The amount of delay, measured in seconds, between
when power is provided to the Rack PDU and when
the Rack PDU provides basic master power to the
outlets.
Allowed values are:
-1 - never apply power automatically.
0 - apply power immediately.
1 to 300 - delay up to 300 seconds (5 minutes).
Parsed from file powernet.mib.txt
Company: None
Module: PowerNet-MIB
The amount of delay, measured in seconds, between
when power is provided to the Rack PDU and when
the Rack PDU provides basic master power to the
outlets
Parsed from file PowerNet-MIB.mib
Module: PowerNet-MIB
rPDU2DeviceConfigColdstartDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The amount of delay, measured in seconds, between when power is provided to the Rack PDU and when the Rack PDU provides basic master power to the outlets. Allowed values are: -1 - never apply power automatically. 0 - apply power immediately. 1 to 300 - delay up to 300 seconds (5 minutes)." ::= { rPDU2DeviceConfigEntry 6 }
Vendor: APC
Module: PowerNet-MIB (powernet401.mib)
Type: TABULAR
Access: read-write
Syntax: INTEGER
Automatically extracted from www.mibdepot.com
rPDU2DeviceConfigColdstartDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The amount of delay, measured in seconds, between when power is provided to the Rack PDU and when the Rack PDU provides basic master power to the outlets" ::= { rPDU2DeviceConfigEntry 6 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.26.4.1.1.1 | rPDU2DeviceConfigIndex | 0 | 0 | The index to the Rack PDU table entry |
1.3.6.1.4.1.318.1.1.26.4.1.1.2 | rPDU2DeviceConfigModule | 0 | 0 | The user-defined Rack PDU numeric ID |
1.3.6.1.4.1.318.1.1.26.4.1.1.3 | rPDU2DeviceConfigName | 0 | 0 | A user-defined string identifying the Rack PDU |
1.3.6.1.4.1.318.1.1.26.4.1.1.4 | rPDU2DeviceConfigLocation | 0 | 0 | A user-defined string identifying the location of the Rack PDU |
1.3.6.1.4.1.318.1.1.26.4.1.1.5 | rPDU2DeviceConfigDisplayOrientation | 0 | 0 | Indicates the intended physical orientation of the seven segment display displayNormal(1) indicates normal orientation displayRev… |
1.3.6.1.4.1.318.1.1.26.4.1.1.7 | rPDU2DeviceConfigLowLoadPowerThreshold | 0 | 0 | User-defined low power draw alarm threshold, measured in tenths of kilowatts |
1.3.6.1.4.1.318.1.1.26.4.1.1.8 | rPDU2DeviceConfigNearOverloadPowerThreshold | 0 | 0 | User-defined near power overload threshold, measured in tenths of kilowatts |
1.3.6.1.4.1.318.1.1.26.4.1.1.9 | rPDU2DeviceConfigOverloadPowerThreshold | 0 | 0 | User-defined power overload threshold, measured in tenths of kilowatts |
1.3.6.1.4.1.318.1.1.26.4.1.1.10 | rPDU2DeviceConfigDevicePeakPowerReset | 0 | 0 | Setting this OID to reset (2) will cause the existing peak power value to be replaced by the current load power value. Getting th… |
1.3.6.1.4.1.318.1.1.26.4.1.1.11 | rPDU2DeviceConfigDeviceEnergyReset | 0 | 0 | Setting this OID to reset (2) will cause the device energy meter value to be reset to zero. Getting this OID in models that suppo… |
1.3.6.1.4.1.318.1.1.26.4.1.1.12 | rPDU2DeviceConfigOutletsEnergyReset | 0 | 0 | Setting this OID to reset (2) will cause the all outlet energy meter values to be reset to zero. Getting this OID will do nothing… |
1.3.6.1.4.1.318.1.1.26.4.1.1.13 | rPDU2DeviceConfigOutletsPeakLoadReset | 0 | 0 | Setting this OID to reset (2) will cause the all outlet peak load values to be reset to zero. Getting this OID will do nothing an… |