The lowest acceptable voltage condition at source 1.
When any phase of source 1 is lower than this voltage,
source quality is considered bad and the generator run signal
is asserted to begin generator operation.
Specified in volts, line-to-line for a 3-wire service or
line-to-neutral for a 4-wire service.
-1 if not available.
Parsed from file powernet.mib.txt
Company: None
Module: PowerNet-MIB
The lowest acceptable voltage condition at source 1.
When any phase of source 1 is lower than this voltage,
source quality is considered bad and the generator run signal
is asserted to begin generator operation.
Specified in volts, line-to-line for a 3-wire service or
line-to-neutral for a 4-wire service.
-1 if not available.
Parsed from file PowerNet-MIB.mib
Module: PowerNet-MIB
xATSSwitchSettingsLowVoltageTransferPoint OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The lowest acceptable voltage condition at source 1. When any phase of source 1 is lower than this voltage, source quality is considered bad and the generator run signal is asserted to begin generator operation. Specified in volts, line-to-line for a 3-wire service or line-to-neutral for a 4-wire service. -1 if not available." ::= { xATSSwitchSettings 1 }
Vendor: American Power Conversion Corp.
Module: PowerNet-MIB
[Automatically extracted from oidview.com]
xATSSwitchSettingsLowVoltageTransferPoint OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The lowest acceptable voltage condition at source 1. When any phase of source 1 is lower than this voltage, source quality is considered bad and the generator run signal is asserted to begin generator operation. Specified in volts, line-to-line for a 3-wire service or line-to-neutral for a 4-wire service. -1 if not available." ::= { xATSSwitchSettings 1 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.17.3.2.1.0 | xATSSwitchSettingsLowVoltageTransferPoint | 0 | 0 | None |
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.17.3.2.2 | xATSSwitchSettingsHighVoltageTransferPoint | 1 | 1 | The highest acceptable voltage condition at source 1. When any phase of source 1 is greater than this voltage, source quality is … |
1.3.6.1.4.1.318.1.1.17.3.2.3 | xATSSwitchSettingsMaxFrequencyDeviation | 1 | 1 | The maximum acceptable frequency deviation condition from nominal at source 1. When source 1 frequency is outside the specified … |
1.3.6.1.4.1.318.1.1.17.3.2.4 | xATSSwitchSettingsMinPhaseBalance | 1 | 1 | The minimum required phase balance at source 1. When the percentage difference between the minimum and maximum phase voltage meas… |
1.3.6.1.4.1.318.1.1.17.3.2.5 | xATSSwitchSettingsNominalRotation | 1 | 1 | The nominal phase rotation (or phase sequence) required by the load. For certain types of equipment, such as rotating machinery,… |
1.3.6.1.4.1.318.1.1.17.3.2.6 | xATSSwitchSettingsAllowClosedTransfer | 1 | 1 | This setting enables seamless (closed) transfers between sources. When possible, both source 1 and source 2 are closed to the ou… |
1.3.6.1.4.1.318.1.1.17.3.2.7 | xATSSwitchSettingsMaxSyncTime | 1 | 1 | When attempting/seeking to perform a closed transfer, this setting defines the maximum time allowed before the transfer switch w… |
1.3.6.1.4.1.318.1.1.17.3.2.8 | xATSSwitchSettingsNeutralTransferTime | 1 | 1 | This setting defines how long both source 1 and source 2 will be disconnected from the output, during an open transfer. Specified… |
1.3.6.1.4.1.318.1.1.17.3.2.9 | xATSSwitchSettingsClearLatchedAlarms | 1 | 1 | Clears any latched alarm conditions. |
1.3.6.1.4.1.318.1.1.17.3.2.10 | xATSSwitchSettingsSetToFactoryDefaults | 1 | 1 | Sets all transfer switch settings to factory default values. |