Reference record for OID 1.3.6.1.4.1.223.10.6.17.1.6



parent
1.3.6.1.4.1.223.10.6.17.1 (uemSensorTableEntry)
node code
6
node name
uemSensorValue
dot oid
1.3.6.1.4.1.223.10.6.17.1.6
type
OBJECT-TYPE
asn1 oid
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) unisys(223) unisysOpen(10) unisysEnvMonitor(6) uemSensorTable(17) uemSensorTableEntry(1) uemSensorValue(6)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) unisys(223) unisysOpen(10) unisysEnvMonitor(6) uemSensorTable(17) uemSensorTableEntry(1) uemSensorValue(6)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprise(1) unisys(223) unisysOpen(10) unisysEnvMonitor(6) uemSensorTable(17) uemSensorTableEntry(1) uemSensorValue(6)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) unisys(223) unisysOpen(10) unisysEnvMonitor(6) uemSensorTable(17) uemSensorTableEntry(1) uemSensorValue(6)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprise(1) unisys(223) unisysOpen(10) unisysEnvMonitor(6) uemSensorTable(17) uemSensorTableEntry(1) uemSensorValue(6)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprises(1) unisys(223) unisysOpen(10) unisysEnvMonitor(6) uemSensorTable(17) uemSensorTableEntry(1) uemSensorValue(6)}
  • iri oid
  • /iso/identified-organization/dod/internet/private/enterprise/unisys/unisysOpen/unisysEnvMonitor/uemSensorTable/uemSensorTableEntry/uemSensorValue
  • /iso/identified-organization/dod/internet/private/enterprises/unisys/unisysOpen/unisysEnvMonitor/uemSensorTable/uemSensorTableEntry/uemSensorValue
  • /iso/org/dod/internet/private/enterprise/unisys/unisysOpen/unisysEnvMonitor/uemSensorTable/uemSensorTableEntry/uemSensorValue
  • /iso/org/dod/internet/private/enterprises/unisys/unisysOpen/unisysEnvMonitor/uemSensorTable/uemSensorTableEntry/uemSensorValue
  • /iso/iso-identified-organization/dod/internet/private/enterprise/unisys/unisysOpen/unisysEnvMonitor/uemSensorTable/uemSensorTableEntry/uemSensorValue
  • /iso/iso-identified-organization/dod/internet/private/enterprises/unisys/unisysOpen/unisysEnvMonitor/uemSensorTable/uemSensorTableEntry/uemSensorValue
  • iri by oid_info
    /ISO/Identified-Organization/6/1/4/1/223/10/6/17/1/6

    Description by mibdepot

    The current numeric value of the sensor. The interpretation of this
    value is related to the type of sensor.
    Fan sensor values are reported in rpms (revolutions per minute).
    Voltage sensor values are reported in millivolts.
    A value of 3300 means 3.3 volts.
    Temperature sensor values are reported as hundreths of Celsius degrees.
    A value of 2500 means 25.0 degrees.

    Parsed from file VisiNet2_mib.txt
    Company: None
    Module: VISINET2-MIB

    Description by circitor

    The current numeric value of the sensor. The interpretation of this
    value is related to the type of sensor.
    Fan sensor values are reported in rpms (revolutions per minute).
    Voltage sensor values are reported in millivolts.
    A value of 3300 means 3.3 volts.
    Temperature sensor values are reported as hundreths of Celsius degrees.
    A value of 2500 means 25.0 degrees.

    Parsed from file VISINET2-MIB.mib
    Module: VISINET2-MIB

    Information by oid_info

    Vendor: Unisys_Corp
    Module: VISINET2-MIB

    [Automatically extracted from oidview.com]

    Information by mibdepot

    uemSensorValue OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The current numeric value of the sensor. The interpretation of this value is related to the type of sensor. Fan sensor values are reported in rpms (revolutions per minute). Voltage sensor values are reported in millivolts. A value of 3300 means 3.3 volts. Temperature sensor values are reported as hundreths of Celsius degrees. A value of 2500 means 25.0 degrees." ::= { uemSensorTableEntry 6 }

    Information by circitor

    uemSensorValue OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The current numeric value of the sensor. The interpretation of this value is related to the type of sensor. Fan sensor values are reported in rpms (revolutions per minute). Voltage sensor values are reported in millivolts. A value of 3300 means 3.3 volts. Temperature sensor values are reported as hundreths of Celsius degrees. A value of 2500 means 25.0 degrees." ::= { uemSensorTableEntry 6 }

    First Registration Authority (recovered by parent 1.3.6.1.4.1.223)

    Brow Lawrence

    Brothers (15)

    OIDNameSub childrenSub Nodes TotalDescription
    1.3.6.1.4.1.223.10.6.17.1.1 uemSensorIndex 0 0 A unique value for each sensor in the monitored system.
    Note: if there are multiple environmental monitoring cards in a
    system, a…
    1.3.6.1.4.1.223.10.6.17.1.2 uemSensorEnvMonIndex 0 0 A link into the EnvMonitor device table. This identifies which environmental
    device is managing this sensor.
    1.3.6.1.4.1.223.10.6.17.1.3 uemSensorType 0 0 The general classification of this sensor.
    1.3.6.1.4.1.223.10.6.17.1.4 uemSensorDescription 0 0 Text describing this sensor.
    1.3.6.1.4.1.223.10.6.17.1.5 uemSensorStatus 0 0 The current state of the sensor.
    1.3.6.1.4.1.223.10.6.17.1.7 uemSensorNominalValue 0 0 This is the normal value expected to be reported by this sensor in
    a properly operating system.
    1.3.6.1.4.1.223.10.6.17.1.8 uemSensorHighCriticalValue 0 0 When the sensor exceeds this value, a critical trap is sent.
    When appropriate, this test point can be disabled by setting
    it to t…
    1.3.6.1.4.1.223.10.6.17.1.9 uemSensorHighCriticalLabel 0 0 Text describing this test point.
    1.3.6.1.4.1.223.10.6.17.1.10 uemSensorHighWarningValue 0 0 When the sensor value exceeds this value, a warning trap is sent.
    This test point is disabled by setting it to the same value as…
    1.3.6.1.4.1.223.10.6.17.1.11 uemSensorHighWarningLabel 0 0 Text describing this test point.
    1.3.6.1.4.1.223.10.6.17.1.12 uemSensorLowWarningValue 0 0 When the sensor value goes below this value, a warning trap is sent.
    This test point can be disabled by setting it to the same v…
    1.3.6.1.4.1.223.10.6.17.1.13 uemSensorLowWarningLabel 0 0 Text describing this test point.
    1.3.6.1.4.1.223.10.6.17.1.14 uemSensorLowCriticalValue 0 0 When the sensor goes below this value, a critical trap is sent.
    This test point can be disabled by setting it to zero.
    1.3.6.1.4.1.223.10.6.17.1.15 uemSensorLowCriticalLabel 0 0 Text describing this test point.
    1.3.6.1.4.1.223.10.6.17.1.16 uemSensorEnabled 0 0 If this field is FALSE, the sensor is disabled. No traps will be sent
    from a disabled sensor.