Status in source: mandatory.
Names: upsSmartConfigReturnDelay
Technical details
{
"smi_kind": "OBJECT-TYPE",
"definition": [
"upsSmartConfigReturnDelay",
"OBJECT-TYPE",
"SYNTAX",
"INTEGER",
"ACCESS",
"read-write",
"STATUS",
"mandatory",
"DESCRIPTION",
"\"The delay in seconds after utility line power returns before the UPS will turn on. This value is also used when the UPS comes out of a reboot and before the UPS wakes up from 'sleep' mode. Allowed values are 0, 60, 180 and 300 seconds. If a value other than a supported value is provided in a set request, the UPS interprets it as a the next higher acceptable value. If the provided value is higher than the highest acceptable value, the highest acceptable value is used.\"",
"::=",
"{",
"upsSmartConfig",
"9",
"}"
],
"syntax_tree": [
[
"SimpleSyntax",
"INTEGER"
],
null,
[
"MaxAccessPart",
"read-write"
],
[
"Status",
"mandatory"
],
[
"DESCRIPTION",
"The delay in seconds after utility line power returns before the UPS will turn on. This value is also used when the UPS comes out of a reboot and before the UPS wakes up from 'sleep' mode. Allowed values are 0, 60, 180 and 300 seconds. If a value other than a supported value is provided in a set request, the UPS interprets it as a the next higher acceptable value. If the provided value is higher than the highest acceptable value, the highest acceptable value is used."
],
null,
null,
null,
null
]
}