upsBasicCompliance MODULE-COMPLIANCE
STATUS current
DESCRIPTION
"The compliance statement for UPSs that support
full-featured functions, such as control."
MODULE -- this module
MANDATORY-GROUPS { upsBasicIdentGroup,
upsBasicBatteryGroup, upsBasicInputGroup,
upsBasicOutputGroup, upsBasicAlarmGroup,
upsBasicTestGroup, upsBasicControlGroup,
upsBasicConfigGroup }
OBJECT upsAlarmDescr
DESCRIPTION
"Support of all `well known alarm types is not
required. The well known alarm types which must be
supported are: upsAlarmOnBattery, upsAlarmLowBattery,
upsAlarmDepletedBattery, upsAlarmTempBad,
upsAlarmInputBad, upsAlarmOutputOverload,
upsAlarmOnBypass, upsAlarmBypassBad,
upsAlarmOutputOffAsRequested,
upsAlarmUpsOffAsRequested, upsAlarmUpsOutputOff,
upsAlarmUpsSystemOff, upsAlarmGeneralFault,
upsAlarmDiagnosticTestFailed,
upsAlarmCommunicationsLost, upsAlarmShutdownPending,
and upsAlarmTestInProgress."
OBJECT upsTestId
DESCRIPTION
"Support of all `well known test types is not
required. If no tests are supported, then the only
well known test type which must be supported is
upsTestNoTestsInitiated."
OBJECT upsOutputSource
SYNTAX INTEGER {
normal(2),
battery(4)
}
DESCRIPTION
"Support of the values other(1), none(2), bypass(4),
booster(6) and reducer(7) is not required."
GROUP upsBasicBypassGroup
DESCRIPTION
"The upsBasicBypassGroup is only required for UPSs
that have a Bypass present."
OBJECT upsShutdownType
MIN-ACCESS read-only
DESCRIPTION
"Read-write access is not required, i.e., compliant
systems need not support more than one shutdown type."
OBJECT upsAutoRestart
MIN-ACCESS read-only
DESCRIPTION
"Read-write access is not required, i.e., compliant
systems need not support more than one restart type."
OBJECT upsConfigInputVoltage
MIN-ACCESS read-only
DESCRIPTION
"Read-write access is not required."
OBJECT upsConfigInputFreq
MIN-ACCESS read-only
DESCRIPTION
"Read-write access is not required."
OBJECT upsConfigOutputVoltage
MIN-ACCESS read-only
DESCRIPTION
"Read-write access is not required."
OBJECT upsConfigOutputFreq
MIN-ACCESS read-only
DESCRIPTION
"Read-write access is not required."
OBJECT upsConfigLowBattTime
DESCRIPTION
"Implementation of all possible values may be onerous
for some systems. Consequently, not all possible
values must be supported. However, at least two
different manufacturer-selected values must be
supported."
View at oid-info.com
The compliance statement for UPSs that support
full-featured functions, such as control.
Parsed from file UPS-MIB.mib
Module: UPS-MIB
Automatically extracted from RFC1628
upsBasicCompliance OBJECT IDENTIFIER ::= { upsCompliances 2 }
upsBasicCompliance MODULE-COMPLIANCE STATUS current DESCRIPTION "The compliance statement for UPSs that support full-featured functions, such as control." MODULE MANDATORY-GROUPS { upsBasicIdentGroup, upsBasicBatteryGroup, upsBasicInputGroup, upsBasicOutputGroup, upsBasicAlarmGroup, upsBasicTestGroup, upsBasicControlGroup, upsBasicConfigGroup } OBJECT upsAlarmDescr DESCRIPTION "Support of all `well known' alarm types is not required. The well known alarm types which must be supported are: upsAlarmOnBattery, upsAlarmLowBattery, upsAlarmDepletedBattery, upsAlarmTempBad, upsAlarmInputBad, upsAlarmOutputOverload, upsAlarmOnBypass, upsAlarmBypassBad, upsAlarmOutputOffAsRequested, upsAlarmUpsOffAsRequested, upsAlarmUpsOutputOff, upsAlarmUpsSystemOff, upsAlarmGeneralFault, upsAlarmDiagnosticTestFailed, upsAlarmCommunicationsLost, upsAlarmShutdownPending, and upsAlarmTestInProgress." OBJECT upsTestId DESCRIPTION "Support of all `well known' test types is not required. If no tests are supported, then the only well known test type which must be supported is upsTestNoTestsInitiated." OBJECT upsOutputSource SYNTAX INTEGER { normal(2), battery(4) } DESCRIPTION "Support of the values other(1), none(2), bypass(4), booster(6) and reducer(7) is not required." GROUP upsBasicBypassGroup DESCRIPTION "The upsBasicBypassGroup is only required for UPSs that have a Bypass present." OBJECT upsShutdownType MIN-ACCESS read-only DESCRIPTION "Read-write access is not required, i.e., compliant systems need not support more than one shutdown type." OBJECT upsAutoRestart MIN-ACCESS read-only DESCRIPTION "Read-write access is not required, i.e., compliant systems need not support more than one restart type." OBJECT upsConfigInputVoltage MIN-ACCESS read-only DESCRIPTION "Read-write access is not required." OBJECT upsConfigInputFreq MIN-ACCESS read-only DESCRIPTION "Read-write access is not required." OBJECT upsConfigOutputVoltage MIN-ACCESS read-only DESCRIPTION "Read-write access is not required." OBJECT upsConfigOutputFreq MIN-ACCESS read-only DESCRIPTION "Read-write access is not required." OBJECT upsConfigLowBattTime DESCRIPTION "Implementation of all possible values may be onerous for some systems. Consequently, not all possible values must be supported. However, at least two different manufacturer-selected values must be supported." ::= { upsCompliances 2 }