upsSmartConfigLowTransferVolt

1.3.6.1.4.1.17420.1.1.2.5.2.3

Description

The minimum line voltage in 1/10 VAC allowed before the UPS system transfers to battery backup. Allowable values depend on the UPS used: 120 Volt units allow settings of 970, 1000, 1030, 1060. 100 Volt units allow settings of 810, 830, 850, 870. 230 Volt units allow settings of 1880, 1960, 2040, 2080. 208 Volt units a…

Full description and source information

Identification

Identifier and names

Parent
1.3.6.1.4.1.17420.1.1.2.5.2 (upsSmartConfig)
Node code
3
Node name
upsSmartConfigLowTransferVolt
Category
SNMP management object
Numeric OID
1.3.6.1.4.1.17420.1.1.2.5.2.3
URN notation
urn:oid:1.3.6.1.4.1.17420.1.1.2.5.2.3
ASN.1, OID-IRI and named path variants
ASN.1 notation

{1 3 6 1 4 1 17420 1 1 2 5 2 3}

  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) digipower(17420) products(1) hardware(1) ups(2) upsConfigp(5) upsSmartConfig(2) upsSmartConfigLowTransferVolt(3)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) dgp(17420) products(1) hardware(1) ups(2) upsConfigp(5) upsSmartConfig(2) upsSmartConfigLowTransferVolt(3)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) digipower(17420) products(1) hardware(1) ups(2) upsConfigp(5) upsSmartConfig(2) upsSmartConfigLowTransferVolt(3)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) dgp(17420) products(1) hardware(1) ups(2) upsConfigp(5) upsSmartConfig(2) upsSmartConfigLowTransferVolt(3)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) digipower(17420) products(1) hardware(1) ups(2) upsConfigp(5) upsSmartConfig(2) upsSmartConfigLowTransferVolt(3)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) dgp(17420) products(1) hardware(1) ups(2) upsConfigp(5) upsSmartConfig(2) upsSmartConfigLowTransferVolt(3)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) vendor-objects(1) digipower(17420) products(1) hardware(1) ups(2) upsConfigp(5) upsSmartConfig(2) upsSmartConfigLowTransferVolt(3)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) vendor-objects(1) dgp(17420) products(1) hardware(1) ups(2) upsConfigp(5) upsSmartConfig(2) upsSmartConfigLowTransferVolt(3)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprise(1) digipower(17420) products(1) hardware(1) ups(2) upsConfigp(5) upsSmartConfig(2) upsSmartConfigLowTransferVolt(3)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprise(1) dgp(17420) products(1) hardware(1) ups(2) upsConfigp(5) upsSmartConfig(2) upsSmartConfigLowTransferVolt(3)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) digipower(17420) products(1) hardware(1) ups(2) upsConfigp(5) upsSmartConfig(2) upsSmartConfigLowTransferVolt(3)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) dgp(17420) products(1) hardware(1) ups(2) upsConfigp(5) upsSmartConfig(2) upsSmartConfigLowTransferVolt(3)}
  • {iso(1) org(3) dod(6) internet(1) private(4) ldap-enterprise(1) digipower(17420) products(1) hardware(1) ups(2) upsConfigp(5) upsSmartConfig(2) upsSmartConfigLowTransferVolt(3)}
  • {iso(1) org(3) dod(6) internet(1) private(4) ldap-enterprise(1) dgp(17420) products(1) hardware(1) ups(2) upsConfigp(5) upsSmartConfig(2) upsSmartConfigLowTransferVolt(3)}
  • {iso(1) org(3) dod(6) internet(1) private(4) vendor-objects(1) digipower(17420) products(1) hardware(1) ups(2) upsConfigp(5) upsSmartConfig(2) upsSmartConfigLowTransferVolt(3)}
  • {iso(1) org(3) dod(6) internet(1) private(4) vendor-objects(1) dgp(17420) products(1) hardware(1) ups(2) upsConfigp(5) upsSmartConfig(2) upsSmartConfigLowTransferVolt(3)}
  • Additional combinations skipped.
OID-IRI notation
  • /1/3/6/1/4/1/17420/1/1/2/5/2/3
  • /ISO/Identified-Organization/6/1/4/1/17420/1/1/2/5/2/3
  • /ISO/3/6/1/4/1/17420/1/1/2/5/2/3
Named path variants
  • /iso/identified-organization/dod/internet/private/enterprise/17420/products/hardware/ups/upsConfigp/upsSmartConfig/upsSmartConfigLowTransferVolt
  • /iso/identified-organization/dod/internet/private/enterprise/digipower/products/hardware/ups/upsConfigp/upsSmartConfig/upsSmartConfigLowTransferVolt
  • /iso/identified-organization/dod/internet/private/enterprise/dgp/products/hardware/ups/upsConfigp/upsSmartConfig/upsSmartConfigLowTransferVolt
  • /iso/identified-organization/dod/internet/private/enterprises/17420/products/hardware/ups/upsConfigp/upsSmartConfig/upsSmartConfigLowTransferVolt
  • /iso/identified-organization/dod/internet/private/enterprises/digipower/products/hardware/ups/upsConfigp/upsSmartConfig/upsSmartConfigLowTransferVolt
  • /iso/identified-organization/dod/internet/private/enterprises/dgp/products/hardware/ups/upsConfigp/upsSmartConfig/upsSmartConfigLowTransferVolt
  • /iso/identified-organization/dod/internet/private/ldap-enterprise/17420/products/hardware/ups/upsConfigp/upsSmartConfig/upsSmartConfigLowTransferVolt
  • /iso/identified-organization/dod/internet/private/ldap-enterprise/digipower/products/hardware/ups/upsConfigp/upsSmartConfig/upsSmartConfigLowTransferVolt
  • /iso/identified-organization/dod/internet/private/ldap-enterprise/dgp/products/hardware/ups/upsConfigp/upsSmartConfig/upsSmartConfigLowTransferVolt
  • /iso/identified-organization/dod/internet/private/vendor-objects/17420/products/hardware/ups/upsConfigp/upsSmartConfig/upsSmartConfigLowTransferVolt
  • /iso/identified-organization/dod/internet/private/vendor-objects/digipower/products/hardware/ups/upsConfigp/upsSmartConfig/upsSmartConfigLowTransferVolt
  • /iso/identified-organization/dod/internet/private/vendor-objects/dgp/products/hardware/ups/upsConfigp/upsSmartConfig/upsSmartConfigLowTransferVolt
  • /iso/org/dod/internet/private/enterprise/17420/products/hardware/ups/upsConfigp/upsSmartConfig/upsSmartConfigLowTransferVolt
  • /iso/org/dod/internet/private/enterprise/digipower/products/hardware/ups/upsConfigp/upsSmartConfig/upsSmartConfigLowTransferVolt
  • /iso/org/dod/internet/private/enterprise/dgp/products/hardware/ups/upsConfigp/upsSmartConfig/upsSmartConfigLowTransferVolt
  • /iso/org/dod/internet/private/enterprises/17420/products/hardware/ups/upsConfigp/upsSmartConfig/upsSmartConfigLowTransferVolt
  • Additional combinations skipped.

SNMP properties

Value type
INTEGER
Maximum access defined by MIB
read-write
Status in MIB
mandatory

Using this OID with SNMP

At least one MIB declaration places this object in a scalar group. A scalar instance uses the suffix .0.

snmpget [connection options] DEVICE .1.3.6.1.4.1.17420.1.1.2.5.2.3.0

Replace the placeholders with your connection and authentication options. Available permissions and device support can differ from the MIB.

Properties come from available MIB definitions. Actual device support and access can differ. See source records below for original files and qualifications.

The displayed source records contain one distinct definition. Compare its source records.

upsSmartConfigLowTransferVolt OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-write
	STATUS mandatory
	DESCRIPTION
		"The minimum line voltage in 1/10 VAC allowed before the
		UPS system transfers to battery backup.
		                
		Allowable values depend on the UPS used:
		120 Volt units allow settings of  970, 1000, 1030, 1060.
		100 Volt units allow settings of 810, 830, 850, 870.
		230 Volt units allow settings of 1880, 1960, 2040, 2080.
		208 Volt units allow settings of 1680, 1720, 1770, 1820.
		                
		If a value other than a supported value is provided in a
		set request, the UPS interprets it as a the next higher
		acceptable value.  If the provided value is higher than
		the highest acceptable value, the highest acceptable
		value is used."
   ::= { upsSmartConfig 3 }

Meaning

Descriptions

1 unique

Identical descriptions are grouped. Different wording and device-specific notes are retained.

The minimum line voltage in 1/10 VAC allowed before the UPS system transfers to battery backup. Allowable values depend on the UPS used: 120 Volt units allow settings of 970, 1000, 1030, 1060. 100 Volt units allow settings of 810, 830, 850, 870. 230 Volt units allow settings of 1880, 1960, 2040, 2080. 208 Volt units allow settings of 1680, 1720, 1770, 1820. If a value other than a supported value is provided in a set request, the UPS interprets it as a the next higher acceptable value. If the provided value is higher than the highest acceptable value, the highest acceptable value is used.

Sources for this description

Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)

See 1 matching source record

Evidence

Source records

1 records

Matching descriptions are grouped; open a group to compare definitions and supporting files.

Records for description 1Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)1 record · 1 source

Description 1

upsSmartConfigLowTransferVolt · mandatoryMultiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)1 source

Status in source: mandatory.

Names: upsSmartConfigLowTransferVolt

Technical details
{
  "smi_kind": "OBJECT-TYPE",
  "definition": [
    "upsSmartConfigLowTransferVolt",
    "OBJECT-TYPE",
    "SYNTAX",
    "INTEGER",
    "ACCESS",
    "read-write",
    "STATUS",
    "mandatory",
    "DESCRIPTION",
    "\"The minimum line voltage in 1/10 VAC allowed before the UPS system transfers to battery backup. Allowable values depend on the UPS used: 120 Volt units allow settings of 970, 1000, 1030, 1060. 100 Volt units allow settings of 810, 830, 850, 870. 230 Volt units allow settings of 1880, 1960, 2040, 2080. 208 Volt units allow settings of 1680, 1720, 1770, 1820. If a value other than a supported value is provided in a set request, the UPS interprets it as a the next higher acceptable value. If the provided value is higher than the highest acceptable value, the highest acceptable value is used.\"",
    "::=",
    "{",
    "upsSmartConfig",
    "3",
    "}"
  ],
  "syntax_tree": [
    [
      "SimpleSyntax",
      "INTEGER"
    ],
    null,
    [
      "MaxAccessPart",
      "read-write"
    ],
    [
      "Status",
      "mandatory"
    ],
    [
      "DESCRIPTION",
      "The minimum line voltage in 1/10 VAC allowed before the UPS system transfers to battery backup. Allowable values depend on the UPS used: 120 Volt units allow settings of 970, 1000, 1030, 1060. 100 Volt units allow settings of 810, 830, 850, 870. 230 Volt units allow settings of 1880, 1960, 2040, 2080. 208 Volt units allow settings of 1680, 1720, 1770, 1820. If a value other than a supported value is provided in a set request, the UPS interprets it as a the next higher acceptable value. If the provided value is higher than the highest acceptable value, the highest acceptable value is used."
    ],
    null,
    null,
    null,
    null
  ]
}

Registration

Registration authorities

First Registration Authority (inferred from ancestor 1.3.6.1.4.1.17420)

Hsieh Harvey

Siblings (11)

OIDNameDirect childrenDescendantsDescription
1.3.6.1.4.1.17420.1.1.2.5.2.1 upsSmartConfigRatedOutputVoltage00
1.3.6.1.4.1.17420.1.1.2.5.2.2 upsSmartConfigHighTransferVolt00
1.3.6.1.4.1.17420.1.1.2.5.2.4 upsSmartConfigAlarm00
1.3.6.1.4.1.17420.1.1.2.5.2.5 upsSmartConfigAlarmTimer00
1.3.6.1.4.1.17420.1.1.2.5.2.6 upsSmartConfigMinReturnCapacity00
1.3.6.1.4.1.17420.1.1.2.5.2.7 upsSmartConfigSensitivity00
1.3.6.1.4.1.17420.1.1.2.5.2.8 upsSmartConfigLowBatteryRunTime00
1.3.6.1.4.1.17420.1.1.2.5.2.9 upsSmartConfigReturnDelay00
1.3.6.1.4.1.17420.1.1.2.5.2.10 upsSmartConfigShutoffDelay00
1.3.6.1.4.1.17420.1.1.2.5.2.11 upsSmartConfigUpsSleepTime00
1.3.6.1.4.1.17420.1.1.2.5.2.12 upsSmartConfigSetEEPROMDefaults00