Available source records contain 15 distinct definitions; some records may not include a definition.
Show 15 published definitions
thresh_low2 · current
thresh_low2 OBJECT-TYPE
SYNTAX Integer32 (-990..999)
UNITS "°C/°F/bar x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Threshold low pression probe 2"
DEFVAL { 0 }
::= { analogObjects 16 }set_max_est_rb · current
set_max_est_rb OBJECT-TYPE
SYNTAX Integer32 (-32767..1940)
UNITS "°C/°F x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Max. Cooling set-point"
DEFVAL { 900 }
::= { analogObjects 16 }opt4-analog · current
opt4-analog OBJECT-TYPE
SYNTAX Integer32 (-32768..32767)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Value of the analog input"
DEFVAL { 0 }
::= { analogObjects 16 }reghyst · current
reghyst OBJECT-TYPE
SYNTAX Integer32 (0..199)
UNITS "°C/°F x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Regulator differential"
DEFVAL { 200 }
::= { analogObjects 16 }set1_max_ok · current
set1_max_ok OBJECT-TYPE
SYNTAX Integer32 (-32767..9990)
UNITS "°C x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Maximum value of St1"
::= { analogObjects 16 }coolRamp · current
coolRamp OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "%"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Cooling Valve Ramp"
::= { analogObjects 16 }derivative-Time-Inverter-Pumps-PID · current
derivative-Time-Inverter-Pumps-PID OBJECT-TYPE
SYNTAX Integer32 (-999..999)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Derivative Time Inverter Pumps PID"
::= { analogObjects 16 }htset-cw · current
htset-cw OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "CW High Temperature Alarm Threshold"
::= { analogObjects 16 }temp_minima_s1 · current
temp_minima_s1 OBJECT-TYPE
SYNTAX Integer32 (-500..900)
UNITS "°C x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Absolute minimum temperature probe S1"
DEFVAL { 900 }
::= { analogObjects 16 }o4 · current
o4 OBJECT-TYPE
SYNTAX Integer32 (-100..100)
UNITS "°C/°F x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Offset probe4"
DEFVAL { 0 }
::= { analogObjects 16 }thresh_low1 · current
thresh_low1 OBJECT-TYPE
SYNTAX Integer32 (-100..50)
UNITS "bar x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Suction low pressure alarm set"
DEFVAL { 10 }
::= { analogObjects 16 }set_temp_ariai · current
set_temp_ariai OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Winter Temp. Setpoint"
::= { analogObjects 16 }win_diff_r3 · current
win_diff_r3 OBJECT-TYPE
SYNTAX Integer32 (1..198)
UNITS "°C x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Heating differential"
DEFVAL { 20 }
::= { analogObjects 16 }set1_max_ok · current
set1_max_ok OBJECT-TYPE
SYNTAX Integer32 (-32767..9990)
UNITS "bar x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Maximum value of St1"
::= { analogObjects 16 }min_set_inv · current
min_set_inv OBJECT-TYPE
SYNTAX Integer32 (-400..32767)
UNITS "°C/°F x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Min. Heating set-point"
DEFVAL { -400 }
::= { analogObjects 16 }