Specifies the percent of the object database that is currently
in use. Each object created consumes memory within the object
database. This attribute can be used to help determine the
device's capacity for additional objects; however, other
performance indicators should also be assessed. This attribute
is valid on the NAE hardware and under device simulation.
Also, an attempt to create an object known to require X bytes
of object database may fail even if more than X bytes are
available in the object database. This is because the object
database is composed of multiple blocks. If the free space of
each block is fewer than X bytes, the request for X bytes will
fail even though the sum total of free space from all blocks is
greater than X bytes.
Parsed from file msea.mib.txt
Company: johnsoncontrols
Module: MSEA-MIB
objectMemoryUsage OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Specifies the percent of the object database that is currently in use. Each object created consumes memory within the object database. This attribute can be used to help determine the device's capacity for additional objects; however, other performance indicators should also be assessed. This attribute is valid on the NAE hardware and under device simulation. Also, an attempt to create an object known to require X bytes of object database may fail even if more than X bytes are available in the object database. This is because the object database is composed of multiple blocks. If the free space of each block is fewer than X bytes, the request for X bytes will fail even though the sum total of free space from all blocks is greater than X bytes." ::= { mseaDiagnostics 2582 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.4399.2.1.1.1.1.3.647 | batteryCondition | 0 | 0 | Specifies the current battery condition. It is updated every 60 seconds. |
1.3.6.1.4.1.4399.2.1.1.1.1.3.650 | covReceivesPerMinute | 0 | 0 | Specifies the number of COV messages the NAE receives from other supervisory devices or field controllers per minute. This attrib… |
1.3.6.1.4.1.4399.2.1.1.1.1.3.651 | covTransmitsPerMinute | 0 | 0 | Specifies the number of COV messages the NAE sends to other supervisory devices per minute. This attribute updates every minute. … |
1.3.6.1.4.1.4399.2.1.1.1.1.3.844 | objectCount | 0 | 0 | Indicates the number (count) of all the object instances within the device. Objects of all classes are included. |
1.3.6.1.4.1.4399.2.1.1.1.1.3.2395 | estimatedFlashAvailable | 0 | 0 | Specifies the estimated flash memory available within the device for use by the user's database and applications. This value can … |
1.3.6.1.4.1.4399.2.1.1.1.1.3.2579 | cpuTemperature | 0 | 0 | Specifies the current CPU (Central Processing Unit) temperature in degrees Celsius for an NAE45-0/NAE55/NIE55. It is updated ever… |
1.3.6.1.4.1.4399.2.1.1.1.1.3.2580 | boardTemperature | 0 | 0 | Specifies the current Printed Wiring Board (PWB) temperature in degrees Celsius. It is updated every 60 seconds. It is obtained f… |
1.3.6.1.4.1.4399.2.1.1.1.1.3.2581 | memoryUsage | 0 | 0 | Specifies the percent of system RAM that is currently in use. |
1.3.6.1.4.1.4399.2.1.1.1.1.3.2583 | cpuUsage | 0 | 0 | Specifies a running average of CPU utilization over the last 50 minutes. The value is updated every 30 seconds. The running avera… |
1.3.6.1.4.1.4399.2.1.1.1.1.3.2584 | flashUsage | 0 | 0 | Specifies the estimated percent of flash memory currently in use. The percentage is based on the portion of flash that is designa… |
1.3.6.1.4.1.4399.2.1.1.1.1.3.32565 | pagerDialStatus | 0 | 0 | Specifies the current status of the pager dial-up connection |