The nominal phase rotation (or phase sequence) required by the load.
For certain types of equipment, such as rotating machinery, phase rotation
is critical for proper operation as it determines the direction which motors
will rotate (clockwise or counterclockwise).
Source quality will be seen as bad if the rotation measured at that
ATS input does not match this setting.
If this setting is set to any, phase rotation is ignored.
Parsed from file powernet.mib.txt
Company: None
Module: PowerNet-MIB
The nominal phase rotation (or phase sequence) required by the load.
For certain types of equipment, such as rotating machinery, phase rotation
is critical for proper operation as it determines the direction which motors
will rotate (clockwise or counterclockwise).
Source quality will be seen as bad if the rotation measured at that
ATS input does not match this setting.
If this setting is set to any, phase rotation is ignored.
Parsed from file PowerNet-MIB.mib
Module: PowerNet-MIB
xATSSwitchSettingsNominalRotation OBJECT-TYPE SYNTAX INTEGER{ abc (1), cba (2), any (3), unknown (4) } ACCESS read-write STATUS mandatory DESCRIPTION "The nominal phase rotation (or phase sequence) required by the load. For certain types of equipment, such as rotating machinery, phase rotation is critical for proper operation as it determines the direction which motors will rotate (clockwise or counterclockwise). Source quality will be seen as bad if the rotation measured at that ATS input does not match this setting. If this setting is set to any, phase rotation is ignored." ::= { xATSSwitchSettings 5 }
Vendor: American Power Conversion Corp.
Module: PowerNet-MIB
[Automatically extracted from oidview.com]
xATSSwitchSettingsNominalRotation OBJECT-TYPE SYNTAX INTEGER{ abc (1), cba (2), any (3), unknown (4) } ACCESS read-write STATUS mandatory DESCRIPTION "The nominal phase rotation (or phase sequence) required by the load. For certain types of equipment, such as rotating machinery, phase rotation is critical for proper operation as it determines the direction which motors will rotate (clockwise or counterclockwise). Source quality will be seen as bad if the rotation measured at that ATS input does not match this setting. If this setting is set to any, phase rotation is ignored." ::= { xATSSwitchSettings 5 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.17.3.2.5.0 | xATSSwitchSettingsNominalRotation | 0 | 0 | None |
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.17.3.2.1 | xATSSwitchSettingsLowVoltageTransferPoint | 1 | 1 | The lowest acceptable voltage condition at source 1. When any phase of source 1 is lower than this voltage, source quality is con… |
1.3.6.1.4.1.318.1.1.17.3.2.2 | xATSSwitchSettingsHighVoltageTransferPoint | 1 | 1 | The highest acceptable voltage condition at source 1. When any phase of source 1 is greater than this voltage, source quality is … |
1.3.6.1.4.1.318.1.1.17.3.2.3 | xATSSwitchSettingsMaxFrequencyDeviation | 1 | 1 | The maximum acceptable frequency deviation condition from nominal at source 1. When source 1 frequency is outside the specified … |
1.3.6.1.4.1.318.1.1.17.3.2.4 | xATSSwitchSettingsMinPhaseBalance | 1 | 1 | The minimum required phase balance at source 1. When the percentage difference between the minimum and maximum phase voltage meas… |
1.3.6.1.4.1.318.1.1.17.3.2.6 | xATSSwitchSettingsAllowClosedTransfer | 1 | 1 | This setting enables seamless (closed) transfers between sources. When possible, both source 1 and source 2 are closed to the ou… |
1.3.6.1.4.1.318.1.1.17.3.2.7 | xATSSwitchSettingsMaxSyncTime | 1 | 1 | When attempting/seeking to perform a closed transfer, this setting defines the maximum time allowed before the transfer switch w… |
1.3.6.1.4.1.318.1.1.17.3.2.8 | xATSSwitchSettingsNeutralTransferTime | 1 | 1 | This setting defines how long both source 1 and source 2 will be disconnected from the output, during an open transfer. Specified… |
1.3.6.1.4.1.318.1.1.17.3.2.9 | xATSSwitchSettingsClearLatchedAlarms | 1 | 1 | Clears any latched alarm conditions. |
1.3.6.1.4.1.318.1.1.17.3.2.10 | xATSSwitchSettingsSetToFactoryDefaults | 1 | 1 | Sets all transfer switch settings to factory default values. |