Reference record for OID 1.3.6.1.2.1.33.1.8.4

Parent
1.3.6.1.2.1.33.1.8 (upsControl)
Node code
4
Node name
upsRebootWithDuration
Numeric OID
1.3.6.1.2.1.33.1.8.4
URN notation
urn:oid:1.3.6.1.2.1.33.1.8.4
Type
OBJECT-TYPE
ASN.1 notation

{1 3 6 1 2 1 33 1 8 4}

  • {iso(1) identified-organization(3) dod(6) internet(1) mgmt(2) mib-2(1) upsMIB(33) upsObjects(1) upsControl(8) upsRebootWithDuration(4)}
  • {iso(1) identified-organization(3) dod(6) internet(1) mgmt(2) mib(1) upsMIB(33) upsObjects(1) upsControl(8) upsRebootWithDuration(4)}
  • {iso(1) identified-organization(3) dod(6) internet(1) mgmt(2) stdmib-2(1) upsMIB(33) upsObjects(1) upsControl(8) upsRebootWithDuration(4)}
  • {iso(1) org(3) dod(6) internet(1) mgmt(2) mib-2(1) upsMIB(33) upsObjects(1) upsControl(8) upsRebootWithDuration(4)}
  • {iso(1) org(3) dod(6) internet(1) mgmt(2) mib(1) upsMIB(33) upsObjects(1) upsControl(8) upsRebootWithDuration(4)}
  • {iso(1) org(3) dod(6) internet(1) mgmt(2) stdmib-2(1) upsMIB(33) upsObjects(1) upsControl(8) upsRebootWithDuration(4)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) mgmt(2) mib-2(1) upsMIB(33) upsObjects(1) upsControl(8) upsRebootWithDuration(4)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) mgmt(2) mib(1) upsMIB(33) upsObjects(1) upsControl(8) upsRebootWithDuration(4)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) mgmt(2) stdmib-2(1) upsMIB(33) upsObjects(1) upsControl(8) upsRebootWithDuration(4)}
  • {iso(1) iso-organization(3) dod(6) internet(1) mgmt(2) mib-2(1) upsMIB(33) upsObjects(1) upsControl(8) upsRebootWithDuration(4)}
  • {iso(1) iso-organization(3) dod(6) internet(1) mgmt(2) mib(1) upsMIB(33) upsObjects(1) upsControl(8) upsRebootWithDuration(4)}
  • {iso(1) iso-organization(3) dod(6) internet(1) mgmt(2) stdmib-2(1) upsMIB(33) upsObjects(1) upsControl(8) upsRebootWithDuration(4)}
OID-IRI notation
  • /1/3/6/1/2/1/33/1/8/4
  • /ISO/Identified-Organization/6/1/2/1/33/1/8/4
  • /ISO/3/6/1/2/1/33/1/8/4
Named path variants
  • /iso/identified-organization/dod/internet/mgmt/mib-2/upsMIB/upsObjects/upsControl/upsRebootWithDuration
  • /iso/identified-organization/dod/internet/mgmt/mib/upsMIB/upsObjects/upsControl/upsRebootWithDuration
  • /iso/identified-organization/dod/internet/mgmt/RFC1066-MIB-INTERPRETATION/upsMIB/upsObjects/upsControl/upsRebootWithDuration
  • /iso/identified-organization/dod/internet/mgmt/stdmib-2/upsMIB/upsObjects/upsControl/upsRebootWithDuration
  • /iso/org/dod/internet/mgmt/mib-2/upsMIB/upsObjects/upsControl/upsRebootWithDuration
  • /iso/org/dod/internet/mgmt/mib/upsMIB/upsObjects/upsControl/upsRebootWithDuration
  • /iso/org/dod/internet/mgmt/RFC1066-MIB-INTERPRETATION/upsMIB/upsObjects/upsControl/upsRebootWithDuration
  • /iso/org/dod/internet/mgmt/stdmib-2/upsMIB/upsObjects/upsControl/upsRebootWithDuration
  • /iso/iso-identified-organization/dod/internet/mgmt/mib-2/upsMIB/upsObjects/upsControl/upsRebootWithDuration
  • /iso/iso-identified-organization/dod/internet/mgmt/mib/upsMIB/upsObjects/upsControl/upsRebootWithDuration
  • /iso/iso-identified-organization/dod/internet/mgmt/RFC1066-MIB-INTERPRETATION/upsMIB/upsObjects/upsControl/upsRebootWithDuration
  • /iso/iso-identified-organization/dod/internet/mgmt/stdmib-2/upsMIB/upsObjects/upsControl/upsRebootWithDuration
  • /iso/iso-organization/dod/internet/mgmt/mib-2/upsMIB/upsObjects/upsControl/upsRebootWithDuration
  • /iso/iso-organization/dod/internet/mgmt/mib/upsMIB/upsObjects/upsControl/upsRebootWithDuration
  • /iso/iso-organization/dod/internet/mgmt/RFC1066-MIB-INTERPRETATION/upsMIB/upsObjects/upsControl/upsRebootWithDuration
  • /iso/iso-organization/dod/internet/mgmt/stdmib-2/upsMIB/upsObjects/upsControl/upsRebootWithDuration

Descriptions

Descriptions may differ between sources. The primary description is shown first.

Primary description: OID Repository

upsRebootWithDuration OBJECT-TYPE
SYNTAX INTEGER (-1..300)
UNITS "seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Setting this object will immediately shutdown (i.e.,
turn off) either the UPS output or the UPS system (as
determined by the value of upsShutdownType at the time
of shutdown) for a period equal to the indicated
number of seconds, after which time the output will be
started, including starting the UPS, if necessary. If
the number of seconds required to perform the request
is greater than the requested duration, then the
requested shutdown and startup cycle shall be
performed in the minimum time possible, but in no case
shall this require more than the requested duration
plus 60 seconds. When read, upsRebootWithDuration
shall return the number of seconds remaining in the
countdown, or -1 if no countdown is in progress. If
the startup should occur during a utility failure, the
startup shall not occur until the utility power is
restored."

View at oid-base.com
Automatically extracted from RFC1628

Alternative description: Circitor

Setting this object will immediately shutdown (i.e.,
turn off) either the UPS output or the UPS system (as
determined by the value of upsShutdownType at the time
of shutdown) for a period equal to the indicated
number of seconds, after which time the output will be
started, including starting the UPS, if necessary. If
the number of seconds required to perform the request
is greater than the requested duration, then the
requested shutdown and startup cycle shall be
performed in the minimum time possible, but in no case
shall this require more than the requested duration
plus 60 seconds. When read, upsRebootWithDuration
shall return the number of seconds remaining in the
countdown, or -1 if no countdown is in progress. If
the startup should occur during a utility failure, the
startup shall not occur until the utility power is
restored.

Parsed from file UPS-MIB.mib
Module: UPS-MIB

Source file: Download UPS-MIB.txt · Publisher's file

Copy from Netdisco; File: rfc/UPS-MIB.txt; 64,945 bytes

Vendor MIB copy from the Netdisco archive.

Related source files and packages:

Source file: Download UPS-MIB · Publisher's file

Copy from LibreNMS; 64,979 bytes

Vendor MIB copy from the LibreNMS archive.

Related source files and packages:

Source file: Download UPS-MIB · Publisher's file

Copy from Observium Community; File: liebert/UPS-MIB; 70,133 bytes

Vendor MIB copy from the Observium Community archive.

Related source files and packages:

Source file: Download UPS-MIB · Publisher's file

Copy from Observium Community; File: rfc/UPS-MIB; 64,979 bytes

Vendor MIB copy from the Observium Community archive.

Related source files and packages:

Source file: Download RFC 1628 · Publisher's file · RFC errata

File: rfc/rfc1628.txt; 83,439 bytes

Related source files and packages:

Source data warning: Published IMPORTS omits mib-2. A reviewed lookup uses its explicit namespace in RFC 1155 and RFC 1213. Published imports, OID numbers and original definitions are preserved; both supporting originals are available below.

Source file: Download UPS-MIB.mib

Publisher path: Mibs; 72,012 bytes

Source file: Download RFC1628_UPS_MIB.MIB.txt

File: liebert/RFC1628_UPS_MIB.MIB.txt; 72,054 bytes

Alternative description: MIBdepot

Setting this object will immediately shutdown (i.e.,
turn off) either the UPS output or the UPS system (as
determined by the value of upsShutdownType at the time
of shutdown) for a period equal to the indicated
number of seconds, after which time the output will be
started, including starting the UPS, if necessary. If
the number of seconds required to perform the request
is greater than the requested duration, then the
requested shutdown and startup cycle shall be
performed in the minimum time possible, but in no case
shall this require more than the requested duration
plus 60 seconds. When read, upsRebootWithDuration
shall return the number of seconds remaining in the
countdown, or -1 if no countdown is in progress. If
the startup should occur during a utility failure, the
startup shall not occur until the utility power is
restored.

Source file: Download upsmibv1.1.mib.txt

File: ge/upsmibv1.1.mib.txt; 42,827 bytes

Related source files and packages:

Source data warning: This historical publication omits an explicitly reviewed standard root import. Exact original declarations and all numeric values are retained; the referenced RFC and IANA allocation establish only the missing standard namespace.

Source file: Download best.mib.txt

File: cai/best.mib.txt; 48,527 bytes

Information from MIBdepot

upsRebootWithDuration OBJECT-TYPE
    SYNTAX  INTEGER	

    ACCESS  read-write
    STATUS  mandatory
    DESCRIPTION
           "Setting this object will immediately shutdown (i.e.,
               turn off) either the UPS output or the UPS system (as
               determined by the value of upsShutdownType at the time
               of shutdown) for a period equal to the indicated
               number of seconds, after which time the output will be
               started, including starting the UPS, if necessary.  If
               the number of seconds required to perform the request
               is greater than the requested duration, then the
               requested shutdown and startup cycle shall be
               performed in the minimum time possible, but in no case
               shall this require more than the requested duration
               plus 60 seconds.  When read, upsRebootWithDuration
               shall return the number of seconds remaining in the
               countdown, or -1 if no countdown is in progress.  If
               the startup should occur during a utility failure, the
               startup shall not occur until the utility power is
               restored."
    ::= { upsControl  4 }

Information from Circitor

upsRebootWithDuration OBJECT-TYPE
       SYNTAX     INTEGER (-1..300)
       UNITS      "seconds"
       MAX-ACCESS read-write
       STATUS     current
       DESCRIPTION
               "Setting this object will immediately shutdown (i.e.,
               turn off) either the UPS output or the UPS system (as
               determined by the value of upsShutdownType at the time
               of shutdown) for a period equal to the indicated
               number of seconds, after which time the output will be
               started, including starting the UPS, if necessary.  If
               the number of seconds required to perform the request
               is greater than the requested duration, then the
               requested shutdown and startup cycle shall be
               performed in the minimum time possible, but in no case
               shall this require more than the requested duration
               plus 60 seconds.  When read, upsRebootWithDuration
               shall return the number of seconds remaining in the
               countdown, or -1 if no countdown is in progress.  If
               the startup should occur during a utility failure, the
               startup shall not occur until the utility power is
               restored."
       ::= { upsControl 4 }

First Registration Authority (inferred from ancestor 1.3.6)

Defense Communication Agency

Current Registration Authority (inferred from ancestor 1.3.6.1.2)

Internet Assigned Numbers Authority

Direct children (1)

OIDNameDirect childrenDescendantsDescription
1.3.6.1.2.1.33.1.8.4.0 upsRebootWithDuration00

Siblings (4)

OIDNameDirect childrenDescendantsDescription
1.3.6.1.2.1.33.1.8.1 upsShutdownType11 upsShutdownType OBJECT-TYPE
SYNTAX INTEGER {
output(1),
system(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This obje…
1.3.6.1.2.1.33.1.8.2 upsShutdownAfterDelay11 upsShutdownAfterDelay OBJECT-TYPE
SYNTAX INTEGER (-1..2147483648)
UNITS "seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPT…
1.3.6.1.2.1.33.1.8.3 upsStartupAfterDelay11 upsStartupAfterDelay OBJECT-TYPE
SYNTAX INTEGER (-1..2147483648)
UNITS "seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPTI…
1.3.6.1.2.1.33.1.8.5 upsAutoRestart11 upsAutoRestart OBJECT-TYPE
SYNTAX INTEGER {
on(1),
off(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Setting this obje…