The humidity range that controls output when the
selected control sensor humidity is below the
setpoint. At the top of this range, the
humidification mode outputs at 100%. The deadband
does not apply to PID-controlled modes. Measured in
tenths of percent relative humidity.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Parsed from file powernet.mib.txt
Company: None
Module: PowerNet-MIB
The humidity range that controls output when the
selected control sensor humidity is below the
setpoint. At the top of this range, the
humidification mode outputs at 100%. The deadband
does not apply to PID-controlled modes. Measured in
tenths of percent relative humidity.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Parsed from file PowerNet-MIB.mib
Module: PowerNet-MIB
airFMSysHumDeadband OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The humidity range that controls output when the selected control sensor humidity is below the setpoint. At the top of this range, the humidification mode outputs at 100%. The deadband does not apply to PID-controlled modes. Measured in tenths of percent relative humidity. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration." ::= { airFMSysHumidify 4 }
Vendor: American Power Conversion Corp.
Module: PowerNet-MIB
[Automatically extracted from oidview.com]
airFMSysHumDeadband OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The humidity range that controls output when the selected control sensor humidity is below the setpoint. At the top of this range, the humidification mode outputs at 100%. The deadband does not apply to PID-controlled modes. Measured in tenths of percent relative humidity. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration." ::= { airFMSysHumidify 4 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.13.1.4.6.4.0 | airFMSysHumDeadband | 0 | 0 | None |
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.13.1.4.6.1 | airFMSysHumState | 1 | 1 | Set the mode to enabled or disabled. Disabled modes will not operate, and you cannot make changes to their settings while they ar… |
1.3.6.1.4.1.318.1.1.13.1.4.6.2 | airFMSysHumEssFunction | 1 | 1 | Set the priority of the mode for alarms and events with the nonessential stop behavior. Nonessential modes are disabled during no… |
1.3.6.1.4.1.318.1.1.13.1.4.6.3 | airFMSysHumSetpoint | 1 | 1 | The target value for the selected control sensor air for this mode. It must be at least 1.0 % RH below the dehumidification setpo… |
1.3.6.1.4.1.318.1.1.13.1.4.6.5 | airFMSysHumCtrlSetting | 1 | 1 | Set the method to control the humidity in the room. The two methods are Relative Humidity (RH) or Dew Point of the selected contr… |
1.3.6.1.4.1.318.1.1.13.1.4.6.6 | airFMSysActualHumCtrl | 1 | 1 | The humidity control method the system is using. A value of notApplicable indicates that this OID does not apply to this device d… |
1.3.6.1.4.1.318.1.1.13.1.4.6.7 | airFMSysHumSensBand | 1 | 1 | The percentage of relative humidity below the setpoint at which the humidifier will output at 100% of capacity. Measured in perc… |