splitTime · mandatory
splitTime OBJECT-TYPE
SYNTAX INTEGER (0..255)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The time in seconds the splitPhase is allowed to receive (i.e. before a Force Off is applied)
when constant demands exist on all phases. In floating coordForceMode, this is always the
maximum time a non-coordinated phase is allowed to receive. In fixed coordForceMode, the
actual allowed time may be longer if a previous phase gapped out.
The splitTime includes all phase clearance times for the associated phase. The split time
shall be longer than the sum of the phase minimum service requirements (Minimum Green,
Yellow Change, Red Clearance, Walk, Pedestrian Clearance, etc.) for the phase. When the
time is NOT adequate to service the minimum service requirements of the phase, Free
Mode shall be the result.
If the cycleTime entry of the associated patternTable entry is zero (i.e. the device is in Free
Mode), then the value of this object shall be applied as a maximum time for the associated
phase.
If the critical path through the phase diagram is less than the cycleTime entry of the
associated patternTable entry, all extra time is allotted to the coordination phase in each
ring.
If the critical path through the phase diagram is greater than the cycleTime entry of the
associated patternTable entry (and the cycleTime is not zero) the device shall operate in the
Free Mode.
TS 3.5-1996
While the Free Mode condition exists, the Local Override bit of shortAlarm shall be set to
one (1)."
REFERENCE
"NEMA TS 2 Clause 3.6.2.1.2"
::= { splitEntry 3 }splitTime · mandatory
splitTime OBJECT-TYPE
SYNTAX INTEGER (0..255)
ACCESS read-write
STATUS mandatory
DESCRIPTION "<Definition> The time in seconds the splitPhase is allowed
to receive (i.e. before a Force Off is applied) when constant
demands exist on all phases. In floating coordForceMode, this is
always the maximum time a non-coordinated phase is allowed to
receive. In fixed coordForceMode, the actual allowed time may be
longer if a previous phase gapped out.
The splitTime includes all phase clearance times for the
associated phase. The split time shall be longer than the sum of
the phase minimum service requirements for the phase. When the
time is NOT adequate to service the minimum service requirements
of the phase, Free Mode shall be the result. The minimum
requirements of a phase with a not-actuated ped include Minimum
Green, Walk, Pedestrian Clear, Yellow Clearance, and Red
Clearance; the minimum requirements of a phase with an actuated
pedestrian include Minimum Green, Yellow Clearance, and Red
Clearance.
If the cycleTime entry of the associated patternTable entry is
zero (i.e. the device is in Free Mode), then the value of this
object shall be applied, if non-zero, as a maximum time for the
associated phase.
If the critical path through the phase diagram is less than the
cycleTime entry of the associated patternTable entry, all extra
time is allotted to the coordination phase in each ring.
If the critical path through the phase diagram is greater than
the cycleTime entry of the associated patternTable entry (and the
cycleTime is not zero) the device shall operate in the Free Mode.
While the Free Mode condition exists, the Local Override bit of
shortAlarm shall be set to one (1).
<Object Identifier> 1.3.6.1.4.1.1206.4.2.1.4.9.1.3
<Unit> second"
REFERENCE "NEMA TS 2 Clause 3.6.2.1.2"
::= { splitEntry 3 }splitTime · optional
splitTime OBJECT-TYPE
SYNTAX INTEGER (0..255)
ACCESS read-write
STATUS optional
DESCRIPTION
"<Definition> The time in seconds the splitPhase is
allowed to receive (i.e. before a Force Off is
applied) when constant demands exist on all phases.
In floating coordForceMode, this is always the
maximum time a non-coordinated phase is allowed to
receive. In fixed coordForceMode, the actual allowed
time may be longer if a previous phase gapped out.
The splitTime includes all phase clearance times for
the associated phase. The split time shall be longer
than the sum of the phase minimum service
requirements for the phase. When the time is NOT
adequate to service the minimum service requirements
of the phase, Free Mode shall be the result. The
minimum requirements of a phase with a not-actuated
ped include Minimum Green, Walk, Pedestrian Clear,
Yellow Clearance, and Red Clearance; the minimum
requirements of a phase with an actuated pedestrian
include Minimum Green, Yellow Clearance, and Red
Clearance.
If the cycleTime entry of the associated
patternTable entry is zero (i.e. the device is in
Free Mode), then the value of this object shall be
applied, if non-zero, as a maximum time for the
associated phase.
If the critical path through the phase diagram is
less than the cycleTime entry of the associated
patternTable entry, all extra time is alloted to the
coordination phase in each ring.
If the critical path through the phase diagram is
greater than the cycleTime entry of the associated
patternTable entry (and the cycleTime is not zero)
the device shall operate in the Free Mode.
While the Free Mode condition exists, the Local
Override bit of shortAlarm shall be set to one (1).
<DescriptiveName> NTCIP-1202::ASC.splitTime
<DataConceptType> Data Element
<Unit> second"
REFERENCE
"NEMA TS 2 Clause 3.6.2.1.2"
::= { splitEntry 3 }splitTime · mandatory
splitTime OBJECT-TYPE
SYNTAX INTEGER (0..255)
ACCESS read-write
STATUS mandatory
DESCRIPTION "<Definition> The time in seconds the splitPhase is allowed
to receive (i.e. before a Force Off is applied) when constant
demands exist on all phases. In floating coordForceMode, this is
always the maximum time a non-coordinated phase is allowed to
receive. In fixed coordForceMode, the actual allowed time may be
longer if a previous phase gapped out.
The splitTime includes all phase clearance times for the
associated phase. The split time shall be longer than the sum of
the phase minimum service requirements for the phase. When the
time is NOT adequate to service the minimum service requirements
of the phase, Free Mode shall be the result. The minimum
requirements of a phase with a not-actuated ped include Minimum
Green, Walk, Pedestrian Clear, Yellow Clearance, and Red
Clearance; the minimum requirements of a phase with an actuated
pedestrian include Minimum Green, Yellow Clearance, and Red
Clearance.
If the cycleTime entry of the associated patternTable entry is
zero (i.e. the device is in Free Mode), then the value of this
object shall be applied, if non-zero, as a maximum time for the
associated phase.
If the critical path through the phase diagram is less than the
cycleTime entry of the associated patternTable entry, all extra
time is allotted to the coordination phase in each ring.
If the critical path through the phase diagram is greater than
the cycleTime entry of the associated patternTable entry (and the
cycleTime is not zero) the device shall operate in the Free Mode.
While the Free Mode condition exists, the Local Override bit of
shortAlarm shall be set to one (1).
<Object Identifier> 1.3.6.1.4.1.1206.4.2.1.4.9.1.3
<Object Type> P
<Unit> second"
REFERENCE "NEMA TS 2 Clause 3.6.2.1.2"
::= { splitEntry 3 }