Status in source: current.
Technical details
{
"smi_kind": "NOTIFICATION-TYPE",
"definition": [
"overCurrentProtectorSensorStateChange",
"NOTIFICATION-TYPE",
"OBJECTS",
"{",
"pduName",
",",
"pduNumber",
",",
"pxInetAddressType",
",",
"pxInetIPAddress",
",",
"agentInetPortNumber",
",",
"overCurrentProtectorLabel",
",",
"typeOfSensor",
",",
"measurementsOverCurrentProtectorSensorTimeStamp",
",",
"measurementsOverCurrentProtectorSensorValue",
",",
"measurementsOverCurrentProtectorSensorState",
",",
"measurementsOverCurrentProtectorSensorSignedValue",
",",
"oldSensorState",
",",
"sysContact",
",",
"sysName",
",",
"sysLocation",
",",
"pduSerialNumber",
",",
"suspectedTripCauseLabel",
"}",
"STATUS",
"current",
"DESCRIPTION",
"\"Overcurrent protector sensor state change. Which value field to use depends on the metadata of the sensor. measurementsOverCurrentProtectorSensorValue is undefined for sensors which can have negative readings, measurementsOverCurrentProtectorSensorSignedValue is undefined for sensors whose range exceeds the Integer32 range. Both fields do not apply to sensors without numerical readings. For trip sensor state changes, if a particular outlet is determined to be likely to have caused the OCP trip, its label is passed in suspectedTripCauseLabel. For an rcmState sensor transitioning to the fail state, the value is the residual current just before the sensor transitioned to the fail state.\"",
"::=",
"{",
"traps",
"65",
"}"
],
"syntax_tree": [
[
"Objects",
[
"pduName",
"pduNumber",
"pxInetAddressType",
"pxInetIPAddress",
"agentInetPortNumber",
"overCurrentProtectorLabel",
"typeOfSensor",
"measurementsOverCurrentProtectorSensorTimeStamp",
"measurementsOverCurrentProtectorSensorValue",
"measurementsOverCurrentProtectorSensorState",
"measurementsOverCurrentProtectorSensorSignedValue",
"oldSensorState",
"sysContact",
"sysName",
"sysLocation",
"pduSerialNumber",
"suspectedTripCauseLabel"
]
],
[
"Status",
"current"
],
[
"DESCRIPTION",
"Overcurrent protector sensor state change. Which value field to use depends on the metadata of the sensor. measurementsOverCurrentProtectorSensorValue is undefined for sensors which can have negative readings, measurementsOverCurrentProtectorSensorSignedValue is undefined for sensors whose range exceeds the Integer32 range. Both fields do not apply to sensors without numerical readings. For trip sensor state changes, if a particular outlet is determined to be likely to have caused the OCP trip, its label is passed in suspectedTripCauseLabel. For an rcmState sensor transitioning to the fail state, the value is the residual current just before the sensor transitioned to the fail state."
],
null
]
}