node name
FalconInput2State
dot oid
1.3.6.1.4.1.3184.1.1.1.3.2.1
type
OBJECT-TYPE
asn1 oid
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) RLE(3184) products(1) Falcon(1) FalconMIB(1) FalconInputs(3) FalconInput2(2) FalconInput2State(1)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) RLE(3184) products(1) Falcon(1) FalconMIB(1) FalconInputs(3) FalconInput2(2) FalconInput2State(1)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprise(1) RLE(3184) products(1) Falcon(1) FalconMIB(1) FalconInputs(3) FalconInput2(2) FalconInput2State(1)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) RLE(3184) products(1) Falcon(1) FalconMIB(1) FalconInputs(3) FalconInput2(2) FalconInput2State(1)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprise(1) RLE(3184) products(1) Falcon(1) FalconMIB(1) FalconInputs(3) FalconInput2(2) FalconInput2State(1)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprises(1) RLE(3184) products(1) Falcon(1) FalconMIB(1) FalconInputs(3) FalconInput2(2) FalconInput2State(1)}
  • iri oid
  • /iso/identified-organization/dod/internet/private/enterprise/RLE/products/Falcon/FalconMIB/FalconInputs/FalconInput2/FalconInput2State
  • /iso/identified-organization/dod/internet/private/enterprises/RLE/products/Falcon/FalconMIB/FalconInputs/FalconInput2/FalconInput2State
  • /iso/org/dod/internet/private/enterprise/RLE/products/Falcon/FalconMIB/FalconInputs/FalconInput2/FalconInput2State
  • /iso/org/dod/internet/private/enterprises/RLE/products/Falcon/FalconMIB/FalconInputs/FalconInput2/FalconInput2State
  • /iso/iso-identified-organization/dod/internet/private/enterprise/RLE/products/Falcon/FalconMIB/FalconInputs/FalconInput2/FalconInput2State
  • /iso/iso-identified-organization/dod/internet/private/enterprises/RLE/products/Falcon/FalconMIB/FalconInputs/FalconInput2/FalconInput2State
  • iri by oid_info
    /ISO/Identified-Organization/6/1/4/1/3184/1/1/1/3/2/1

    Description by mibdepot

    The state of use of Input Number 2. When a sensor is
    connected to Input 2 set State to installed(2) to
    indicate that the value of FalconReading2 is valid.
    When no sensor is connected to Input 2 set
    State to notInstalled(1) to indicate that the value of
    FalconReading2 may not be valid.
    This variable is stored in non-volatile memory.

    Parsed from file Falconmib.txt
    Company: None
    Module: RLE-FALCON-MIB

    Description by circitor

    The state of use of Input Number 2. When a sensor is
    connected to Input 2 set State to installed(2) to
    indicate that the value of falconReading2 is valid.
    When no sensor is connected to Input 2 set
    State to notInstalled(1) to indicate that the value of
    falconReading2 may not be valid.
    This variable is stored in non-volatile memory.

    Parsed from file RLE-FALCON-MIB.mib
    Module: RLE-FALCON-MIB

    Information by oid_info

    Vendor: Raymond and Lae Engineering, Inc.
    Module: RLE-FALCON-MIB

    [Automatically extracted from oidview.com]

    Information by mibdepot

    FalconInput2State OBJECT-TYPE SYNTAX INTEGER { notInstalled(1), Analog_4to20_Installed(2), Digital_NO_Installed(3), Digital_NC_Installed(4) } ACCESS read-write STATUS mandatory DESCRIPTION "The state of use of Input Number 2. When a sensor is connected to Input 2 set State to installed(2) to indicate that the value of FalconReading2 is valid. When no sensor is connected to Input 2 set State to notInstalled(1) to indicate that the value of FalconReading2 may not be valid. This variable is stored in non-volatile memory." ::= { FalconInput2 1 }

    Information by circitor

    falconInput2State OBJECT-TYPE SYNTAX INTEGER { notinstalled(1), analog-4to20-installed(2), digital-no-installed(3), digital-nc-installed(4) } ACCESS read-write STATUS mandatory DESCRIPTION "The state of use of Input Number 2. When a sensor is connected to Input 2 set State to installed(2) to indicate that the value of falconReading2 is valid. When no sensor is connected to Input 2 set State to notInstalled(1) to indicate that the value of falconReading2 may not be valid. This variable is stored in non-volatile memory." ::= { falconInput2 1 }

    First Registration Authority (recovered by parent 1.3.6.1.4.1.3184)

    Raymond Donald

    Children (1)

    OIDNameSub childrenSub Nodes TotalDescription
    1.3.6.1.4.1.3184.1.1.1.3.2.1.0 0 0 0 FalconInput2State

    Brothers (12)

    OIDNameSub childrenSub Nodes TotalDescription
    1.3.6.1.4.1.3184.1.1.1.3.2.2 FalconInput2Reading 1 1 The reading for sensor 2.
    If the input is digital, the reading will be 1 (active) or
    0 (inactive)
    1.3.6.1.4.1.3184.1.1.1.3.2.3 FalconInput2Gain 1 1 A correction gain associated with the sensor variable.
    The value of gain is multiplied by the value from
    Input Sensor Number 2 to…
    1.3.6.1.4.1.3184.1.1.1.3.2.4 FalconInput2Offset 1 1 A correction Offset associated with the sensor variable.
    The value of Offset is added to the value from
    Input Sensor Number 2 to …
    1.3.6.1.4.1.3184.1.1.1.3.2.5 FalconInput2Label 1 1 A user-defined text string associated with Input Number 2.
    The text string is stored in non-volatile memory.
    1.3.6.1.4.1.3184.1.1.1.3.2.6 FalconInput2UOM 1 1 A user-defined text string associated with Input Number 2.
    The text string is stored in non-volatile memory.
    1.3.6.1.4.1.3184.1.1.1.3.2.7 FalconInput2HighLimit2 1 1 When input 2 reaches or exceeds this value a trap will
    be generated signifying a high alarm condition at
    sensor 2.
    The HighLimit v…
    1.3.6.1.4.1.3184.1.1.1.3.2.8 FalconInput2HighLimit 1 1 When input 2 reaches or exceeds this value a trap will
    be generated signifying a high alarm condition at
    sensor 2.
    The HighLimit v…
    1.3.6.1.4.1.3184.1.1.1.3.2.9 FalconInput2LowLimit 1 1 When input 2 reaches or goes below this value a trap will
    be generated signifying a low alarm condition at sensor 2.
    The LowLimit…
    1.3.6.1.4.1.3184.1.1.1.3.2.10 FalconInput2LowLimit2 1 1 When input 2 reaches or goes below this value a trap will
    be generated signifying a low alarm condition at sensor 2.
    The LowLimit…
    1.3.6.1.4.1.3184.1.1.1.3.2.11 FalconInput2RlyControl 1 1 The control of the output relays. This is a binary
    setting with each bit representing an alarm state.
    To set K1 on a high alarm, …
    1.3.6.1.4.1.3184.1.1.1.3.2.12 FalconInput2Delay 1 1 The number of seconds an alarm for this input must
    be present before annunication. The range of this
    setting is 0..600.
    This varia…
    1.3.6.1.4.1.3184.1.1.1.3.2.13 FalconInput2Hysteresis 1 1 The value of alarm hysteresis for this input.
    The input reading must decrease or increase by this