Reference record for OID 1.3.6.1.4.1.318.1.1.1.11.2.15

Parent
1.3.6.1.4.1.318.1.1.1.11.2 (upsAdvState)
Node code
15
Node name
upsAdvStateGalaxyVseriesSpecificFault
Numeric OID
1.3.6.1.4.1.318.1.1.1.11.2.15
URN notation
urn:oid:1.3.6.1.4.1.318.1.1.1.11.2.15
ASN.1 notation

{1 3 6 1 4 1 318 1 1 1 11 2 15}

  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateGalaxyVseriesSpecificFault(15)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateGalaxyVseriesSpecificFault(15)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateGalaxyVseriesSpecificFault(15)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) vendor-objects(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateGalaxyVseriesSpecificFault(15)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateGalaxyVseriesSpecificFault(15)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateGalaxyVseriesSpecificFault(15)}
  • {iso(1) org(3) dod(6) internet(1) private(4) ldap-enterprise(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateGalaxyVseriesSpecificFault(15)}
  • {iso(1) org(3) dod(6) internet(1) private(4) vendor-objects(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateGalaxyVseriesSpecificFault(15)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateGalaxyVseriesSpecificFault(15)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateGalaxyVseriesSpecificFault(15)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateGalaxyVseriesSpecificFault(15)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) vendor-objects(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateGalaxyVseriesSpecificFault(15)}
  • {iso(1) iso-organization(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateGalaxyVseriesSpecificFault(15)}
  • {iso(1) iso-organization(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateGalaxyVseriesSpecificFault(15)}
  • {iso(1) iso-organization(3) dod(6) internet(1) private(4) ldap-enterprise(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateGalaxyVseriesSpecificFault(15)}
  • {iso(1) iso-organization(3) dod(6) internet(1) private(4) vendor-objects(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateGalaxyVseriesSpecificFault(15)}
OID-IRI notation
  • /1/3/6/1/4/1/318/1/1/1/11/2/15
  • /ISO/Identified-Organization/6/1/4/1/318/1/1/1/11/2/15
  • /ISO/3/6/1/4/1/318/1/1/1/11/2/15
Named path variants
  • /iso/identified-organization/dod/internet/private/enterprise/apc/products/hardware/ups/upsState/upsAdvState/upsAdvStateGalaxyVseriesSpecificFault
  • /iso/identified-organization/dod/internet/private/enterprise/PDU/products/hardware/ups/upsState/upsAdvState/upsAdvStateGalaxyVseriesSpecificFault
  • /iso/identified-organization/dod/internet/private/enterprises/apc/products/hardware/ups/upsState/upsAdvState/upsAdvStateGalaxyVseriesSpecificFault
  • /iso/identified-organization/dod/internet/private/enterprises/PDU/products/hardware/ups/upsState/upsAdvState/upsAdvStateGalaxyVseriesSpecificFault
  • /iso/identified-organization/dod/internet/private/ldap-enterprise/apc/products/hardware/ups/upsState/upsAdvState/upsAdvStateGalaxyVseriesSpecificFault
  • /iso/identified-organization/dod/internet/private/ldap-enterprise/PDU/products/hardware/ups/upsState/upsAdvState/upsAdvStateGalaxyVseriesSpecificFault
  • /iso/identified-organization/dod/internet/private/vendor-objects/apc/products/hardware/ups/upsState/upsAdvState/upsAdvStateGalaxyVseriesSpecificFault
  • /iso/identified-organization/dod/internet/private/vendor-objects/PDU/products/hardware/ups/upsState/upsAdvState/upsAdvStateGalaxyVseriesSpecificFault
  • /iso/org/dod/internet/private/enterprise/apc/products/hardware/ups/upsState/upsAdvState/upsAdvStateGalaxyVseriesSpecificFault
  • /iso/org/dod/internet/private/enterprise/PDU/products/hardware/ups/upsState/upsAdvState/upsAdvStateGalaxyVseriesSpecificFault
  • /iso/org/dod/internet/private/enterprises/apc/products/hardware/ups/upsState/upsAdvState/upsAdvStateGalaxyVseriesSpecificFault
  • /iso/org/dod/internet/private/enterprises/PDU/products/hardware/ups/upsState/upsAdvState/upsAdvStateGalaxyVseriesSpecificFault
  • /iso/org/dod/internet/private/ldap-enterprise/apc/products/hardware/ups/upsState/upsAdvState/upsAdvStateGalaxyVseriesSpecificFault
  • /iso/org/dod/internet/private/ldap-enterprise/PDU/products/hardware/ups/upsState/upsAdvState/upsAdvStateGalaxyVseriesSpecificFault
  • /iso/org/dod/internet/private/vendor-objects/apc/products/hardware/ups/upsState/upsAdvState/upsAdvStateGalaxyVseriesSpecificFault
  • /iso/org/dod/internet/private/vendor-objects/PDU/products/hardware/ups/upsState/upsAdvState/upsAdvStateGalaxyVseriesSpecificFault
  • Additional combinations skipped.

Descriptions

upsAdvStateGalaxyVseriesSpecificFault — Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community)

An ASCII string containing 32 flags representing current active faults on a Galaxy V series UPS. The upsAdvStateAbnormalConditions OID shall be used to report active faults as per its description. Additional fault information shall be provided through the upsAdvStateGalaxyVseriesSpecificFault OID. If the Network Card is unable to determine the values of the flags, this variable is set to 'UNKNOWN'. If this variable is not supported by the connected UPS, this variable is set to 'NOT SUPPORTED'. The flags are numbered from 1 to 32, and read from left to right. The flags are defined as follows: Flag 1: Input voltage is out of tolerance Flag 2: Input frequency is out of tolerance Flag 3: External sync frequency is out of tolerance Flag 4: Output frequency is out of tolerance Flag 5: The static bypass switch needs a technical check but is still fully operational Flag 6: Static bypass switch is inoperable. UPS is prevented from going into static bypass operation Flag 7: PBUS cable 1 may be damaged Flag 8: PBUS cable 2 may be damaged Flag 9: The parallel system is not configured correctly or is not working correctly Flag 10: The UC in the controller box is not working correctly Flag 11: Power module surveillance detected a fault Flag 12: The SLC in the controller box is not working correctly Flag 13: No SBS present Flag 14: No power module(s) present Flag 15: Controller box disabled Flag 16: Display communication lost - disconnected Flag 17: The energy storage surveillance has detected a battery temperature above shutdown limit Flag 18: Modular battery cabinet fuse blown Flag 19: Battery module temperature sensor not working correctly Flag 20: The energy storage surveillance has detected a battery discharge current above shutdown limit Flag 21: Ground fault detected Flag 22: External energy storage monitoring: Minor alarm Flag 23: External energy storage monitoring: Major alarm Flag 24: Temperature of input and/or output transformer is too high Flag 25: Parallel breaker status inconsistency detected Flag 26: UC communication lost - disconnected Flag 27: PMC communication lost - disconnected Flag 28: NMC communication lost - disconnected Flag 29: BMC communication lost - disconnected Flag 30: <Reserved> Flag 31: <Reserved> Flag 32: <Reserved>

Source records

upsAdvStateGalaxyVseriesSpecificFault

Status in source: optional.

Names: upsAdvStateGalaxyVseriesSpecificFault

Technical details
{
  "smi_kind": "OBJECT-TYPE",
  "definition": [
    "upsAdvStateGalaxyVseriesSpecificFault",
    "OBJECT-TYPE",
    "SYNTAX",
    "DisplayString",
    "ACCESS",
    "read-only",
    "STATUS",
    "optional",
    "DESCRIPTION",
    "\"An ASCII string containing 32 flags representing current active faults on a Galaxy V series UPS. The upsAdvStateAbnormalConditions OID shall be used to report active faults as per its description. Additional fault information shall be provided through the upsAdvStateGalaxyVseriesSpecificFault OID. If the Network Card is unable to determine the values of the flags, this variable is set to 'UNKNOWN'. If this variable is not supported by the connected UPS, this variable is set to 'NOT SUPPORTED'. The flags are numbered from 1 to 32, and read from left to right. The flags are defined as follows: Flag 1: Input voltage is out of tolerance Flag 2: Input frequency is out of tolerance Flag 3: External sync frequency is out of tolerance Flag 4: Output frequency is out of tolerance Flag 5: The static bypass switch needs a technical check but is still fully operational Flag 6: Static bypass switch is inoperable. UPS is prevented from going into static bypass operation Flag 7: PBUS cable 1 may be damaged Flag 8: PBUS cable 2 may be damaged Flag 9: The parallel system is not configured correctly or is not working correctly Flag 10: The UC in the controller box is not working correctly Flag 11: Power module surveillance detected a fault Flag 12: The SLC in the controller box is not working correctly Flag 13: No SBS present Flag 14: No power module(s) present Flag 15: Controller box disabled Flag 16: Display communication lost - disconnected Flag 17: The energy storage surveillance has detected a battery temperature above shutdown limit Flag 18: Modular battery cabinet fuse blown Flag 19: Battery module temperature sensor not working correctly Flag 20: The energy storage surveillance has detected a battery discharge current above shutdown limit Flag 21: Ground fault detected Flag 22: External energy storage monitoring: Minor alarm Flag 23: External energy storage monitoring: Major alarm Flag 24: Temperature of input and/or output transformer is too high Flag 25: Parallel breaker status inconsistency detected Flag 26: UC communication lost - disconnected Flag 27: PMC communication lost - disconnected Flag 28: NMC communication lost - disconnected Flag 29: BMC communication lost - disconnected Flag 30: <Reserved> Flag 31: <Reserved> Flag 32: <Reserved>\"",
    "::=",
    "{",
    "upsAdvState",
    "15",
    "}"
  ],
  "syntax_tree": [
    [
      "row",
      "DisplayString"
    ],
    null,
    [
      "MaxAccessPart",
      "read-only"
    ],
    [
      "Status",
      "optional"
    ],
    [
      "DESCRIPTION",
      "An ASCII string containing 32 flags representing current active faults on a Galaxy V series UPS. The upsAdvStateAbnormalConditions OID shall be used to report active faults as per its description. Additional fault information shall be provided through the upsAdvStateGalaxyVseriesSpecificFault OID. If the Network Card is unable to determine the values of the flags, this variable is set to 'UNKNOWN'. If this variable is not supported by the connected UPS, this variable is set to 'NOT SUPPORTED'. The flags are numbered from 1 to 32, and read from left to right. The flags are defined as follows: Flag 1: Input voltage is out of tolerance Flag 2: Input frequency is out of tolerance Flag 3: External sync frequency is out of tolerance Flag 4: Output frequency is out of tolerance Flag 5: The static bypass switch needs a technical check but is still fully operational Flag 6: Static bypass switch is inoperable. UPS is prevented from going into static bypass operation Flag 7: PBUS cable 1 may be damaged Flag 8: PBUS cable 2 may be damaged Flag 9: The parallel system is not configured correctly or is not working correctly Flag 10: The UC in the controller box is not working correctly Flag 11: Power module surveillance detected a fault Flag 12: The SLC in the controller box is not working correctly Flag 13: No SBS present Flag 14: No power module(s) present Flag 15: Controller box disabled Flag 16: Display communication lost - disconnected Flag 17: The energy storage surveillance has detected a battery temperature above shutdown limit Flag 18: Modular battery cabinet fuse blown Flag 19: Battery module temperature sensor not working correctly Flag 20: The energy storage surveillance has detected a battery discharge current above shutdown limit Flag 21: Ground fault detected Flag 22: External energy storage monitoring: Minor alarm Flag 23: External energy storage monitoring: Major alarm Flag 24: Temperature of input and/or output transformer is too high Flag 25: Parallel breaker status inconsistency detected Flag 26: UC communication lost - disconnected Flag 27: PMC communication lost - disconnected Flag 28: NMC communication lost - disconnected Flag 29: BMC communication lost - disconnected Flag 30: <Reserved> Flag 31: <Reserved> Flag 32: <Reserved>"
    ],
    null,
    null,
    null,
    null
  ]
}
  • Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community) · Publisher's source file: PowerNet-MIB

    Vendor MIB copy from the LibreNMS archive.

    Module: PowerNet-MIB

    Published definition
    upsAdvStateGalaxyVseriesSpecificFault OBJECT-TYPE
       SYNTAX DisplayString
       ACCESS read-only
       STATUS optional
       DESCRIPTION
            "An ASCII string containing 32 flags representing
            current active faults on a Galaxy V series UPS.
            The upsAdvStateAbnormalConditions OID shall be used to report
            active faults as per its description. Additional fault information
            shall be provided through the upsAdvStateGalaxyVseriesSpecificFault OID.
            If the Network Card is unable to determine the values of the flags, this
            variable is set to 'UNKNOWN'. If this variable is not
            supported by the connected UPS, this variable is set to
            'NOT SUPPORTED'.
    
            The flags are numbered from 1 to 32, and read from left to
            right. The flags are defined as follows:
    
            Flag  1: Input voltage is out of tolerance
            Flag  2: Input frequency is out of tolerance
            Flag  3: External sync frequency is out of tolerance
            Flag  4: Output frequency is out of tolerance
    
            Flag  5: The static bypass switch needs a technical check but is still fully operational
            Flag  6: Static bypass switch is inoperable. UPS is prevented from going into static bypass operation
            Flag  7: PBUS cable 1 may be damaged
            Flag  8: PBUS cable 2 may be damaged
    
            Flag  9: The parallel system is not configured correctly or is not working correctly
            Flag 10: The UC in the controller box is not working correctly
            Flag 11: Power module surveillance detected a fault
            Flag 12: The SLC in the controller box is not working correctly
    
            Flag 13: No SBS present
            Flag 14: No power module(s) present
            Flag 15: Controller box disabled
            Flag 16: Display communication lost - disconnected
    
            Flag 17: The energy storage surveillance has detected a battery temperature above shutdown limit
            Flag 18: Modular battery cabinet fuse blown
            Flag 19: Battery module temperature sensor not working correctly
            Flag 20: The energy storage surveillance has detected a battery discharge current above shutdown limit
    
            Flag 21: Ground fault detected
            Flag 22: External energy storage monitoring: Minor alarm
            Flag 23: External energy storage monitoring: Major alarm
            Flag 24: Temperature of input and/or output transformer is too high
    
            Flag 25: Parallel breaker status inconsistency detected
            Flag 26: UC communication lost - disconnected
            Flag 27: PMC communication lost - disconnected
            Flag 28: NMC communication lost - disconnected
    
            Flag 29: BMC communication lost - disconnected
            Flag 30: <Reserved>
            Flag 31: <Reserved>
            Flag 32: <Reserved>"
       ::= { upsAdvState 15 }
    Module imports
    {'RFC-1212': ['OBJECT-TYPE'], 'RFC-1215': ['TRAP-TYPE'], 'RFC1155-SMI': ['enterprises', 'IpAddress', 'Gauge', 'TimeTicks'], 'RFC1213-MIB': ['DisplayString'], 'SNMP-FRAMEWORK-MIB': ['SnmpAdminString']}

    Related source files and packages:


    Source location: PowerNet-MIB::upsAdvStateGalaxyVseriesSpecificFault.
    Source version and references

    Downloaded: 2026-10-24T02:14:13.503326+00:00.

  • Multiple manufacturers; see the original MIB MIB copies (LibreNMS/Observium Community) · Publisher's source file: Source package: observium-community-latest.tar.gz

    Vendor MIB copy from the Observium Community archive.

    Module: PowerNet-MIB

    Published definition
    upsAdvStateGalaxyVseriesSpecificFault OBJECT-TYPE
       SYNTAX DisplayString
       ACCESS read-only
       STATUS optional
       DESCRIPTION
            "An ASCII string containing 32 flags representing
            current active faults on a Galaxy V series UPS.
            The upsAdvStateAbnormalConditions OID shall be used to report
            active faults as per its description. Additional fault information
            shall be provided through the upsAdvStateGalaxyVseriesSpecificFault OID.
            If the Network Card is unable to determine the values of the flags, this
            variable is set to 'UNKNOWN'. If this variable is not
            supported by the connected UPS, this variable is set to
            'NOT SUPPORTED'.
    
            The flags are numbered from 1 to 32, and read from left to
            right. The flags are defined as follows:
    
            Flag  1: Input voltage is out of tolerance
            Flag  2: Input frequency is out of tolerance
            Flag  3: External sync frequency is out of tolerance
            Flag  4: Output frequency is out of tolerance
    
            Flag  5: The static bypass switch needs a technical check but is still fully operational
            Flag  6: Static bypass switch is inoperable. UPS is prevented from going into static bypass operation
            Flag  7: PBUS cable 1 may be damaged
            Flag  8: PBUS cable 2 may be damaged
    
            Flag  9: The parallel system is not configured correctly or is not working correctly
            Flag 10: The UC in the controller box is not working correctly
            Flag 11: Power module surveillance detected a fault
            Flag 12: The SLC in the controller box is not working correctly
    
            Flag 13: No SBS present
            Flag 14: No power module(s) present
            Flag 15: Controller box disabled
            Flag 16: Display communication lost - disconnected
    
            Flag 17: The energy storage surveillance has detected a battery temperature above shutdown limit
            Flag 18: Modular battery cabinet fuse blown
            Flag 19: Battery module temperature sensor not working correctly
            Flag 20: The energy storage surveillance has detected a battery discharge current above shutdown limit
    
            Flag 21: Ground fault detected
            Flag 22: External energy storage monitoring: Minor alarm
            Flag 23: External energy storage monitoring: Major alarm
            Flag 24: Temperature of input and/or output transformer is too high
    
            Flag 25: Parallel breaker status inconsistency detected
            Flag 26: UC communication lost - disconnected
            Flag 27: PMC communication lost - disconnected
            Flag 28: NMC communication lost - disconnected
    
            Flag 29: BMC communication lost - disconnected
            Flag 30: <Reserved>
            Flag 31: <Reserved>
            Flag 32: <Reserved>"
       ::= { upsAdvState 15 }
    Module imports
    {'RFC-1212': ['OBJECT-TYPE'], 'RFC-1215': ['TRAP-TYPE'], 'RFC1155-SMI': ['enterprises', 'IpAddress', 'Gauge', 'TimeTicks'], 'RFC1213-MIB': ['DisplayString'], 'SNMP-FRAMEWORK-MIB': ['SnmpAdminString']}

    Related source files and packages:


    Source location: PowerNet-MIB::upsAdvStateGalaxyVseriesSpecificFault.
    Source version and references

    Downloaded: 2026-10-24T02:14:28.042136+00:00.

First Registration Authority (inferred from ancestor 1.3.6.1.4.1.318)

Yoest Peter C.

Siblings (15)

OIDNameDirect childrenDescendantsDescription
1.3.6.1.4.1.318.1.1.1.11.2.1 upsAdvStateAbnormalConditions11 An ASCII string containing the 32 flags representing the current active UPS faults. If the Network Card is unable to determine …
1.3.6.1.4.1.318.1.1.1.11.2.2 upsAdvStateSymmetra3PhaseSpecificFaults11 An ASCII string containing the 64 flags representing the current active UPS specific faults for the Symmetra 3-Phase UPS models…
1.3.6.1.4.1.318.1.1.1.11.2.3 upsAdvStateDP300ESpecificFaults11 An ASCII string containing the 64 flags representing the current active UPS specific faults for the Silcon DP300E UPS models. I…
1.3.6.1.4.1.318.1.1.1.11.2.4 upsAdvStateSymmetraSpecificFaults11 An ASCII string containing the 64 flags representing the current active UPS specific faults for the Symmetra UPS models. If the…
1.3.6.1.4.1.318.1.1.1.11.2.5 upsAdvStateSmartUPSSpecificFaults11 An ASCII string containing the 64 flags representing the current active UPS specific faults for the Smart-UPS UPS models. If th…
1.3.6.1.4.1.318.1.1.1.11.2.6 upsAdvStateSystemMessages11 An ASCII string containing the 3 digit Decimal code
representing the current active message from the
System Message Register. Eac…
1.3.6.1.4.1.318.1.1.1.11.2.7 upsAdvStateTotaltimeonbattery00 Total time the UPS has been in battery operation.
1.3.6.1.4.1.318.1.1.1.11.2.8 upsAdvStateTotaltimeonbypass00 Total time the UPS has been in bypass operation.
1.3.6.1.4.1.318.1.1.1.11.2.9 upsAdvStateTotaltimeonNormal00 Total time the UPS has been in normal operation.
1.3.6.1.4.1.318.1.1.1.11.2.10 upsAdvStateNumberoftimesonbattery00 Number of times the UPS was on battery.
Since the last reset of statistical data.
1.3.6.1.4.1.318.1.1.1.11.2.11 upsAdvStateNumberoftimesbypass00 Number of times the UPS was in bypass.
Since the last reset of statistical data.
1.3.6.1.4.1.318.1.1.1.11.2.12 upsAdvStateNumberoftimesNormal00 Number of times the UPS was in normal operation.
Since the last reset of statistical data.
1.3.6.1.4.1.318.1.1.1.11.2.13 upsAdvStateEcomode00 Eco mode status.
1: UPS is on Eco-mode
2: UPS is not on Eco-mode.
1.3.6.1.4.1.318.1.1.1.11.2.14 upsAdvStateLifeCycleManagement00
1.3.6.1.4.1.318.1.1.1.11.2.16 upsAdvStateGutorModularSpecificFaults00