The target value for the selected control sensor air
for this mode. It must be at least 1.0 % RH below
the dehumidification setpoint. Measured in tenths of
percent relative humidity.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Parsed from file powernet.mib.txt
Company: None
Module: PowerNet-MIB
The target value for the selected control sensor air
for this mode. It must be at least 1.0 % RH below
the dehumidification setpoint. Measured in tenths of
percent relative humidity.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Parsed from file PowerNet-MIB.mib
Module: PowerNet-MIB
airFMSysHumSetpoint OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The target value for the selected control sensor air for this mode. It must be at least 1.0 % RH below the dehumidification setpoint. Measured in tenths of percent relative humidity. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration." ::= { airFMSysHumidify 3 }
Vendor: American Power Conversion Corp.
Module: PowerNet-MIB
[Automatically extracted from oidview.com]
airFMSysHumSetpoint OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The target value for the selected control sensor air for this mode. It must be at least 1.0 % RH below the dehumidification setpoint. Measured in tenths of percent relative humidity. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration." ::= { airFMSysHumidify 3 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.13.1.4.6.3.0 | airFMSysHumSetpoint | 0 | 0 | None |
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.13.1.4.6.1 | airFMSysHumState | 1 | 1 | Set the mode to enabled or disabled. Disabled modes will not operate, and you cannot make changes to their settings while they ar… |
1.3.6.1.4.1.318.1.1.13.1.4.6.2 | airFMSysHumEssFunction | 1 | 1 | Set the priority of the mode for alarms and events with the nonessential stop behavior. Nonessential modes are disabled during no… |
1.3.6.1.4.1.318.1.1.13.1.4.6.4 | airFMSysHumDeadband | 1 | 1 | The humidity range that controls output when the selected control sensor humidity is below the setpoint. At the top of this range… |
1.3.6.1.4.1.318.1.1.13.1.4.6.5 | airFMSysHumCtrlSetting | 1 | 1 | Set the method to control the humidity in the room. The two methods are Relative Humidity (RH) or Dew Point of the selected contr… |
1.3.6.1.4.1.318.1.1.13.1.4.6.6 | airFMSysActualHumCtrl | 1 | 1 | The humidity control method the system is using. A value of notApplicable indicates that this OID does not apply to this device d… |
1.3.6.1.4.1.318.1.1.13.1.4.6.7 | airFMSysHumSensBand | 1 | 1 | The percentage of relative humidity below the setpoint at which the humidifier will output at 100% of capacity. Measured in perc… |