Reference record for OID 1.3.6.1.4.1.318.1.1.1.11.2.16

Parent
1.3.6.1.4.1.318.1.1.1.11.2 (upsAdvState)
Node code
16
Node name
upsAdvStateGutorModularSpecificFaults
Numeric OID
1.3.6.1.4.1.318.1.1.1.11.2.16
URN notation
urn:oid:1.3.6.1.4.1.318.1.1.1.11.2.16
ASN.1 notation

{1 3 6 1 4 1 318 1 1 1 11 2 16}

  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateGutorModularSpecificFaults(16)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateGutorModularSpecificFaults(16)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateGutorModularSpecificFaults(16)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) vendor-objects(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateGutorModularSpecificFaults(16)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateGutorModularSpecificFaults(16)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateGutorModularSpecificFaults(16)}
  • {iso(1) org(3) dod(6) internet(1) private(4) ldap-enterprise(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateGutorModularSpecificFaults(16)}
  • {iso(1) org(3) dod(6) internet(1) private(4) vendor-objects(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateGutorModularSpecificFaults(16)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateGutorModularSpecificFaults(16)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateGutorModularSpecificFaults(16)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateGutorModularSpecificFaults(16)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) vendor-objects(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateGutorModularSpecificFaults(16)}
  • {iso(1) iso-organization(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateGutorModularSpecificFaults(16)}
  • {iso(1) iso-organization(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateGutorModularSpecificFaults(16)}
  • {iso(1) iso-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateGutorModularSpecificFaults(16)}
  • {iso(1) iso-organization(3) dod(6) internet(1) private(4) vendor-objects(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateGutorModularSpecificFaults(16)}
OID-IRI notation
  • /1/3/6/1/4/1/318/1/1/1/11/2/16
  • /ISO/Identified-Organization/6/1/4/1/318/1/1/1/11/2/16
  • /ISO/3/6/1/4/1/318/1/1/1/11/2/16
Named path variants
  • /iso/identified-organization/dod/internet/private/enterprise/apc/products/hardware/ups/upsState/upsAdvState/upsAdvStateGutorModularSpecificFaults
  • /iso/identified-organization/dod/internet/private/enterprise/PDU/products/hardware/ups/upsState/upsAdvState/upsAdvStateGutorModularSpecificFaults
  • /iso/identified-organization/dod/internet/private/enterprises/apc/products/hardware/ups/upsState/upsAdvState/upsAdvStateGutorModularSpecificFaults
  • /iso/identified-organization/dod/internet/private/enterprises/PDU/products/hardware/ups/upsState/upsAdvState/upsAdvStateGutorModularSpecificFaults
  • /iso/identified-organization/dod/internet/private/ldap-enterprise/apc/products/hardware/ups/upsState/upsAdvState/upsAdvStateGutorModularSpecificFaults
  • /iso/identified-organization/dod/internet/private/ldap-enterprise/PDU/products/hardware/ups/upsState/upsAdvState/upsAdvStateGutorModularSpecificFaults
  • /iso/identified-organization/dod/internet/private/vendor-objects/apc/products/hardware/ups/upsState/upsAdvState/upsAdvStateGutorModularSpecificFaults
  • /iso/identified-organization/dod/internet/private/vendor-objects/PDU/products/hardware/ups/upsState/upsAdvState/upsAdvStateGutorModularSpecificFaults
  • /iso/org/dod/internet/private/enterprise/apc/products/hardware/ups/upsState/upsAdvState/upsAdvStateGutorModularSpecificFaults
  • /iso/org/dod/internet/private/enterprise/PDU/products/hardware/ups/upsState/upsAdvState/upsAdvStateGutorModularSpecificFaults
  • /iso/org/dod/internet/private/enterprises/apc/products/hardware/ups/upsState/upsAdvState/upsAdvStateGutorModularSpecificFaults
  • /iso/org/dod/internet/private/enterprises/PDU/products/hardware/ups/upsState/upsAdvState/upsAdvStateGutorModularSpecificFaults
  • /iso/org/dod/internet/private/ldap-enterprise/apc/products/hardware/ups/upsState/upsAdvState/upsAdvStateGutorModularSpecificFaults
  • /iso/org/dod/internet/private/ldap-enterprise/PDU/products/hardware/ups/upsState/upsAdvState/upsAdvStateGutorModularSpecificFaults
  • /iso/org/dod/internet/private/vendor-objects/apc/products/hardware/ups/upsState/upsAdvState/upsAdvStateGutorModularSpecificFaults
  • /iso/org/dod/internet/private/vendor-objects/PDU/products/hardware/ups/upsState/upsAdvState/upsAdvStateGutorModularSpecificFaults
  • Additional combinations skipped.

Descriptions

upsAdvStateGutorModularSpecificFaults — Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)

An ASCII string containing the 64 flags representing the current active Charger Rectifier and UPS specific faults for Gutor Modular models. Flag allocation: Flag 1 to 16 for breakers status (Charger Rectifier + UPS). 16 Flags Flag 17 to 32 for module errors. 16 Flags Flag 33 to 44 For charger errors. 12 Flags Flag 45 to 54 for battery errors. 10 flags Flag 55 to 64 for temperature errors. 10 flags If the Network Card is unable to determine the values of the flags, this variable is set to 'UNKNOWN'. If the connected UPS does not use this variable, it is set to 'NOT SUPPORTED'. The flags are numbered from 1 to 64 and read from left to right. The bits are defined as follows: Breaker (16 signals) Flag 1: Rectifier AC mains breaker 1 is OPEN Flag 2: Battery breaker 1 is OPEN Flag 3: Rectifier DC output breaker is OPEN Flag 4: PSU redundancy lost Flag 5: DC distribution feeder is OPEN Flag 6: Surge protection device is OPEN Flag 7: Option input 1 is ACTIVE Flag 8: Emergency power OFF is ACTIVE Flag 9: Inverter DC input breaker is OPEN Flag 10: Bypass AC mains breaker is OPEN Flag 11: System AC output breaker is OPEN Flag 12: AC distribution feeder is OPEN Flag 13: Rectifier AC mains breaker 2 is OPEN Flag 14: Battery breaker 2 is OPEN Flag 15: <Not Used> Flag 16: Roof fan disturbance is ACTIVE Flag 1 to Flag 16 should be accessible for device type charger, inverter and UPS Charger modules (16 signals) Flag 17: < 1431 - Module configuration mismatch > Flag 18: < 1433 - Load sharing error (All power modules) > Flag 19: < 1435 - Fan fault (All power modules) > Flag 20: < 1437 - Output voltage out of range (All power modules) > Flag 21: < 1436 - Input voltage out of range (All power modules) > Flag 22: < 1504 - System switched off > Flag 23: < 1513 - Warning address reserve > Flag 24: < 1514 - Address reserve error > Flag 25: < 1515 - Power reserve error > Flag 26: <Not Used> Flag 27: <Not Used> Flag 28: <Not Used> Flag 29: <Not Used> Flag 30: <Not Used> Flag 31: <Not Used> Flag 32: <Not Used> ALL (12 signals) Flag 33: < 6 - Common Alarm > Flag 34: < 7 - Urgent incident > Flag 35: < 8 - Non-urgent alarm > Flag 36: < 9 - HMI-MCU Com. Error > Flag 37: < 1428 - Equalization charge blocked > Flag 38: < 1432 - Boost charge blocked > Flag 39: < 1440 - High DC warning > Flag 40: < 1441 - High DC shutdown > Flag 41: < 1442 - Low DC warning > Flag 42: < 1443 - Low DC shutdown > Flag 43: <Not Used> Flag 44: <Not Used> Battery (10 signals) Flag 45: < 11 - Battery symmetry fault > Flag 46: < 1429 - Battery current limitation active > Flag 47: < 1430 - Battery current limitation configuration error > Flag 48: < 1512 - Battery temperature sensor defective > Flag 49: <Not Used> Flag 50: <Not Used> Flag 51: <Not Used> Flag 52: <Not Used> Flag 53: <Not Used> Flag 54: <Not Used> Temperature (10 signals) Flag 55: < 1444 - MCU temperature too high > Flag 56: <Not Used> Flag 57: <Not Used> Flag 58: <Not Used> Flag 59: <Not Used> Flag 60: <Not Used> Flag 61: <Not Used> Flag 62: <Not Used> Flag 63: <Not Used> Flag 64: <Not Used>

Source records

upsAdvStateGutorModularSpecificFaults

Status in source: optional.

Names: upsAdvStateGutorModularSpecificFaults

Technical details
{
  "smi_kind": "OBJECT-TYPE",
  "definition": [
    "upsAdvStateGutorModularSpecificFaults",
    "OBJECT-TYPE",
    "SYNTAX",
    "DisplayString",
    "ACCESS",
    "read-only",
    "STATUS",
    "optional",
    "DESCRIPTION",
    "\"An ASCII string containing the 64 flags representing the current active Charger Rectifier and UPS specific faults for Gutor Modular models. Flag allocation: Flag 1 to 16 for breakers status (Charger Rectifier + UPS). 16 Flags Flag 17 to 32 for module errors. 16 Flags Flag 33 to 44 For charger errors. 12 Flags Flag 45 to 54 for battery errors. 10 flags Flag 55 to 64 for temperature errors. 10 flags If the Network Card is unable to determine the values of the flags, this variable is set to 'UNKNOWN'. If the connected UPS does not use this variable, it is set to 'NOT SUPPORTED'. The flags are numbered from 1 to 64 and read from left to right. The bits are defined as follows: Breaker (16 signals) Flag 1: Rectifier AC mains breaker 1 is OPEN Flag 2: Battery breaker 1 is OPEN Flag 3: Rectifier DC output breaker is OPEN Flag 4: PSU redundancy lost Flag 5: DC distribution feeder is OPEN Flag 6: Surge protection device is OPEN Flag 7: Option input 1 is ACTIVE Flag 8: Emergency power OFF is ACTIVE Flag 9: Inverter DC input breaker is OPEN Flag 10: Bypass AC mains breaker is OPEN Flag 11: System AC output breaker is OPEN Flag 12: AC distribution feeder is OPEN Flag 13: Rectifier AC mains breaker 2 is OPEN Flag 14: Battery breaker 2 is OPEN Flag 15: <Not Used> Flag 16: Roof fan disturbance is ACTIVE Flag 1 to Flag 16 should be accessible for device type charger, inverter and UPS Charger modules (16 signals) Flag 17: < 1431 - Module configuration mismatch > Flag 18: < 1433 - Load sharing error (All power modules) > Flag 19: < 1435 - Fan fault (All power modules) > Flag 20: < 1437 - Output voltage out of range (All power modules) > Flag 21: < 1436 - Input voltage out of range (All power modules) > Flag 22: < 1504 - System switched off > Flag 23: < 1513 - Warning address reserve > Flag 24: < 1514 - Address reserve error > Flag 25: < 1515 - Power reserve error > Flag 26: <Not Used> Flag 27: <Not Used> Flag 28: <Not Used> Flag 29: <Not Used> Flag 30: <Not Used> Flag 31: <Not Used> Flag 32: <Not Used> ALL (12 signals) Flag 33: < 6 - Common Alarm > Flag 34: < 7 - Urgent incident > Flag 35: < 8 - Non-urgent alarm > Flag 36: < 9 - HMI-MCU Com. Error > Flag 37: < 1428 - Equalization charge blocked > Flag 38: < 1432 - Boost charge blocked > Flag 39: < 1440 - High DC warning > Flag 40: < 1441 - High DC shutdown > Flag 41: < 1442 - Low DC warning > Flag 42: < 1443 - Low DC shutdown > Flag 43: <Not Used> Flag 44: <Not Used> Battery (10 signals) Flag 45: < 11 - Battery symmetry fault > Flag 46: < 1429 - Battery current limitation active > Flag 47: < 1430 - Battery current limitation configuration error > Flag 48: < 1512 - Battery temperature sensor defective > Flag 49: <Not Used> Flag 50: <Not Used> Flag 51: <Not Used> Flag 52: <Not Used> Flag 53: <Not Used> Flag 54: <Not Used> Temperature (10 signals) Flag 55: < 1444 - MCU temperature too high > Flag 56: <Not Used> Flag 57: <Not Used> Flag 58: <Not Used> Flag 59: <Not Used> Flag 60: <Not Used> Flag 61: <Not Used> Flag 62: <Not Used> Flag 63: <Not Used> Flag 64: <Not Used>\"",
    "::=",
    "{",
    "upsAdvState",
    "16",
    "}"
  ],
  "syntax_tree": [
    [
      "row",
      "DisplayString"
    ],
    null,
    [
      "MaxAccessPart",
      "read-only"
    ],
    [
      "Status",
      "optional"
    ],
    [
      "DESCRIPTION",
      "An ASCII string containing the 64 flags representing the current active Charger Rectifier and UPS specific faults for Gutor Modular models. Flag allocation: Flag 1 to 16 for breakers status (Charger Rectifier + UPS). 16 Flags Flag 17 to 32 for module errors. 16 Flags Flag 33 to 44 For charger errors. 12 Flags Flag 45 to 54 for battery errors. 10 flags Flag 55 to 64 for temperature errors. 10 flags If the Network Card is unable to determine the values of the flags, this variable is set to 'UNKNOWN'. If the connected UPS does not use this variable, it is set to 'NOT SUPPORTED'. The flags are numbered from 1 to 64 and read from left to right. The bits are defined as follows: Breaker (16 signals) Flag 1: Rectifier AC mains breaker 1 is OPEN Flag 2: Battery breaker 1 is OPEN Flag 3: Rectifier DC output breaker is OPEN Flag 4: PSU redundancy lost Flag 5: DC distribution feeder is OPEN Flag 6: Surge protection device is OPEN Flag 7: Option input 1 is ACTIVE Flag 8: Emergency power OFF is ACTIVE Flag 9: Inverter DC input breaker is OPEN Flag 10: Bypass AC mains breaker is OPEN Flag 11: System AC output breaker is OPEN Flag 12: AC distribution feeder is OPEN Flag 13: Rectifier AC mains breaker 2 is OPEN Flag 14: Battery breaker 2 is OPEN Flag 15: <Not Used> Flag 16: Roof fan disturbance is ACTIVE Flag 1 to Flag 16 should be accessible for device type charger, inverter and UPS Charger modules (16 signals) Flag 17: < 1431 - Module configuration mismatch > Flag 18: < 1433 - Load sharing error (All power modules) > Flag 19: < 1435 - Fan fault (All power modules) > Flag 20: < 1437 - Output voltage out of range (All power modules) > Flag 21: < 1436 - Input voltage out of range (All power modules) > Flag 22: < 1504 - System switched off > Flag 23: < 1513 - Warning address reserve > Flag 24: < 1514 - Address reserve error > Flag 25: < 1515 - Power reserve error > Flag 26: <Not Used> Flag 27: <Not Used> Flag 28: <Not Used> Flag 29: <Not Used> Flag 30: <Not Used> Flag 31: <Not Used> Flag 32: <Not Used> ALL (12 signals) Flag 33: < 6 - Common Alarm > Flag 34: < 7 - Urgent incident > Flag 35: < 8 - Non-urgent alarm > Flag 36: < 9 - HMI-MCU Com. Error > Flag 37: < 1428 - Equalization charge blocked > Flag 38: < 1432 - Boost charge blocked > Flag 39: < 1440 - High DC warning > Flag 40: < 1441 - High DC shutdown > Flag 41: < 1442 - Low DC warning > Flag 42: < 1443 - Low DC shutdown > Flag 43: <Not Used> Flag 44: <Not Used> Battery (10 signals) Flag 45: < 11 - Battery symmetry fault > Flag 46: < 1429 - Battery current limitation active > Flag 47: < 1430 - Battery current limitation configuration error > Flag 48: < 1512 - Battery temperature sensor defective > Flag 49: <Not Used> Flag 50: <Not Used> Flag 51: <Not Used> Flag 52: <Not Used> Flag 53: <Not Used> Flag 54: <Not Used> Temperature (10 signals) Flag 55: < 1444 - MCU temperature too high > Flag 56: <Not Used> Flag 57: <Not Used> Flag 58: <Not Used> Flag 59: <Not Used> Flag 60: <Not Used> Flag 61: <Not Used> Flag 62: <Not Used> Flag 63: <Not Used> Flag 64: <Not Used>"
    ],
    null,
    null,
    null,
    null
  ]
}
  • Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community) · Publisher's source file: PowerNet-MIB

    Vendor MIB copy from the LibreNMS archive.

    Module: PowerNet-MIB

    Published definition
    upsAdvStateGutorModularSpecificFaults  OBJECT-TYPE
       SYNTAX DisplayString
       ACCESS read-only
       STATUS optional
       DESCRIPTION
            "An ASCII string containing the 64 flags representing
             the current active Charger Rectifier and UPS specific faults for Gutor Modular models.
             Flag allocation:
             Flag 1 to 16 for breakers status (Charger Rectifier + UPS). 16 Flags
             Flag 17 to 32 for module errors.  16 Flags
             Flag 33 to 44 For charger errors. 12 Flags
             Flag 45 to 54 for battery errors. 10 flags
             Flag 55 to 64 for temperature errors. 10 flags
             If the Network Card is unable to determine the values of the flags, this variable is set to 'UNKNOWN'.
             If the connected UPS does not use this variable, it is set to 'NOT SUPPORTED'.
    
             The flags are numbered from 1 to 64 and read from left to right. The bits are defined as follows:
    
             Breaker (16 signals)
    
             Flag 1: Rectifier AC mains breaker 1 is OPEN
             Flag 2: Battery breaker 1 is OPEN
             Flag 3: Rectifier DC output breaker is OPEN
             Flag 4: PSU redundancy lost
             Flag 5: DC distribution feeder is OPEN
             Flag 6: Surge protection device is OPEN
             Flag 7: Option input 1 is ACTIVE
             Flag 8: Emergency power OFF is ACTIVE
             Flag 9: Inverter DC input breaker is OPEN
             Flag 10: Bypass AC mains breaker is OPEN
             Flag 11: System AC output breaker is OPEN
             Flag 12: AC distribution feeder is OPEN
             Flag 13: Rectifier AC mains breaker 2 is OPEN
             Flag 14: Battery breaker 2 is OPEN
             Flag 15: <Not Used>
             Flag 16: Roof fan disturbance is ACTIVE
    
             Flag 1 to Flag 16 should be accessible for device type charger, inverter and UPS		 
    
             Charger modules (16 signals)
    
             Flag 17: < 1431 - Module configuration mismatch >
             Flag 18: < 1433 - Load sharing error (All power modules) >
             Flag 19: < 1435 - Fan fault (All power modules) >
             Flag 20: < 1437 - Output voltage out of range (All power modules) >
             Flag 21: < 1436 - Input voltage out of range (All power modules) >
             Flag 22: < 1504 - System switched off >
             Flag 23: < 1513 - Warning address reserve >
             Flag 24: < 1514 - Address reserve error >
             Flag 25: < 1515 - Power reserve error >
             Flag 26: <Not Used>
             Flag 27: <Not Used>
             Flag 28: <Not Used>
             Flag 29: <Not Used>
             Flag 30: <Not Used>
             Flag 31: <Not Used>
             Flag 32: <Not Used>
    
             ALL (12 signals)
    
             Flag 33: < 6 - Common Alarm >
             Flag 34: < 7 - Urgent incident >
             Flag 35: < 8 - Non-urgent alarm >
             Flag 36: < 9 -	HMI-MCU Com. Error > 
             Flag 37: < 1428 - Equalization charge blocked >
             Flag 38: < 1432 - Boost charge blocked >
             Flag 39: < 1440 - High DC warning >
             Flag 40: < 1441 - High DC shutdown >
             Flag 41: < 1442 - Low DC warning >
             Flag 42: < 1443 - Low DC shutdown >
             Flag 43: <Not Used>
             Flag 44: <Not Used>
    
             Battery (10 signals)
    
             Flag 45: < 11 - Battery symmetry fault >
             Flag 46: < 1429 - Battery current limitation active >
             Flag 47: < 1430 - Battery current limitation configuration error >
             Flag 48: < 1512 - Battery temperature sensor defective >
             Flag 49: <Not Used>
             Flag 50: <Not Used>
             Flag 51: <Not Used>
             Flag 52: <Not Used>
             Flag 53: <Not Used>
             Flag 54: <Not Used>
    
             Temperature (10 signals)
    
             Flag 55: < 1444 - MCU temperature too high >
             Flag 56: <Not Used>
             Flag 57: <Not Used>
             Flag 58: <Not Used>
             Flag 59: <Not Used>
             Flag 60: <Not Used>
             Flag 61: <Not Used>
             Flag 62: <Not Used>
             Flag 63: <Not Used>
             Flag 64: <Not Used>"
          ::= { upsAdvState 16 }
    Module imports
    {'RFC-1212': ['OBJECT-TYPE'], 'RFC-1215': ['TRAP-TYPE'], 'RFC1155-SMI': ['enterprises', 'IpAddress', 'Gauge', 'TimeTicks'], 'RFC1213-MIB': ['DisplayString'], 'SNMP-FRAMEWORK-MIB': ['SnmpAdminString']}

    Related source files and packages:


    Source location: PowerNet-MIB::upsAdvStateGutorModularSpecificFaults.
    Source version and references

    Downloaded: 2026-10-24T02:14:13.503326+00:00.

  • Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community) · Publisher's source file: Source package: observium-community-latest.tar.gz

    Vendor MIB copy from the Observium Community archive.

    Module: PowerNet-MIB

    Published definition
    upsAdvStateGutorModularSpecificFaults  OBJECT-TYPE
       SYNTAX DisplayString
       ACCESS read-only
       STATUS optional
       DESCRIPTION
            "An ASCII string containing the 64 flags representing
             the current active Charger Rectifier and UPS specific faults for Gutor Modular models.
             Flag allocation:
             Flag 1 to 16 for breakers status (Charger Rectifier + UPS). 16 Flags
             Flag 17 to 32 for module errors.  16 Flags
             Flag 33 to 44 For charger errors. 12 Flags
             Flag 45 to 54 for battery errors. 10 flags
             Flag 55 to 64 for temperature errors. 10 flags
             If the Network Card is unable to determine the values of the flags, this variable is set to 'UNKNOWN'.
             If the connected UPS does not use this variable, it is set to 'NOT SUPPORTED'.
    
             The flags are numbered from 1 to 64 and read from left to right. The bits are defined as follows:
    
             Breaker (16 signals)
    
             Flag 1: Rectifier AC mains breaker 1 is OPEN
             Flag 2: Battery breaker 1 is OPEN
             Flag 3: Rectifier DC output breaker is OPEN
             Flag 4: PSU redundancy lost
             Flag 5: DC distribution feeder is OPEN
             Flag 6: Surge protection device is OPEN
             Flag 7: Option input 1 is ACTIVE
             Flag 8: Emergency power OFF is ACTIVE
             Flag 9: Inverter DC input breaker is OPEN
             Flag 10: Bypass AC mains breaker is OPEN
             Flag 11: System AC output breaker is OPEN
             Flag 12: AC distribution feeder is OPEN
             Flag 13: Rectifier AC mains breaker 2 is OPEN
             Flag 14: Battery breaker 2 is OPEN
             Flag 15: <Not Used>
             Flag 16: Roof fan disturbance is ACTIVE
    
             Flag 1 to Flag 16 should be accessible for device type charger, inverter and UPS		 
    
             Charger modules (16 signals)
    
             Flag 17: < 1431 - Module configuration mismatch >
             Flag 18: < 1433 - Load sharing error (All power modules) >
             Flag 19: < 1435 - Fan fault (All power modules) >
             Flag 20: < 1437 - Output voltage out of range (All power modules) >
             Flag 21: < 1436 - Input voltage out of range (All power modules) >
             Flag 22: < 1504 - System switched off >
             Flag 23: < 1513 - Warning address reserve >
             Flag 24: < 1514 - Address reserve error >
             Flag 25: < 1515 - Power reserve error >
             Flag 26: <Not Used>
             Flag 27: <Not Used>
             Flag 28: <Not Used>
             Flag 29: <Not Used>
             Flag 30: <Not Used>
             Flag 31: <Not Used>
             Flag 32: <Not Used>
    
             ALL (12 signals)
    
             Flag 33: < 6 - Common Alarm >
             Flag 34: < 7 - Urgent incident >
             Flag 35: < 8 - Non-urgent alarm >
             Flag 36: < 9 -	HMI-MCU Com. Error > 
             Flag 37: < 1428 - Equalization charge blocked >
             Flag 38: < 1432 - Boost charge blocked >
             Flag 39: < 1440 - High DC warning >
             Flag 40: < 1441 - High DC shutdown >
             Flag 41: < 1442 - Low DC warning >
             Flag 42: < 1443 - Low DC shutdown >
             Flag 43: <Not Used>
             Flag 44: <Not Used>
    
             Battery (10 signals)
    
             Flag 45: < 11 - Battery symmetry fault >
             Flag 46: < 1429 - Battery current limitation active >
             Flag 47: < 1430 - Battery current limitation configuration error >
             Flag 48: < 1512 - Battery temperature sensor defective >
             Flag 49: <Not Used>
             Flag 50: <Not Used>
             Flag 51: <Not Used>
             Flag 52: <Not Used>
             Flag 53: <Not Used>
             Flag 54: <Not Used>
    
             Temperature (10 signals)
    
             Flag 55: < 1444 - MCU temperature too high >
             Flag 56: <Not Used>
             Flag 57: <Not Used>
             Flag 58: <Not Used>
             Flag 59: <Not Used>
             Flag 60: <Not Used>
             Flag 61: <Not Used>
             Flag 62: <Not Used>
             Flag 63: <Not Used>
             Flag 64: <Not Used>"
          ::= { upsAdvState 16 }
    Module imports
    {'RFC-1212': ['OBJECT-TYPE'], 'RFC-1215': ['TRAP-TYPE'], 'RFC1155-SMI': ['enterprises', 'IpAddress', 'Gauge', 'TimeTicks'], 'RFC1213-MIB': ['DisplayString'], 'SNMP-FRAMEWORK-MIB': ['SnmpAdminString']}

    Related source files and packages:


    Source location: PowerNet-MIB::upsAdvStateGutorModularSpecificFaults.
    Source version and references

    Downloaded: 2026-10-24T02:14:28.042136+00:00.

First Registration Authority (inferred from ancestor 1.3.6.1.4.1.318)

Yoest Peter C.

Siblings (15)

OIDNameDirect childrenDescendantsDescription
1.3.6.1.4.1.318.1.1.1.11.2.1 upsAdvStateAbnormalConditions11 An ASCII string containing the 32 flags representing the current active UPS faults. If the Network Card is unable to determine …
1.3.6.1.4.1.318.1.1.1.11.2.2 upsAdvStateSymmetra3PhaseSpecificFaults11 An ASCII string containing the 64 flags representing the current active UPS specific faults for the Symmetra 3-Phase UPS models…
1.3.6.1.4.1.318.1.1.1.11.2.3 upsAdvStateDP300ESpecificFaults11 An ASCII string containing the 64 flags representing the current active UPS specific faults for the Silcon DP300E UPS models. I…
1.3.6.1.4.1.318.1.1.1.11.2.4 upsAdvStateSymmetraSpecificFaults11 An ASCII string containing the 64 flags representing the current active UPS specific faults for the Symmetra UPS models. If the…
1.3.6.1.4.1.318.1.1.1.11.2.5 upsAdvStateSmartUPSSpecificFaults11 An ASCII string containing the 64 flags representing the current active UPS specific faults for the Smart-UPS UPS models. If th…
1.3.6.1.4.1.318.1.1.1.11.2.6 upsAdvStateSystemMessages11 An ASCII string containing the 3 digit Decimal code
representing the current active message from the
System Message Register. Eac…
1.3.6.1.4.1.318.1.1.1.11.2.7 upsAdvStateTotaltimeonbattery00 Total time the UPS has been in battery operation.
1.3.6.1.4.1.318.1.1.1.11.2.8 upsAdvStateTotaltimeonbypass00 Total time the UPS has been in bypass operation.
1.3.6.1.4.1.318.1.1.1.11.2.9 upsAdvStateTotaltimeonNormal00 Total time the UPS has been in normal operation.
1.3.6.1.4.1.318.1.1.1.11.2.10 upsAdvStateNumberoftimesonbattery00 Number of times the UPS was on battery.
Since the last reset of statistical data.
1.3.6.1.4.1.318.1.1.1.11.2.11 upsAdvStateNumberoftimesbypass00 Number of times the UPS was in bypass.
Since the last reset of statistical data.
1.3.6.1.4.1.318.1.1.1.11.2.12 upsAdvStateNumberoftimesNormal00 Number of times the UPS was in normal operation.
Since the last reset of statistical data.
1.3.6.1.4.1.318.1.1.1.11.2.13 upsAdvStateEcomode00 Eco mode status.
1: UPS is on Eco-mode
2: UPS is not on Eco-mode.
1.3.6.1.4.1.318.1.1.1.11.2.14 upsAdvStateLifeCycleManagement00
1.3.6.1.4.1.318.1.1.1.11.2.15 upsAdvStateGalaxyVseriesSpecificFault00