The maximum acceptable frequency deviation condition from nominal at source 1.
When source 1 frequency is outside the specified range,
source quality is considered bad and the generator run signal
is asserted to begin generator operation.
Specified in tenths of Hertz above or below nominal.
A value of zero indicates that frequency is ignored when
determining source quality.
-1 if not available.
Parsed from file powernet.mib.txt
Company: None
Module: PowerNet-MIB
The maximum acceptable frequency deviation condition from nominal at source 1.
When source 1 frequency is outside the specified range,
source quality is considered bad and the generator run signal
is asserted to begin generator operation.
Specified in tenths of Hertz above or below nominal.
A value of zero indicates that frequency is ignored when
determining source quality.
-1 if not available.
Parsed from file PowerNet-MIB.mib
Module: PowerNet-MIB
xATSSwitchSettingsMaxFrequencyDeviation OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The maximum acceptable frequency deviation condition from nominal at source 1. When source 1 frequency is outside the specified range, source quality is considered bad and the generator run signal is asserted to begin generator operation. Specified in tenths of Hertz above or below nominal. A value of zero indicates that frequency is ignored when determining source quality. -1 if not available." ::= { xATSSwitchSettings 3 }
Vendor: American Power Conversion Corp.
Module: PowerNet-MIB
[Automatically extracted from oidview.com]
xATSSwitchSettingsMaxFrequencyDeviation OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The maximum acceptable frequency deviation condition from nominal at source 1. When source 1 frequency is outside the specified range, source quality is considered bad and the generator run signal is asserted to begin generator operation. Specified in tenths of Hertz above or below nominal. A value of zero indicates that frequency is ignored when determining source quality. -1 if not available." ::= { xATSSwitchSettings 3 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.17.3.2.3.0 | xATSSwitchSettingsMaxFrequencyDeviation | 0 | 0 | None |
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.17.3.2.1 | xATSSwitchSettingsLowVoltageTransferPoint | 1 | 1 | The lowest acceptable voltage condition at source 1. When any phase of source 1 is lower than this voltage, source quality is con… |
1.3.6.1.4.1.318.1.1.17.3.2.2 | xATSSwitchSettingsHighVoltageTransferPoint | 1 | 1 | The highest acceptable voltage condition at source 1. When any phase of source 1 is greater than this voltage, source quality is … |
1.3.6.1.4.1.318.1.1.17.3.2.4 | xATSSwitchSettingsMinPhaseBalance | 1 | 1 | The minimum required phase balance at source 1. When the percentage difference between the minimum and maximum phase voltage meas… |
1.3.6.1.4.1.318.1.1.17.3.2.5 | xATSSwitchSettingsNominalRotation | 1 | 1 | The nominal phase rotation (or phase sequence) required by the load. For certain types of equipment, such as rotating machinery,… |
1.3.6.1.4.1.318.1.1.17.3.2.6 | xATSSwitchSettingsAllowClosedTransfer | 1 | 1 | This setting enables seamless (closed) transfers between sources. When possible, both source 1 and source 2 are closed to the ou… |
1.3.6.1.4.1.318.1.1.17.3.2.7 | xATSSwitchSettingsMaxSyncTime | 1 | 1 | When attempting/seeking to perform a closed transfer, this setting defines the maximum time allowed before the transfer switch w… |
1.3.6.1.4.1.318.1.1.17.3.2.8 | xATSSwitchSettingsNeutralTransferTime | 1 | 1 | This setting defines how long both source 1 and source 2 will be disconnected from the output, during an open transfer. Specified… |
1.3.6.1.4.1.318.1.1.17.3.2.9 | xATSSwitchSettingsClearLatchedAlarms | 1 | 1 | Clears any latched alarm conditions. |
1.3.6.1.4.1.318.1.1.17.3.2.10 | xATSSwitchSettingsSetToFactoryDefaults | 1 | 1 | Sets all transfer switch settings to factory default values. |