upsSmartConfigMinReturnCapacity

1.3.6.1.4.1.17420.1.1.2.5.2.6

Description

The minimum battery capacity as a percent of full capacity required before the UPS will return from a low battery shutdown condition. In other words, the UPS will not re-energize the output until the battery capacity is equal to this value. Allowed values are 0, 10, 25, or 90 percent. If a value other than a supported…

Full description and source information

Identification

Identifier and names

Parent
1.3.6.1.4.1.17420.1.1.2.5.2 (upsSmartConfig)
Node code
6
Node name
upsSmartConfigMinReturnCapacity
Category
SNMP management object
Numeric OID
1.3.6.1.4.1.17420.1.1.2.5.2.6
URN notation
urn:oid:1.3.6.1.4.1.17420.1.1.2.5.2.6
ASN.1, OID-IRI and named path variants
ASN.1 notation

{1 3 6 1 4 1 17420 1 1 2 5 2 6}

  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) digipower(17420) products(1) hardware(1) ups(2) upsConfigp(5) upsSmartConfig(2) upsSmartConfigMinReturnCapacity(6)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) dgp(17420) products(1) hardware(1) ups(2) upsConfigp(5) upsSmartConfig(2) upsSmartConfigMinReturnCapacity(6)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) digipower(17420) products(1) hardware(1) ups(2) upsConfigp(5) upsSmartConfig(2) upsSmartConfigMinReturnCapacity(6)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) dgp(17420) products(1) hardware(1) ups(2) upsConfigp(5) upsSmartConfig(2) upsSmartConfigMinReturnCapacity(6)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) digipower(17420) products(1) hardware(1) ups(2) upsConfigp(5) upsSmartConfig(2) upsSmartConfigMinReturnCapacity(6)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) dgp(17420) products(1) hardware(1) ups(2) upsConfigp(5) upsSmartConfig(2) upsSmartConfigMinReturnCapacity(6)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) vendor-objects(1) digipower(17420) products(1) hardware(1) ups(2) upsConfigp(5) upsSmartConfig(2) upsSmartConfigMinReturnCapacity(6)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) vendor-objects(1) dgp(17420) products(1) hardware(1) ups(2) upsConfigp(5) upsSmartConfig(2) upsSmartConfigMinReturnCapacity(6)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprise(1) digipower(17420) products(1) hardware(1) ups(2) upsConfigp(5) upsSmartConfig(2) upsSmartConfigMinReturnCapacity(6)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprise(1) dgp(17420) products(1) hardware(1) ups(2) upsConfigp(5) upsSmartConfig(2) upsSmartConfigMinReturnCapacity(6)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) digipower(17420) products(1) hardware(1) ups(2) upsConfigp(5) upsSmartConfig(2) upsSmartConfigMinReturnCapacity(6)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) dgp(17420) products(1) hardware(1) ups(2) upsConfigp(5) upsSmartConfig(2) upsSmartConfigMinReturnCapacity(6)}
  • {iso(1) org(3) dod(6) internet(1) private(4) ldap-enterprise(1) digipower(17420) products(1) hardware(1) ups(2) upsConfigp(5) upsSmartConfig(2) upsSmartConfigMinReturnCapacity(6)}
  • {iso(1) org(3) dod(6) internet(1) private(4) ldap-enterprise(1) dgp(17420) products(1) hardware(1) ups(2) upsConfigp(5) upsSmartConfig(2) upsSmartConfigMinReturnCapacity(6)}
  • {iso(1) org(3) dod(6) internet(1) private(4) vendor-objects(1) digipower(17420) products(1) hardware(1) ups(2) upsConfigp(5) upsSmartConfig(2) upsSmartConfigMinReturnCapacity(6)}
  • {iso(1) org(3) dod(6) internet(1) private(4) vendor-objects(1) dgp(17420) products(1) hardware(1) ups(2) upsConfigp(5) upsSmartConfig(2) upsSmartConfigMinReturnCapacity(6)}
  • Additional combinations skipped.
OID-IRI notation
  • /1/3/6/1/4/1/17420/1/1/2/5/2/6
  • /ISO/Identified-Organization/6/1/4/1/17420/1/1/2/5/2/6
  • /ISO/3/6/1/4/1/17420/1/1/2/5/2/6
Named path variants
  • /iso/identified-organization/dod/internet/private/enterprise/17420/products/hardware/ups/upsConfigp/upsSmartConfig/upsSmartConfigMinReturnCapacity
  • /iso/identified-organization/dod/internet/private/enterprise/digipower/products/hardware/ups/upsConfigp/upsSmartConfig/upsSmartConfigMinReturnCapacity
  • /iso/identified-organization/dod/internet/private/enterprise/dgp/products/hardware/ups/upsConfigp/upsSmartConfig/upsSmartConfigMinReturnCapacity
  • /iso/identified-organization/dod/internet/private/enterprises/17420/products/hardware/ups/upsConfigp/upsSmartConfig/upsSmartConfigMinReturnCapacity
  • /iso/identified-organization/dod/internet/private/enterprises/digipower/products/hardware/ups/upsConfigp/upsSmartConfig/upsSmartConfigMinReturnCapacity
  • /iso/identified-organization/dod/internet/private/enterprises/dgp/products/hardware/ups/upsConfigp/upsSmartConfig/upsSmartConfigMinReturnCapacity
  • /iso/identified-organization/dod/internet/private/ldap-enterprise/17420/products/hardware/ups/upsConfigp/upsSmartConfig/upsSmartConfigMinReturnCapacity
  • /iso/identified-organization/dod/internet/private/ldap-enterprise/digipower/products/hardware/ups/upsConfigp/upsSmartConfig/upsSmartConfigMinReturnCapacity
  • /iso/identified-organization/dod/internet/private/ldap-enterprise/dgp/products/hardware/ups/upsConfigp/upsSmartConfig/upsSmartConfigMinReturnCapacity
  • /iso/identified-organization/dod/internet/private/vendor-objects/17420/products/hardware/ups/upsConfigp/upsSmartConfig/upsSmartConfigMinReturnCapacity
  • /iso/identified-organization/dod/internet/private/vendor-objects/digipower/products/hardware/ups/upsConfigp/upsSmartConfig/upsSmartConfigMinReturnCapacity
  • /iso/identified-organization/dod/internet/private/vendor-objects/dgp/products/hardware/ups/upsConfigp/upsSmartConfig/upsSmartConfigMinReturnCapacity
  • /iso/org/dod/internet/private/enterprise/17420/products/hardware/ups/upsConfigp/upsSmartConfig/upsSmartConfigMinReturnCapacity
  • /iso/org/dod/internet/private/enterprise/digipower/products/hardware/ups/upsConfigp/upsSmartConfig/upsSmartConfigMinReturnCapacity
  • /iso/org/dod/internet/private/enterprise/dgp/products/hardware/ups/upsConfigp/upsSmartConfig/upsSmartConfigMinReturnCapacity
  • /iso/org/dod/internet/private/enterprises/17420/products/hardware/ups/upsConfigp/upsSmartConfig/upsSmartConfigMinReturnCapacity
  • Additional combinations skipped.

SNMP properties

Value type
INTEGER
Maximum access defined by MIB
read-write
Status in MIB
mandatory

Using this OID with SNMP

At least one MIB declaration places this object in a scalar group. A scalar instance uses the suffix .0.

snmpget [connection options] DEVICE .1.3.6.1.4.1.17420.1.1.2.5.2.6.0

Replace the placeholders with your connection and authentication options. Available permissions and device support can differ from the MIB.

Properties come from available MIB definitions. Actual device support and access can differ. See source records below for original files and qualifications.

The displayed source records contain one distinct definition. Compare its source records.

upsSmartConfigMinReturnCapacity OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-write
	STATUS mandatory
	DESCRIPTION
		"The minimum battery capacity as a percent of full capacity
		required before the UPS will return from a low battery
		shutdown condition.  In other words, the UPS will not
		re-energize the output until the battery capacity is equal
		to this value. Allowed values are 0, 10, 25, or 90  percent.
		                
		If a value other than a supported value is provided in a
		set request, the UPS interprets it as a the next higher
		acceptable value.  If the provided value is higher than
		the highest acceptable value, the highest acceptable
		value is used."
   ::= { upsSmartConfig 6 }

Meaning

Descriptions

1 unique

Identical descriptions are grouped. Different wording and device-specific notes are retained.

The minimum battery capacity as a percent of full capacity required before the UPS will return from a low battery shutdown condition. In other words, the UPS will not re-energize the output until the battery capacity is equal to this value. Allowed values are 0, 10, 25, or 90 percent. If a value other than a supported value is provided in a set request, the UPS interprets it as a the next higher acceptable value. If the provided value is higher than the highest acceptable value, the highest acceptable value is used.

Sources for this description

Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)

See 1 matching source record

Evidence

Source records

1 records

Matching descriptions are grouped; open a group to compare definitions and supporting files.

Records for description 1Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)1 record · 1 source

Description 1

upsSmartConfigMinReturnCapacity · mandatoryMultiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)1 source

Status in source: mandatory.

Names: upsSmartConfigMinReturnCapacity

Technical details
{
  "smi_kind": "OBJECT-TYPE",
  "definition": [
    "upsSmartConfigMinReturnCapacity",
    "OBJECT-TYPE",
    "SYNTAX",
    "INTEGER",
    "ACCESS",
    "read-write",
    "STATUS",
    "mandatory",
    "DESCRIPTION",
    "\"The minimum battery capacity as a percent of full capacity required before the UPS will return from a low battery shutdown condition. In other words, the UPS will not re-energize the output until the battery capacity is equal to this value. Allowed values are 0, 10, 25, or 90 percent. If a value other than a supported value is provided in a set request, the UPS interprets it as a the next higher acceptable value. If the provided value is higher than the highest acceptable value, the highest acceptable value is used.\"",
    "::=",
    "{",
    "upsSmartConfig",
    "6",
    "}"
  ],
  "syntax_tree": [
    [
      "SimpleSyntax",
      "INTEGER"
    ],
    null,
    [
      "MaxAccessPart",
      "read-write"
    ],
    [
      "Status",
      "mandatory"
    ],
    [
      "DESCRIPTION",
      "The minimum battery capacity as a percent of full capacity required before the UPS will return from a low battery shutdown condition. In other words, the UPS will not re-energize the output until the battery capacity is equal to this value. Allowed values are 0, 10, 25, or 90 percent. If a value other than a supported value is provided in a set request, the UPS interprets it as a the next higher acceptable value. If the provided value is higher than the highest acceptable value, the highest acceptable value is used."
    ],
    null,
    null,
    null,
    null
  ]
}

Registration

Registration authorities

First Registration Authority (inferred from ancestor 1.3.6.1.4.1.17420)

Hsieh Harvey

Siblings (11)

OIDNameDirect childrenDescendantsDescription
1.3.6.1.4.1.17420.1.1.2.5.2.1 upsSmartConfigRatedOutputVoltage00
1.3.6.1.4.1.17420.1.1.2.5.2.2 upsSmartConfigHighTransferVolt00
1.3.6.1.4.1.17420.1.1.2.5.2.3 upsSmartConfigLowTransferVolt00
1.3.6.1.4.1.17420.1.1.2.5.2.4 upsSmartConfigAlarm00
1.3.6.1.4.1.17420.1.1.2.5.2.5 upsSmartConfigAlarmTimer00
1.3.6.1.4.1.17420.1.1.2.5.2.7 upsSmartConfigSensitivity00
1.3.6.1.4.1.17420.1.1.2.5.2.8 upsSmartConfigLowBatteryRunTime00
1.3.6.1.4.1.17420.1.1.2.5.2.9 upsSmartConfigReturnDelay00
1.3.6.1.4.1.17420.1.1.2.5.2.10 upsSmartConfigShutoffDelay00
1.3.6.1.4.1.17420.1.1.2.5.2.11 upsSmartConfigUpsSleepTime00
1.3.6.1.4.1.17420.1.1.2.5.2.12 upsSmartConfigSetEEPROMDefaults00