The maximum line voltage in VAC allowed before the
UPS system transfers to battery backup.
Allowed values depend on the UPS used:
100 volt units allow settings of 108, 110, 112, and 114.
120 volt units allow settings of 129, 132, 135, and 138.
208 volt units allow settings of 224, 229, 234, and 239.
230 volt units allow settings of 253, 264, 271, and 280.
Matrix Notes:
Matrix units configured for 208V input allow settings of
240, 244, 248, and 252. Matrix units configured for 240V
input allow settings of 276, 264, 253, and 282.
If a value other than a supported value is provided in a
set request, the UPS interprets it as the next lower
acceptable value. If the provided value is lower than
the lowest acceptable value, the lowest acceptable
value is used.
Parsed from file powernet.mib.txt
Company: None
Module: PowerNet-MIB
upsAdvConfigHightransferVolt
View at oid-info.com
The maximum line voltage in VAC allowed before the
UPS system transfers to battery backup.
For a list of allowed values supported by your UPS model,
see the UPS User's Manual.
If a value other than a supported value is provided in a
set request, the UPS interprets it as a the next higher
acceptable value. If the provided value is higher than
the highest acceptable value, the highest acceptable
value is used.
Parsed from file PowerNet-MIB.mib
Module: PowerNet-MIB
upsAdvConfigHighTransferVolt OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The maximum line voltage in VAC allowed before the UPS system transfers to battery backup. Allowed values depend on the UPS used: 100 volt units allow settings of 108, 110, 112, and 114. 120 volt units allow settings of 129, 132, 135, and 138. 208 volt units allow settings of 224, 229, 234, and 239. 230 volt units allow settings of 253, 264, 271, and 280. Matrix Notes: Matrix units configured for 208V input allow settings of 240, 244, 248, and 252. Matrix units configured for 240V input allow settings of 276, 264, 253, and 282. If a value other than a supported value is provided in a set request, the UPS interprets it as the next lower acceptable value. If the provided value is lower than the lowest acceptable value, the lowest acceptable value is used." ::= { upsAdvConfig 2 }
Vendor: American Power Conversion Corp.
Module: PowerNet-MIB
[Automatically extracted from oidview.com]
upsAdvConfigHighTransferVolt OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The maximum line voltage in VAC allowed before the UPS system transfers to battery backup. For a list of allowed values supported by your UPS model, see the UPS User's Manual. If a value other than a supported value is provided in a set request, the UPS interprets it as a the next higher acceptable value. If the provided value is higher than the highest acceptable value, the highest acceptable value is used." ::= { upsAdvConfig 2 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.1.5.2.2.0 | upsAdvConfigHighTransferVolt | 0 | 0 | upsAdvConfigHightransferVolt |
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.1.5.2.1 | upsAdvConfigRatedOutputVoltage | 1 | 1 | The nominal output voltage from the UPS in VAC. For a list of allowed values supported by your UPS model, see the UPS User's Manu… |
1.3.6.1.4.1.318.1.1.1.5.2.3 | upsAdvConfigLowTransferVolt | 1 | 1 | The minimum line voltage in VAC allowed before the UPS system transfers to battery backup. For a list of allowed values supporte… |
1.3.6.1.4.1.318.1.1.1.5.2.4 | upsAdvConfigAlarm | 1 | 1 | A flag indicating how the UPS should handle audible line fail alarms. |
1.3.6.1.4.1.318.1.1.1.5.2.5 | upsAdvConfigAlarmTimer | 1 | 1 | The time after initial line failure at which the UPS begins emitting audible alarms (beeping). This timer is observed only if th… |
1.3.6.1.4.1.318.1.1.1.5.2.6 | upsAdvConfigMinReturnCapacity | 1 | 1 | The minimum battery capacity required before the UPS will return from a low battery shutdown condition. The capacity is measured… |
1.3.6.1.4.1.318.1.1.1.5.2.7 | upsAdvConfigSensitivity | 1 | 1 | The sensitivity of the UPS to utility line abnormalities or noises. |
1.3.6.1.4.1.318.1.1.1.5.2.8 | upsAdvConfigLowBatteryRunTime | 1 | 1 | The desired run time of the UPS, in seconds, once the low battery condition is reached. Allowed values are 120, 300, 420, or 600… |
1.3.6.1.4.1.318.1.1.1.5.2.9 | upsAdvConfigReturnDelay | 1 | 1 | The delay in seconds after utility line power returns before the UPS will turn on. This value is also used when the UPS comes ou… |
1.3.6.1.4.1.318.1.1.1.5.2.10 | upsAdvConfigShutoffDelay | 1 | 1 | The delay in seconds the UPS remains on after being told to turn off. Allowed values are 20, 180, 300, and 600 seconds. If a valu… |
1.3.6.1.4.1.318.1.1.1.5.2.11 | upsAdvConfigUpsSleepTime | 1 | 1 | The time in seconds for the UPS to go to 'sleep' when instructed. When in sleep mode, the UPS will not provide output power rega… |
1.3.6.1.4.1.318.1.1.1.5.2.12 | upsAdvConfigSetEEPROMDefaults | 1 | 1 | WRITE: Resets the UPS EEPROM variables to default values. READ: returns 0 |
1.3.6.1.4.1.318.1.1.1.5.2.13 | upsAdvConfigDipSwitchTable, upsAdvConfigDipSwitchSetting | 1 | 3 | upsAdvConfigDipSwitchtable |
1.3.6.1.4.1.318.1.1.1.5.2.14 | upsAdvConfigBattExhaustThresh | 1 | 1 | The number of seconds prior to battery exhaustion when the UPS will switch off power to its load. |
1.3.6.1.4.1.318.1.1.1.5.2.15 | upsAdvConfigPassword | 1 | 1 | The password entered at the UPS front panel to enable local configuation of the EEProm. If the password is disabled or is not sup… |
1.3.6.1.4.1.318.1.1.1.5.2.16 | upsAdvConfigAllowedSetTable | 1 | 4 | The table listing the allowed values for all discrete configurable UPS variables. |
1.3.6.1.4.1.318.1.1.1.5.2.17 | upsAdvConfigBattCabAmpHour | 1 | 1 | Configure the amp-hour setting of the UPS battery cabinet. |
1.3.6.1.4.1.318.1.1.1.5.2.18 | upsAdvConfigPositionSelector | 1 | 1 | Configure UPS position selector. If the UPS doesn't support this configuration it will report unknown (1). The positions are eit… |
1.3.6.1.4.1.318.1.1.1.5.2.19 | upsAdvConfigOutputFreqRange | 1 | 1 | Configure the output frequency tolerance range. unknown(1) indicates the output frequency is unknown. freqRangeAUTO(2) configure … |
1.3.6.1.4.1.318.1.1.1.5.2.20 | upsAdvConfigUPSFail | 1 | 1 | Configure the UPS fail action. If UPS fails, and frequency or voltage is out of range it will either GotoBypass (2) or DropLoad … |
1.3.6.1.4.1.318.1.1.1.5.2.21 | upsAdvConfigAlarmRedundancy | 1 | 1 | Configure settings of UPS alarm if the redundancy is under the current redundancy. Use 0 for never. |
1.3.6.1.4.1.318.1.1.1.5.2.22 | upsAdvConfigAlarmLoadOver | 1 | 1 | Configure settings of UPS alarm if the load is over the current load in kVA. Use -1 for never. |
1.3.6.1.4.1.318.1.1.1.5.2.23 | upsAdvConfigAlarmRuntimeUnder | 1 | 1 | Configure settings of UPS alarm if the runtime is under the current time of minutes. Use -1 for never. |
1.3.6.1.4.1.318.1.1.1.5.2.24 | upsAdvConfigVoutReporting | 1 | 1 | Configure the way the UPS scales its output voltage readings. unknown(1) indicates the Vout Reporting is unknown. voutAUTO(2) con… |
1.3.6.1.4.1.318.1.1.1.5.2.25 | upsAdvConfigNumExternalBatteries | 1 | 1 | Configure the number of external batteries connected to the UPS. |
1.3.6.1.4.1.318.1.1.1.5.2.26 | upsAdvConfigSimpleSignalShutdowns | 1 | 1 | Configure Simple Signal shutdown commands from the Simple Signal port to be issued to the UPS. unknown(1) indicates the Simple Si… |
1.3.6.1.4.1.318.1.1.1.5.2.27 | upsAdvConfigMaxShutdownTime | 1 | 1 | The maximum amount of time for server shutdown to complete before a UPS shutdown occurs. |
1.3.6.1.4.1.318.1.1.1.5.2.28 | upsAsiUpsControlServerRequestShutdown | 1 | 1 | Start a server shutdown sequence: serverShutdownOff: Shutdown server and turn off UPS serverShutdownReboot: Shutdown server and t… |
1.3.6.1.4.1.318.1.1.1.5.2.29 | upsAdvConfigMinReturnRuntime | 1 | 1 | The minimum amount of run time in seconds required before the output will be turned on, using power calculation captured at star… |
1.3.6.1.4.1.318.1.1.1.5.2.30 | upsAdvConfigBasicSignalLowBatteryDuration | 1 | 1 | The duration of runtime in seconds during an on-battery condition at which the UPS will signal the basic low battery shutdown co… |
1.3.6.1.4.1.318.1.1.1.5.2.31 | upsAdvConfigBypassPhaseLockRequired | 1 | 1 | Sets the condition for when bypass is an acceptable mode of operation as a requirement. |
1.3.6.1.4.1.318.1.1.1.5.2.32 | upsAdvConfigOutputFreqSlewRate | 1 | 1 | The rate at which the UPS will change its output frequency in response to utility frequency changes. |
1.3.6.1.4.1.318.1.1.1.5.2.33 | upsAdvConfigChargerLevel | 1 | 1 | Sets the rate at which the UPS charges its batteries. |
1.3.6.1.4.1.318.1.1.1.5.2.34 | upsAdvConfigBypassToleranceSetting | 1 | 1 | This setting allows selecting from standard bypass tolerance configurations to suit their situation. |
1.3.6.1.4.1.318.1.1.1.5.2.35 | upsAdvConfigMainsSetting | 1 | 1 | Configure the type of mains supply system. singleInput (1) indicates a single supply system. dualInput (2) indicates a dual sup… |
1.3.6.1.4.1.318.1.1.1.5.2.36 | upsAdvConfigACWiringSetting | 1 | 1 | Configure the AC wiring of the system. threeWire (1) indicates 3-wire system configuration. fourWire (2) indicates 4-wire system… |
1.3.6.1.4.1.318.1.1.1.5.2.37 | upsAdvConfigUpperOutputVoltTolerance | 1 | 1 | Upper tolerance of the output RMS voltage before transferring to bypass. Expressed as percent of nominal voltage. |
1.3.6.1.4.1.318.1.1.1.5.2.38 | upsAdvConfigLowerOutputVoltTolerance | 1 | 1 | Lower tolerance of the output RMS voltage before transferring to bypass. Expressed as percent of nominal voltage. |
1.3.6.1.4.1.318.1.1.1.5.2.39 | upsAdvConfigUpperBypassVoltTolerance | 1 | 1 | Upper tolerance of the bypass voltage that allows transfer to bypass by user. Expressed as percent of nominal voltage. |
1.3.6.1.4.1.318.1.1.1.5.2.40 | upsAdvConfigLowerBypassVoltTolerance | 1 | 1 | Lower tolerance of the bypass voltage that allows transfer to bypass by user. Expressed as percent of nominal voltage. |
1.3.6.1.4.1.318.1.1.1.5.2.41 | upsAdvConfigOutofSyncBypassTransferDelay | 1 | 1 | Configure the time (in milliseconds), indicating the gap in output voltage if an asynchronous transfer to bypass needs to occur. |
1.3.6.1.4.1.318.1.1.1.5.2.43 | upsAdvConfigWarningAlarmDelay | 0 | 0 | Configure the time delay for reporting warning alarms (in seconds). |
1.3.6.1.4.1.318.1.1.1.5.2.44 | upsAdvConfigInformationalAlarmDelay | 0 | 0 | Configure the time delay for reporting informational alarms (in seconds). |
1.3.6.1.4.1.318.1.1.1.5.2.45 | upsAdvConfigGreenMode | 0 | 0 | Enable/Disable UPS green mode feature. |
1.3.6.1.4.1.318.1.1.1.5.2.46 | upsAdvConfigLCDLocalLanguage | 0 | 0 | Configure the language setting of the UPS LCD display information. |
1.3.6.1.4.1.318.1.1.1.5.2.47 | upsAdvConfigLCDLockOut | 0 | 0 | Enable/Disable the control function of the UPS via the LCD Display. |
1.3.6.1.4.1.318.1.1.1.5.2.48 | upsAdvConfigChargerRate | 0 | 0 | Change the maximum allowed UPS charge rate on select products where 100% represents the manufacturer's recommended rate. A char… |
1.3.6.1.4.1.318.1.1.1.5.2.49 | upsAdvConfigBatterySelection | 0 | 0 | Configure the installed battery type on select products where VRLA is Valve Regulated Lead Acid type battery and Vented Cell is … |