The output table entry containing the voltage, current, PF,
percent load, VA, Watts for the Modular PDU.
Parsed from file CPQPOWER1.62.MIB.txt
Company: compaq
Module: CPQPOWER-MIB
mpduOutputEntry OBJECT-TYPE SYNTAX MpduOutputEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The output table entry containing the voltage, current, PF, percent load, VA, Watts for the Modular PDU." INDEX { mpduIdentIndex, mpduOutputIndex } ::= { mpduOutputTable 1 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.232.165.5.2.1.1.1 | mpduOutputIndex | 0 | 0 | Index for the MpduOutputEntry table. |
1.3.6.1.4.1.232.165.5.2.1.1.2 | mpduOutputStatus | 0 | 0 | The overall status of the device: off, on, problem. |
1.3.6.1.4.1.232.165.5.2.1.1.3 | mpduOutputBreakerRating | 0 | 0 | The rating of each MPDU Output in Ampere. |
1.3.6.1.4.1.232.165.5.2.1.1.4 | mpduOutputSmartDevice | 0 | 0 | A smart cord device detected: False, True. |
1.3.6.1.4.1.232.165.5.2.1.1.5 | mpduOutputPercentLoad | 0 | 0 | The MPDU's each output load in percent of rated capacity. Value is presented in 1/10 of the percentage i.e. 125 is 12.5%. A val… |
1.3.6.1.4.1.232.165.5.2.1.1.6 | mpduOutputVoltage | 0 | 0 | The measured output voltage from the PDU meters in volts. Value is presented in 1/10 of the Volt i.e. 2095 is 209.5 V. A value o… |
1.3.6.1.4.1.232.165.5.2.1.1.7 | mpduOutputCurrent | 0 | 0 | The measured output current from the PDU meters in amps. Value is presented in 1/100 of the Ampere i.e. 175 is 1.75 A. A value o… |
1.3.6.1.4.1.232.165.5.2.1.1.8 | mpduOutputPowerVA | 0 | 0 | The total VA load (VI) measured on the PDU in VA. A value of -1 will be returned if the power is unable to be calculated. |
1.3.6.1.4.1.232.165.5.2.1.1.9 | mpduOutputPowerWatt | 0 | 0 | The total power load measured on the PDU in Watts. A value of -1 will be returned if the power is unable to be calculated. |
1.3.6.1.4.1.232.165.5.2.1.1.10 | mpduOutputPowerFactor | 0 | 0 | The power factor is presented in 1/100 of the unit i.e. 98 is 0.98. A value of -1 will be returned if the power factor is unabl… |
1.3.6.1.4.1.232.165.5.2.1.1.11 | mpduOutputWarningThreshold | 0 | 0 | Report the User-set threshhold limit for Warning in percentage |
1.3.6.1.4.1.232.165.5.2.1.1.12 | mpduOutputCriticalThreshold | 0 | 0 | Report the User-set threshhold limit for Critical in percentage |