upsAdvStateGutorModularSpecificFaults — Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)
An ASCII string containing the 64 flags representing the current active Charger Rectifier and UPS specific faults for Gutor Modular models. Flag allocation: Flag 1 to 16 for breakers status (Charger Rectifier + UPS). 16 Flags Flag 17 to 32 for module errors. 16 Flags Flag 33 to 44 For charger errors. 12 Flags Flag 45 to 54 for battery errors. 10 flags Flag 55 to 64 for temperature errors. 10 flags If the Network Card is unable to determine the values of the flags, this variable is set to 'UNKNOWN'. If the connected UPS does not use this variable, it is set to 'NOT SUPPORTED'. The flags are numbered from 1 to 64 and read from left to right. The bits are defined as follows: Breaker (16 signals) Flag 1: Rectifier AC mains breaker 1 is OPEN Flag 2: Battery breaker 1 is OPEN Flag 3: Rectifier DC output breaker is OPEN Flag 4: PSU redundancy lost Flag 5: DC distribution feeder is OPEN Flag 6: Surge protection device is OPEN Flag 7: Option input 1 is ACTIVE Flag 8: Emergency power OFF is ACTIVE Flag 9: Inverter DC input breaker is OPEN Flag 10: Bypass AC mains breaker is OPEN Flag 11: System AC output breaker is OPEN Flag 12: AC distribution feeder is OPEN Flag 13: Rectifier AC mains breaker 2 is OPEN Flag 14: Battery breaker 2 is OPEN Flag 15: <Not Used> Flag 16: Roof fan disturbance is ACTIVE Flag 1 to Flag 16 should be accessible for device type charger, inverter and UPS Charger modules (16 signals) Flag 17: < 1431 - Module configuration mismatch > Flag 18: < 1433 - Load sharing error (All power modules) > Flag 19: < 1435 - Fan fault (All power modules) > Flag 20: < 1437 - Output voltage out of range (All power modules) > Flag 21: < 1436 - Input voltage out of range (All power modules) > Flag 22: < 1504 - System switched off > Flag 23: < 1513 - Warning address reserve > Flag 24: < 1514 - Address reserve error > Flag 25: < 1515 - Power reserve error > Flag 26: <Not Used> Flag 27: <Not Used> Flag 28: <Not Used> Flag 29: <Not Used> Flag 30: <Not Used> Flag 31: <Not Used> Flag 32: <Not Used> ALL (12 signals) Flag 33: < 6 - Common Alarm > Flag 34: < 7 - Urgent incident > Flag 35: < 8 - Non-urgent alarm > Flag 36: < 9 - HMI-MCU Com. Error > Flag 37: < 1428 - Equalization charge blocked > Flag 38: < 1432 - Boost charge blocked > Flag 39: < 1440 - High DC warning > Flag 40: < 1441 - High DC shutdown > Flag 41: < 1442 - Low DC warning > Flag 42: < 1443 - Low DC shutdown > Flag 43: <Not Used> Flag 44: <Not Used> Battery (10 signals) Flag 45: < 11 - Battery symmetry fault > Flag 46: < 1429 - Battery current limitation active > Flag 47: < 1430 - Battery current limitation configuration error > Flag 48: < 1512 - Battery temperature sensor defective > Flag 49: <Not Used> Flag 50: <Not Used> Flag 51: <Not Used> Flag 52: <Not Used> Flag 53: <Not Used> Flag 54: <Not Used> Temperature (10 signals) Flag 55: < 1444 - MCU temperature too high > Flag 56: <Not Used> Flag 57: <Not Used> Flag 58: <Not Used> Flag 59: <Not Used> Flag 60: <Not Used> Flag 61: <Not Used> Flag 62: <Not Used> Flag 63: <Not Used> Flag 64: <Not Used>