Status in source: mandatory.
Names: saRingCplCouplingLinks
Technical details
{
"smi_kind": "OBJECT-TYPE",
"definition": [
"saRingCplCouplingLinks",
"OBJECT-TYPE",
"SYNTAX",
"INTEGER",
"{",
"basicRedundancy",
"(",
"1",
")",
",",
"extendedRedundancy",
"(",
"2",
")",
"}",
"ACCESS",
"read-write",
"STATUS",
"mandatory",
"DESCRIPTION",
"\"Maximum coupling links between two coupled rings or nets which will be in forwarding in case of a failure in one of the coupled rings or nets. If there is no connection starting from the switch in slave or local operational state over the route of the coupled rings or nets to oneself the slave or the local mode want to set the coupling port in forwarding after a timeout period. basicRedundancy(1) prevents the slave or the local mode from setting its coupling port into forwarding in case of the described failure. In this case the segment which is connected to this coupling port is unreachable until the failure is eliminated. In extendedRedundancy(2) the coupling port and the partner coupling port are allowed to be in forwarding.\"",
"::=",
"{",
"saRingCouplingEntry",
"16",
"}"
],
"syntax_tree": [
[
"SimpleSyntax",
"INTEGER",
[
"enumSpec",
[
[
"basicRedundancy",
1
],
[
"extendedRedundancy",
2
]
]
]
],
null,
[
"MaxAccessPart",
"read-write"
],
[
"Status",
"mandatory"
],
[
"DESCRIPTION",
"Maximum coupling links between two coupled rings or nets which will be in forwarding in case of a failure in one of the coupled rings or nets. If there is no connection starting from the switch in slave or local operational state over the route of the coupled rings or nets to oneself the slave or the local mode want to set the coupling port in forwarding after a timeout period. basicRedundancy(1) prevents the slave or the local mode from setting its coupling port into forwarding in case of the described failure. In this case the segment which is connected to this coupling port is unreachable until the failure is eliminated. In extendedRedundancy(2) the coupling port and the partner coupling port are allowed to be in forwarding."
],
null,
null,
null,
null
]
}
- Schneider Electric Transparent Factory official MIB
· Publisher's source file: Schneider Electric SchneiderTFE-V01-04.mib — M580 support package
Module: TFPRIVATE-MIB
See published definition above
Module imports
{'IF-MIB': ['ifIndex'], 'RFC-1212': ['OBJECT-TYPE'], 'RFC-1215': ['TRAP-TYPE'], 'BRIDGE-MIB': ['BridgeId', 'dot1dStaticAddress'], 'RFC1155-SMI': ['IpAddress', 'Counter', 'TimeTicks', 'enterprises'], 'RFC1213-MIB': ['DisplayString', 'PhysAddress', 'mib-2'], 'Q-BRIDGE-MIB': ['VlanIndex', 'dot1qVlanIndex', 'dot1qFdbId'], 'IANAifType-MIB': ['IANAifType']}
Source data warning: Official Schneider Electric MIB distributed in the M580 support package. The package contains distinct historical editions; applicability to a specific device or firmware is not established by this file alone.
· Download Schneider Electric SchneiderTFE-V01-04.mib — M580 support package
Related source files and packages: