Reference record for OID 1.3.6.1.4.1.318.1.1.1.11.2.14

Parent
1.3.6.1.4.1.318.1.1.1.11.2 (upsAdvState)
Node code
14
Node name
upsAdvStateLifeCycleManagement
Numeric OID
1.3.6.1.4.1.318.1.1.1.11.2.14
URN notation
urn:oid:1.3.6.1.4.1.318.1.1.1.11.2.14
ASN.1 notation

{1 3 6 1 4 1 318 1 1 1 11 2 14}

  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateLifeCycleManagement(14)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateLifeCycleManagement(14)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateLifeCycleManagement(14)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) vendor-objects(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateLifeCycleManagement(14)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateLifeCycleManagement(14)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateLifeCycleManagement(14)}
  • {iso(1) org(3) dod(6) internet(1) private(4) ldap-enterprise(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateLifeCycleManagement(14)}
  • {iso(1) org(3) dod(6) internet(1) private(4) vendor-objects(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateLifeCycleManagement(14)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateLifeCycleManagement(14)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateLifeCycleManagement(14)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateLifeCycleManagement(14)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) vendor-objects(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateLifeCycleManagement(14)}
  • {iso(1) iso-organization(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateLifeCycleManagement(14)}
  • {iso(1) iso-organization(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateLifeCycleManagement(14)}
  • {iso(1) iso-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateLifeCycleManagement(14)}
  • {iso(1) iso-organization(3) dod(6) internet(1) private(4) vendor-objects(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateLifeCycleManagement(14)}
OID-IRI notation
  • /1/3/6/1/4/1/318/1/1/1/11/2/14
  • /ISO/Identified-Organization/6/1/4/1/318/1/1/1/11/2/14
  • /ISO/3/6/1/4/1/318/1/1/1/11/2/14
Named path variants
  • /iso/identified-organization/dod/internet/private/enterprise/apc/products/hardware/ups/upsState/upsAdvState/upsAdvStateLifeCycleManagement
  • /iso/identified-organization/dod/internet/private/enterprise/PDU/products/hardware/ups/upsState/upsAdvState/upsAdvStateLifeCycleManagement
  • /iso/identified-organization/dod/internet/private/enterprises/apc/products/hardware/ups/upsState/upsAdvState/upsAdvStateLifeCycleManagement
  • /iso/identified-organization/dod/internet/private/enterprises/PDU/products/hardware/ups/upsState/upsAdvState/upsAdvStateLifeCycleManagement
  • /iso/identified-organization/dod/internet/private/ldap-enterprise/apc/products/hardware/ups/upsState/upsAdvState/upsAdvStateLifeCycleManagement
  • /iso/identified-organization/dod/internet/private/ldap-enterprise/PDU/products/hardware/ups/upsState/upsAdvState/upsAdvStateLifeCycleManagement
  • /iso/identified-organization/dod/internet/private/vendor-objects/apc/products/hardware/ups/upsState/upsAdvState/upsAdvStateLifeCycleManagement
  • /iso/identified-organization/dod/internet/private/vendor-objects/PDU/products/hardware/ups/upsState/upsAdvState/upsAdvStateLifeCycleManagement
  • /iso/org/dod/internet/private/enterprise/apc/products/hardware/ups/upsState/upsAdvState/upsAdvStateLifeCycleManagement
  • /iso/org/dod/internet/private/enterprise/PDU/products/hardware/ups/upsState/upsAdvState/upsAdvStateLifeCycleManagement
  • /iso/org/dod/internet/private/enterprises/apc/products/hardware/ups/upsState/upsAdvState/upsAdvStateLifeCycleManagement
  • /iso/org/dod/internet/private/enterprises/PDU/products/hardware/ups/upsState/upsAdvState/upsAdvStateLifeCycleManagement
  • /iso/org/dod/internet/private/ldap-enterprise/apc/products/hardware/ups/upsState/upsAdvState/upsAdvStateLifeCycleManagement
  • /iso/org/dod/internet/private/ldap-enterprise/PDU/products/hardware/ups/upsState/upsAdvState/upsAdvStateLifeCycleManagement
  • /iso/org/dod/internet/private/vendor-objects/apc/products/hardware/ups/upsState/upsAdvState/upsAdvStateLifeCycleManagement
  • /iso/org/dod/internet/private/vendor-objects/PDU/products/hardware/ups/upsState/upsAdvState/upsAdvStateLifeCycleManagement
  • Additional combinations skipped.

Descriptions

upsAdvStateLifeCycleManagement — Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)

An ASCII string containing the 16 flags representing the life cycle management alerts for the device. If the Network Card is unable to determine the values of the flags, this variable is set to 'UNKNOWN'. If the connected UPS does not use this variable, it is set to 'NOT SUPPORTED'. The flags are numbered from 1 to 16, and read from left to right. The bits are defined as follows: Flag 1: End of Warranty Soon Flag 2: Battery Check Recommended Flag 3: Service Period On Wearing Parts Expired Flag 4: Secure Start-up Recommended Flag 5: Fan Life Expired Flag 6: DC Capacitor Life Expired Flag 7: AC Capacitor Life Expired Flag 8: Supply Service Life Expired Flag 9: Ups Out Of Limits Warning Flag 10: Air Filter Life Expired Flag 11: <Not Used> Flag 12: <Not Used> Flag 13: <Not Used> Flag 14: <Not Used> Flag 15: <Not Used> Flag 16: <Not Used>

Source records

upsAdvStateLifeCycleManagement

Status in source: mandatory.

Names: upsAdvStateLifeCycleManagement

Technical details
{
  "smi_kind": "OBJECT-TYPE",
  "definition": [
    "upsAdvStateLifeCycleManagement",
    "OBJECT-TYPE",
    "SYNTAX",
    "DisplayString",
    "ACCESS",
    "read-only",
    "STATUS",
    "mandatory",
    "DESCRIPTION",
    "\"An ASCII string containing the 16 flags representing the life cycle management alerts for the device. If the Network Card is unable to determine the values of the flags, this variable is set to 'UNKNOWN'. If the connected UPS does not use this variable, it is set to 'NOT SUPPORTED'. The flags are numbered from 1 to 16, and read from left to right. The bits are defined as follows: Flag 1: End of Warranty Soon Flag 2: Battery Check Recommended Flag 3: Service Period On Wearing Parts Expired Flag 4: Secure Start-up Recommended Flag 5: Fan Life Expired Flag 6: DC Capacitor Life Expired Flag 7: AC Capacitor Life Expired Flag 8: Supply Service Life Expired Flag 9: Ups Out Of Limits Warning Flag 10: Air Filter Life Expired Flag 11: <Not Used> Flag 12: <Not Used> Flag 13: <Not Used> Flag 14: <Not Used> Flag 15: <Not Used> Flag 16: <Not Used>\"",
    "::=",
    "{",
    "upsAdvState",
    "14",
    "}"
  ],
  "syntax_tree": [
    [
      "row",
      "DisplayString"
    ],
    null,
    [
      "MaxAccessPart",
      "read-only"
    ],
    [
      "Status",
      "mandatory"
    ],
    [
      "DESCRIPTION",
      "An ASCII string containing the 16 flags representing the life cycle management alerts for the device. If the Network Card is unable to determine the values of the flags, this variable is set to 'UNKNOWN'. If the connected UPS does not use this variable, it is set to 'NOT SUPPORTED'. The flags are numbered from 1 to 16, and read from left to right. The bits are defined as follows: Flag 1: End of Warranty Soon Flag 2: Battery Check Recommended Flag 3: Service Period On Wearing Parts Expired Flag 4: Secure Start-up Recommended Flag 5: Fan Life Expired Flag 6: DC Capacitor Life Expired Flag 7: AC Capacitor Life Expired Flag 8: Supply Service Life Expired Flag 9: Ups Out Of Limits Warning Flag 10: Air Filter Life Expired Flag 11: <Not Used> Flag 12: <Not Used> Flag 13: <Not Used> Flag 14: <Not Used> Flag 15: <Not Used> Flag 16: <Not Used>"
    ],
    null,
    null,
    null,
    null
  ]
}
  • Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community) · Publisher's source file: PowerNet-MIB

    Vendor MIB copy from the LibreNMS archive.

    Module: PowerNet-MIB

    Published definition
    upsAdvStateLifeCycleManagement OBJECT-TYPE
       SYNTAX DisplayString
       ACCESS read-only
       STATUS mandatory
       DESCRIPTION
          "An ASCII string containing the 16 flags representing the life cycle management alerts
          for the device. If the Network Card is unable to determine the values of the flags,
          this variable is set to 'UNKNOWN'. If the connected UPS does not use this variable,
          it is set to 'NOT SUPPORTED'.
    
          The flags are numbered from 1 to 16, and read from left
          to right. The bits are defined as follows:
    
          Flag  1:	End of Warranty Soon
          Flag  2:	Battery Check Recommended
          Flag  3:	Service Period On Wearing Parts Expired
          Flag  4:	Secure Start-up Recommended
    
          Flag  5:	Fan Life Expired
          Flag  6: 	DC Capacitor Life Expired
          Flag  7: 	AC Capacitor Life Expired
          Flag  8: 	Supply Service Life Expired
    
          Flag  9: 	Ups Out Of Limits Warning
          Flag 10:  Air Filter Life Expired
          Flag 11: 	<Not Used>
          Flag 12: 	<Not Used>
    
          Flag 13: 	<Not Used>
          Flag 14: 	<Not Used>
          Flag 15: 	<Not Used>
          Flag 16: 	<Not Used>"
       ::= { upsAdvState 14 }
    Module imports
    {'RFC-1212': ['OBJECT-TYPE'], 'RFC-1215': ['TRAP-TYPE'], 'RFC1155-SMI': ['enterprises', 'IpAddress', 'Gauge', 'TimeTicks'], 'RFC1213-MIB': ['DisplayString'], 'SNMP-FRAMEWORK-MIB': ['SnmpAdminString']}

    Related source files and packages:


    Source location: PowerNet-MIB::upsAdvStateLifeCycleManagement.
    Source version and references

    Downloaded: 2026-10-24T02:14:13.503326+00:00.

  • Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community) · Publisher's source file: Source package: observium-community-latest.tar.gz

    Vendor MIB copy from the Observium Community archive.

    Module: PowerNet-MIB

    Published definition
    upsAdvStateLifeCycleManagement OBJECT-TYPE
       SYNTAX DisplayString
       ACCESS read-only
       STATUS mandatory
       DESCRIPTION
          "An ASCII string containing the 16 flags representing the life cycle management alerts
          for the device. If the Network Card is unable to determine the values of the flags,
          this variable is set to 'UNKNOWN'. If the connected UPS does not use this variable,
          it is set to 'NOT SUPPORTED'.
    
          The flags are numbered from 1 to 16, and read from left
          to right. The bits are defined as follows:
    
          Flag  1:	End of Warranty Soon
          Flag  2:	Battery Check Recommended
          Flag  3:	Service Period On Wearing Parts Expired
          Flag  4:	Secure Start-up Recommended
    
          Flag  5:	Fan Life Expired
          Flag  6: 	DC Capacitor Life Expired
          Flag  7: 	AC Capacitor Life Expired
          Flag  8: 	Supply Service Life Expired
    
          Flag  9: 	Ups Out Of Limits Warning
          Flag 10:  Air Filter Life Expired
          Flag 11: 	<Not Used>
          Flag 12: 	<Not Used>
    
          Flag 13: 	<Not Used>
          Flag 14: 	<Not Used>
          Flag 15: 	<Not Used>
          Flag 16: 	<Not Used>"
       ::= { upsAdvState 14 }
    Module imports
    {'RFC-1212': ['OBJECT-TYPE'], 'RFC-1215': ['TRAP-TYPE'], 'RFC1155-SMI': ['enterprises', 'IpAddress', 'Gauge', 'TimeTicks'], 'RFC1213-MIB': ['DisplayString'], 'SNMP-FRAMEWORK-MIB': ['SnmpAdminString']}

    Related source files and packages:


    Source location: PowerNet-MIB::upsAdvStateLifeCycleManagement.
    Source version and references

    Downloaded: 2026-10-24T02:14:28.042136+00:00.

First Registration Authority (inferred from ancestor 1.3.6.1.4.1.318)

Yoest Peter C.

Siblings (15)

OIDNameDirect childrenDescendantsDescription
1.3.6.1.4.1.318.1.1.1.11.2.1 upsAdvStateAbnormalConditions11 An ASCII string containing the 32 flags representing the current active UPS faults. If the Network Card is unable to determine …
1.3.6.1.4.1.318.1.1.1.11.2.2 upsAdvStateSymmetra3PhaseSpecificFaults11 An ASCII string containing the 64 flags representing the current active UPS specific faults for the Symmetra 3-Phase UPS models…
1.3.6.1.4.1.318.1.1.1.11.2.3 upsAdvStateDP300ESpecificFaults11 An ASCII string containing the 64 flags representing the current active UPS specific faults for the Silcon DP300E UPS models. I…
1.3.6.1.4.1.318.1.1.1.11.2.4 upsAdvStateSymmetraSpecificFaults11 An ASCII string containing the 64 flags representing the current active UPS specific faults for the Symmetra UPS models. If the…
1.3.6.1.4.1.318.1.1.1.11.2.5 upsAdvStateSmartUPSSpecificFaults11 An ASCII string containing the 64 flags representing the current active UPS specific faults for the Smart-UPS UPS models. If th…
1.3.6.1.4.1.318.1.1.1.11.2.6 upsAdvStateSystemMessages11 An ASCII string containing the 3 digit Decimal code
representing the current active message from the
System Message Register. Eac…
1.3.6.1.4.1.318.1.1.1.11.2.7 upsAdvStateTotaltimeonbattery00 Total time the UPS has been in battery operation.
1.3.6.1.4.1.318.1.1.1.11.2.8 upsAdvStateTotaltimeonbypass00 Total time the UPS has been in bypass operation.
1.3.6.1.4.1.318.1.1.1.11.2.9 upsAdvStateTotaltimeonNormal00 Total time the UPS has been in normal operation.
1.3.6.1.4.1.318.1.1.1.11.2.10 upsAdvStateNumberoftimesonbattery00 Number of times the UPS was on battery.
Since the last reset of statistical data.
1.3.6.1.4.1.318.1.1.1.11.2.11 upsAdvStateNumberoftimesbypass00 Number of times the UPS was in bypass.
Since the last reset of statistical data.
1.3.6.1.4.1.318.1.1.1.11.2.12 upsAdvStateNumberoftimesNormal00 Number of times the UPS was in normal operation.
Since the last reset of statistical data.
1.3.6.1.4.1.318.1.1.1.11.2.13 upsAdvStateEcomode00 Eco mode status.
1: UPS is on Eco-mode
2: UPS is not on Eco-mode.
1.3.6.1.4.1.318.1.1.1.11.2.15 upsAdvStateGalaxyVseriesSpecificFault00
1.3.6.1.4.1.318.1.1.1.11.2.16 upsAdvStateGutorModularSpecificFaults00