An ASCII string containing the 32 flags representing
the current active UPS faults. If the Network Card
is unable to determine the values of the flags, this
variable is set to 'UNKNOWN'. If this variable is not
supported by the connected UPS, this variable is set to
'NOT SUPPORTED'.
The flags are numbered from 1 to 32, and read from left to
right. The flags are defined as follows:
Flag 1: Power Module Failure
Flag 2: Main Intelligence Module Failure
Flag 3: Redundant Intelligence Module Failure
Flag 4: Battery Failure
Flag 5: Load(kVA) Alarm Threshold Violation
Flag 6: Redundancy Lost
Flag 7: Redundancy Below Alarm Threshold
Flag 8: Bypass not in Range; Either Frequency or Voltage
Flag 9: Bypass Contactor Stuck in Bypass Condition
Flag 10: Bypass Contactor Stuck in On-Line Condition
Flag 11: In Bypass due to an Internal Fault
Flag 12: In Bypass due to an Overload
Flag 13: In Maintenance Bypass
Flag 14: Input Circuit Braker Tripped Open
Flag 15: System Level Fan Failure
Flag 16: Redundant Intelligent Module in Control
Flag 17: IIC Inter-Module Communication Failure
Flag 18: No Working Power Modules
Flag 19: Load Shutdown From Bypass; Input Frequency
Flag 20: Runtime Below Alarm Threshold
Flag 21: Extended Run Frame Fault
Flag 22: Output Voltage out of Range
Flag 23: UPS Not Synchronized
Flag 24: No Batteries Installed
Flag 25: Battery Voltage High
Flag 26: UPS Specific Fault Detected
Flag 27: Site Wiring Fault
Flag 28: Backfeed Protection Relay Opened
Flag 29:
Flag 30:
Flag 31:
Flag 32:
Parsed from file powernet.mib.txt
Company: None
Module: PowerNet-MIB
An ASCII string containing the 32 flags representing
the current active UPS faults. If the Network Card
is unable to determine the values of the flags, this
variable is set to 'UNKNOWN'. If this variable is not
supported by the connected UPS, this variable is set to
'NOT SUPPORTED'.
The flags are numbered from 1 to 32, and read from left to
right. The flags are defined as follows:
Flag 1: Power Module Failure
Flag 2: Main Intelligence Module Failure
Flag 3: Redundant Intelligence Module Failure
Flag 4: Battery Failure
Flag 5: Load(kVA) Alarm Threshold Violation
Flag 6: Redundancy Lost
Flag 7: Redundancy Below Alarm Threshold
Flag 8: Bypass not in Range; Either Frequency or Voltage
Flag 9: Bypass Contactor Stuck in Bypass Condition
Flag 10: Bypass Contactor Stuck in On-Line Condition
Flag 11: In Bypass due to an Internal Fault
Flag 12: In Bypass due to an Overload
Flag 13: In Maintenance Bypass
Flag 14: Input Circuit Braker Tripped Open
Flag 15: System Level Fan Failure
Flag 16: Redundant Intelligent Module in Control
Flag 17: IIC Inter-Module Communication Failure
Flag 18: No Working Power Modules
Flag 19: Load Shutdown From Bypass; Input Frequency
Flag 20: Runtime Below Alarm Threshold
Flag 21: Extended Run Frame Fault
Flag 22: Output Voltage out of Range
Flag 23: UPS Not Synchronized
Flag 24: No Batteries Installed
Flag 25: Battery Voltage High
Flag 26: UPS Specific Fault Detected
Flag 27: Site Wiring Fault
Flag 28: Backfeed Protection Relay Opened
Flag 29:
Flag 30:
Flag 31:
Flag 32:
Parsed from file PowerNet-MIB.mib
Module: PowerNet-MIB
upsAdvStateAbnormalConditions OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "An ASCII string containing the 32 flags representing the current active UPS faults. If the Network Card is unable to determine the values of the flags, this variable is set to 'UNKNOWN'. If this variable is not supported by the connected UPS, this variable is set to 'NOT SUPPORTED'. The flags are numbered from 1 to 32, and read from left to right. The flags are defined as follows: Flag 1: Power Module Failure Flag 2: Main Intelligence Module Failure Flag 3: Redundant Intelligence Module Failure Flag 4: Battery Failure Flag 5: Load(kVA) Alarm Threshold Violation Flag 6: Redundancy Lost Flag 7: Redundancy Below Alarm Threshold Flag 8: Bypass not in Range; Either Frequency or Voltage Flag 9: Bypass Contactor Stuck in Bypass Condition Flag 10: Bypass Contactor Stuck in On-Line Condition Flag 11: In Bypass due to an Internal Fault Flag 12: In Bypass due to an Overload Flag 13: In Maintenance Bypass Flag 14: Input Circuit Braker Tripped Open Flag 15: System Level Fan Failure Flag 16: Redundant Intelligent Module in Control Flag 17: IIC Inter-Module Communication Failure Flag 18: No Working Power Modules Flag 19: Load Shutdown From Bypass; Input Frequency Flag 20: Runtime Below Alarm Threshold Flag 21: Extended Run Frame Fault Flag 22: Output Voltage out of Range Flag 23: UPS Not Synchronized Flag 24: No Batteries Installed Flag 25: Battery Voltage High Flag 26: UPS Specific Fault Detected Flag 27: Site Wiring Fault Flag 28: Backfeed Protection Relay Opened Flag 29:
Flag 30: Flag 31: Flag 32: " ::= { upsAdvState 1 }
Vendor: American Power Conversion Corp.
Module: PowerNet-MIB
[Automatically extracted from oidview.com]
upsAdvStateAbnormalConditions OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "An ASCII string containing the 32 flags representing the current active UPS faults. If the Network Card is unable to determine the values of the flags, this variable is set to 'UNKNOWN'. If this variable is not supported by the connected UPS, this variable is set to 'NOT SUPPORTED'. The flags are numbered from 1 to 32, and read from left to right. The flags are defined as follows: Flag 1: Power Module Failure Flag 2: Main Intelligence Module Failure Flag 3: Redundant Intelligence Module Failure Flag 4: Battery Failure Flag 5: Load(kVA) Alarm Threshold Violation Flag 6: Redundancy Lost Flag 7: Redundancy Below Alarm Threshold Flag 8: Bypass not in Range; Either Frequency or Voltage Flag 9: Bypass Contactor Stuck in Bypass Condition Flag 10: Bypass Contactor Stuck in On-Line Condition Flag 11: In Bypass due to an Internal Fault Flag 12: In Bypass due to an Overload Flag 13: In Maintenance Bypass Flag 14: Input Circuit Braker Tripped Open Flag 15: System Level Fan Failure Flag 16: Redundant Intelligent Module in Control Flag 17: IIC Inter-Module Communication Failure Flag 18: No Working Power Modules Flag 19: Load Shutdown From Bypass; Input Frequency Flag 20: Runtime Below Alarm Threshold Flag 21: Extended Run Frame Fault Flag 22: Output Voltage out of Range Flag 23: UPS Not Synchronized Flag 24: No Batteries Installed Flag 25: Battery Voltage High Flag 26: UPS Specific Fault Detected Flag 27: Site Wiring Fault Flag 28: Backfeed Protection Relay Opened Flag 29:
Flag 30: Flag 31: Flag 32: " ::= { upsAdvState 1 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.1.11.2.1.0 | upsAdvStateAbnormalConditions | 0 | 0 | None |
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.1.11.2.2 | upsAdvStateSymmetra3PhaseSpecificFaults | 1 | 1 | An ASCII string containing the 64 flags representing the current active UPS specific faults for the Symmetra 3-Phase UPS models. … |
1.3.6.1.4.1.318.1.1.1.11.2.3 | upsAdvStateDP300ESpecificFaults | 1 | 1 | An ASCII string containing the 64 flags representing the current active UPS specific faults for the Silcon DP300E UPS models. If … |
1.3.6.1.4.1.318.1.1.1.11.2.4 | upsAdvStateSymmetraSpecificFaults | 1 | 1 | An ASCII string containing the 64 flags representing the current active UPS specific faults for the Symmetra UPS models. If the N… |
1.3.6.1.4.1.318.1.1.1.11.2.5 | upsAdvStateSmartUPSSpecificFaults | 1 | 1 | An ASCII string containing the 64 flags representing the current active UPS specific faults for the Smart-UPS UPS models. If the … |
1.3.6.1.4.1.318.1.1.1.11.2.6 | upsAdvStateSystemMessages | 1 | 1 | An ASCII string containing the 3 digit Decimal code representing the current active message from the System Message Register. Eac… |
1.3.6.1.4.1.318.1.1.1.11.2.7 | upsAdvStateTotaltimeonbattery | 0 | 0 | Total time the UPS has been in battery operation. |
1.3.6.1.4.1.318.1.1.1.11.2.8 | upsAdvStateTotaltimeonbypass | 0 | 0 | Total time the UPS has been in bypass operation. |
1.3.6.1.4.1.318.1.1.1.11.2.9 | upsAdvStateTotaltimeonNormal | 0 | 0 | Total time the UPS has been in normal operation. |
1.3.6.1.4.1.318.1.1.1.11.2.10 | upsAdvStateNumberoftimesonbattery | 0 | 0 | Number of times the UPS was on battery. Since the last reset of statistical data. |
1.3.6.1.4.1.318.1.1.1.11.2.11 | upsAdvStateNumberoftimesbypass | 0 | 0 | Number of times the UPS was in bypass. Since the last reset of statistical data. |
1.3.6.1.4.1.318.1.1.1.11.2.12 | upsAdvStateNumberoftimesNormal | 0 | 0 | Number of times the UPS was in normal operation. Since the last reset of statistical data. |
1.3.6.1.4.1.318.1.1.1.11.2.13 | upsAdvStateEcomode | 0 | 0 | Eco mode status. 1: UPS is on Eco-mode 2: UPS is not on Eco-mode. |