Reference record for OID 1.3.6.1.4.1.318.1.1.1.11.2.1



parent
1.3.6.1.4.1.318.1.1.1.11.2 (upsAdvState)
node code
1
node name
upsAdvStateAbnormalConditions
dot oid
1.3.6.1.4.1.318.1.1.1.11.2.1
type
OBJECT-TYPE
asn1 oid
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateAbnormalConditions(1)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateAbnormalConditions(1)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateAbnormalConditions(1)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateAbnormalConditions(1)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateAbnormalConditions(1)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateAbnormalConditions(1)}
  • iri oid
  • /iso/identified-organization/dod/internet/private/enterprise/apc/products/hardware/ups/upsState/upsAdvState/upsAdvStateAbnormalConditions
  • /iso/identified-organization/dod/internet/private/enterprises/apc/products/hardware/ups/upsState/upsAdvState/upsAdvStateAbnormalConditions
  • /iso/org/dod/internet/private/enterprise/apc/products/hardware/ups/upsState/upsAdvState/upsAdvStateAbnormalConditions
  • /iso/org/dod/internet/private/enterprises/apc/products/hardware/ups/upsState/upsAdvState/upsAdvStateAbnormalConditions
  • /iso/iso-identified-organization/dod/internet/private/enterprise/apc/products/hardware/ups/upsState/upsAdvState/upsAdvStateAbnormalConditions
  • /iso/iso-identified-organization/dod/internet/private/enterprises/apc/products/hardware/ups/upsState/upsAdvState/upsAdvStateAbnormalConditions
  • iri by oid_info
    /ISO/Identified-Organization/6/1/4/1/318/1/1/1/11/2/1

    Description by mibdepot

    An ASCII string containing the 32 flags representing
    the current active UPS faults. If the Network Card
    is unable to determine the values of the flags, this
    variable is set to 'UNKNOWN'. If this variable is not
    supported by the connected UPS, this variable is set to
    'NOT SUPPORTED'.

    The flags are numbered from 1 to 32, and read from left to
    right. The flags are defined as follows:

    Flag 1: Power Module Failure
    Flag 2: Main Intelligence Module Failure
    Flag 3: Redundant Intelligence Module Failure
    Flag 4: Battery Failure

    Flag 5: Load(kVA) Alarm Threshold Violation
    Flag 6: Redundancy Lost
    Flag 7: Redundancy Below Alarm Threshold
    Flag 8: Bypass not in Range; Either Frequency or Voltage

    Flag 9: Bypass Contactor Stuck in Bypass Condition
    Flag 10: Bypass Contactor Stuck in On-Line Condition
    Flag 11: In Bypass due to an Internal Fault
    Flag 12: In Bypass due to an Overload

    Flag 13: In Maintenance Bypass
    Flag 14: Input Circuit Braker Tripped Open
    Flag 15: System Level Fan Failure
    Flag 16: Redundant Intelligent Module in Control

    Flag 17: IIC Inter-Module Communication Failure
    Flag 18: No Working Power Modules
    Flag 19: Load Shutdown From Bypass; Input Frequency
    Flag 20: Runtime Below Alarm Threshold

    Flag 21: Extended Run Frame Fault
    Flag 22: Output Voltage out of Range
    Flag 23: UPS Not Synchronized
    Flag 24: No Batteries Installed

    Flag 25: Battery Voltage High
    Flag 26: UPS Specific Fault Detected
    Flag 27: Site Wiring Fault
    Flag 28: Backfeed Protection Relay Opened

    Flag 29:
    Flag 30:
    Flag 31:
    Flag 32:

    Parsed from file powernet.mib.txt
    Company: None
    Module: PowerNet-MIB

    Description by circitor

    An ASCII string containing the 32 flags representing
    the current active UPS faults. If the Network Card
    is unable to determine the values of the flags, this
    variable is set to 'UNKNOWN'. If this variable is not
    supported by the connected UPS, this variable is set to
    'NOT SUPPORTED'.

    The flags are numbered from 1 to 32, and read from left to
    right. The flags are defined as follows:

    Flag 1: Power Module Failure
    Flag 2: Main Intelligence Module Failure
    Flag 3: Redundant Intelligence Module Failure
    Flag 4: Battery Failure

    Flag 5: Load(kVA) Alarm Threshold Violation
    Flag 6: Redundancy Lost
    Flag 7: Redundancy Below Alarm Threshold
    Flag 8: Bypass not in Range; Either Frequency or Voltage

    Flag 9: Bypass Contactor Stuck in Bypass Condition
    Flag 10: Bypass Contactor Stuck in On-Line Condition
    Flag 11: In Bypass due to an Internal Fault
    Flag 12: In Bypass due to an Overload

    Flag 13: In Maintenance Bypass
    Flag 14: Input Circuit Braker Tripped Open
    Flag 15: System Level Fan Failure
    Flag 16: Redundant Intelligent Module in Control

    Flag 17: IIC Inter-Module Communication Failure
    Flag 18: No Working Power Modules
    Flag 19: Load Shutdown From Bypass; Input Frequency
    Flag 20: Runtime Below Alarm Threshold

    Flag 21: Extended Run Frame Fault
    Flag 22: Output Voltage out of Range
    Flag 23: UPS Not Synchronized
    Flag 24: No Batteries Installed

    Flag 25: Battery Voltage High
    Flag 26: UPS Specific Fault Detected
    Flag 27: Site Wiring Fault
    Flag 28: Backfeed Protection Relay Opened

    Flag 29:
    Flag 30:
    Flag 31:
    Flag 32:

    Parsed from file PowerNet-MIB.mib
    Module: PowerNet-MIB

    Information by mibdepot

    upsAdvStateAbnormalConditions OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "An ASCII string containing the 32 flags representing the current active UPS faults. If the Network Card is unable to determine the values of the flags, this variable is set to 'UNKNOWN'. If this variable is not supported by the connected UPS, this variable is set to 'NOT SUPPORTED'. The flags are numbered from 1 to 32, and read from left to right. The flags are defined as follows: Flag 1: Power Module Failure Flag 2: Main Intelligence Module Failure Flag 3: Redundant Intelligence Module Failure Flag 4: Battery Failure Flag 5: Load(kVA) Alarm Threshold Violation Flag 6: Redundancy Lost Flag 7: Redundancy Below Alarm Threshold Flag 8: Bypass not in Range; Either Frequency or Voltage Flag 9: Bypass Contactor Stuck in Bypass Condition Flag 10: Bypass Contactor Stuck in On-Line Condition Flag 11: In Bypass due to an Internal Fault Flag 12: In Bypass due to an Overload Flag 13: In Maintenance Bypass Flag 14: Input Circuit Braker Tripped Open Flag 15: System Level Fan Failure Flag 16: Redundant Intelligent Module in Control Flag 17: IIC Inter-Module Communication Failure Flag 18: No Working Power Modules Flag 19: Load Shutdown From Bypass; Input Frequency Flag 20: Runtime Below Alarm Threshold Flag 21: Extended Run Frame Fault Flag 22: Output Voltage out of Range Flag 23: UPS Not Synchronized Flag 24: No Batteries Installed Flag 25: Battery Voltage High Flag 26: UPS Specific Fault Detected Flag 27: Site Wiring Fault Flag 28: Backfeed Protection Relay Opened Flag 29: Flag 30: Flag 31: Flag 32: " ::= { upsAdvState 1 }

    Information by oid_info

    Vendor: American Power Conversion Corp.
    Module: PowerNet-MIB

    [Automatically extracted from oidview.com]

    Information by circitor

    upsAdvStateAbnormalConditions OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "An ASCII string containing the 32 flags representing the current active UPS faults. If the Network Card is unable to determine the values of the flags, this variable is set to 'UNKNOWN'. If this variable is not supported by the connected UPS, this variable is set to 'NOT SUPPORTED'. The flags are numbered from 1 to 32, and read from left to right. The flags are defined as follows: Flag 1: Power Module Failure Flag 2: Main Intelligence Module Failure Flag 3: Redundant Intelligence Module Failure Flag 4: Battery Failure Flag 5: Load(kVA) Alarm Threshold Violation Flag 6: Redundancy Lost Flag 7: Redundancy Below Alarm Threshold Flag 8: Bypass not in Range; Either Frequency or Voltage Flag 9: Bypass Contactor Stuck in Bypass Condition Flag 10: Bypass Contactor Stuck in On-Line Condition Flag 11: In Bypass due to an Internal Fault Flag 12: In Bypass due to an Overload Flag 13: In Maintenance Bypass Flag 14: Input Circuit Braker Tripped Open Flag 15: System Level Fan Failure Flag 16: Redundant Intelligent Module in Control Flag 17: IIC Inter-Module Communication Failure Flag 18: No Working Power Modules Flag 19: Load Shutdown From Bypass; Input Frequency Flag 20: Runtime Below Alarm Threshold Flag 21: Extended Run Frame Fault Flag 22: Output Voltage out of Range Flag 23: UPS Not Synchronized Flag 24: No Batteries Installed Flag 25: Battery Voltage High Flag 26: UPS Specific Fault Detected Flag 27: Site Wiring Fault Flag 28: Backfeed Protection Relay Opened Flag 29: Flag 30: Flag 31: Flag 32: " ::= { upsAdvState 1 }

    First Registration Authority (recovered by parent 1.3.6.1.4.1.318)

    Yoest Peter C.

    Children (1)

    OIDNameSub childrenSub Nodes TotalDescription
    1.3.6.1.4.1.318.1.1.1.11.2.1.0 upsAdvStateAbnormalConditions 0 0 None

    Brothers (12)

    OIDNameSub childrenSub Nodes TotalDescription
    1.3.6.1.4.1.318.1.1.1.11.2.2 upsAdvStateSymmetra3PhaseSpecificFaults 1 1 An ASCII string containing the 64 flags representing
    the current active UPS specific faults for the Symmetra
    3-Phase UPS models. …
    1.3.6.1.4.1.318.1.1.1.11.2.3 upsAdvStateDP300ESpecificFaults 1 1 An ASCII string containing the 64 flags representing
    the current active UPS specific faults for the Silcon
    DP300E UPS models. If …
    1.3.6.1.4.1.318.1.1.1.11.2.4 upsAdvStateSymmetraSpecificFaults 1 1 An ASCII string containing the 64 flags representing
    the current active UPS specific faults for the Symmetra
    UPS models. If the N…
    1.3.6.1.4.1.318.1.1.1.11.2.5 upsAdvStateSmartUPSSpecificFaults 1 1 An ASCII string containing the 64 flags representing
    the current active UPS specific faults for the Smart-UPS
    UPS models. If the …
    1.3.6.1.4.1.318.1.1.1.11.2.6 upsAdvStateSystemMessages 1 1 An ASCII string containing the 3 digit Decimal code
    representing the current active message from the
    System Message Register. Eac…
    1.3.6.1.4.1.318.1.1.1.11.2.7 upsAdvStateTotaltimeonbattery 0 0 Total time the UPS has been in battery operation.
    1.3.6.1.4.1.318.1.1.1.11.2.8 upsAdvStateTotaltimeonbypass 0 0 Total time the UPS has been in bypass operation.
    1.3.6.1.4.1.318.1.1.1.11.2.9 upsAdvStateTotaltimeonNormal 0 0 Total time the UPS has been in normal operation.
    1.3.6.1.4.1.318.1.1.1.11.2.10 upsAdvStateNumberoftimesonbattery 0 0 Number of times the UPS was on battery.
    Since the last reset of statistical data.
    1.3.6.1.4.1.318.1.1.1.11.2.11 upsAdvStateNumberoftimesbypass 0 0 Number of times the UPS was in bypass.
    Since the last reset of statistical data.
    1.3.6.1.4.1.318.1.1.1.11.2.12 upsAdvStateNumberoftimesNormal 0 0 Number of times the UPS was in normal operation.
    Since the last reset of statistical data.
    1.3.6.1.4.1.318.1.1.1.11.2.13 upsAdvStateEcomode 0 0 Eco mode status.
    1: UPS is on Eco-mode
    2: UPS is not on Eco-mode.