11 }sgl_l_umid · current
sgl_l_umid OBJECT-TYPE
SYNTAX Integer32 (0..1000)
UNITS "% x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Low humidity alarm offset"
DEFVAL { 200 }
::= { analogObjects 11 }min_set_co · current
min_set_co OBJECT-TYPE
SYNTAX Integer32 (-99..999)
UNITS "bar x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Minimum compressor Set Point"
DEFVAL { 25 }
::= { analogObjects 11 }v4l · current
v4l OBJECT-TYPE
SYNTAX Integer32 (-2000..32767)
UNITS "bar/… x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Min value of probe 4"
DEFVAL { 0 }
::= { analogObjects 11 }fan_on_cond · current
fan_on_cond OBJECT-TYPE
SYNTAX Integer32 (0..199)
UNITS "°C/°F x10"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Temperature off condensator fan."
::= { analogObjects 11 }setp_est_r1 · current
setp_est_r1 OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "°C/°F x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Cooling Set-point"
DEFVAL { 400 }
::= { analogObjects 11 }differenz_all · current
differenz_all OBJECT-TYPE
SYNTAX Integer32 (-990..990)
UNITS "°C x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Alarm differential (absolute value)"
DEFVAL { 20 }
::= { analogObjects 11 }