Reference record for OID 1.3.6.1.4.1.318.1.1.1.11.2.3



parent
1.3.6.1.4.1.318.1.1.1.11.2 (upsAdvState)
node code
3
node name
upsAdvStateDP300ESpecificFaults
dot oid
1.3.6.1.4.1.318.1.1.1.11.2.3
type
OBJECT-TYPE
asn1 oid
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateDP300ESpecificFaults(3)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateDP300ESpecificFaults(3)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateDP300ESpecificFaults(3)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateDP300ESpecificFaults(3)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateDP300ESpecificFaults(3)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) ups(1) upsState(11) upsAdvState(2) upsAdvStateDP300ESpecificFaults(3)}
  • iri oid
  • /iso/identified-organization/dod/internet/private/enterprise/apc/products/hardware/ups/upsState/upsAdvState/upsAdvStateDP300ESpecificFaults
  • /iso/identified-organization/dod/internet/private/enterprises/apc/products/hardware/ups/upsState/upsAdvState/upsAdvStateDP300ESpecificFaults
  • /iso/org/dod/internet/private/enterprise/apc/products/hardware/ups/upsState/upsAdvState/upsAdvStateDP300ESpecificFaults
  • /iso/org/dod/internet/private/enterprises/apc/products/hardware/ups/upsState/upsAdvState/upsAdvStateDP300ESpecificFaults
  • /iso/iso-identified-organization/dod/internet/private/enterprise/apc/products/hardware/ups/upsState/upsAdvState/upsAdvStateDP300ESpecificFaults
  • /iso/iso-identified-organization/dod/internet/private/enterprises/apc/products/hardware/ups/upsState/upsAdvState/upsAdvStateDP300ESpecificFaults
  • iri by oid_info
    /ISO/Identified-Organization/6/1/4/1/318/1/1/1/11/2/3

    Description by mibdepot

    An ASCII string containing the 64 flags representing
    the current active UPS specific faults for the Silcon
    DP300E UPS models. If the Network Card is unable to
    determine the values of the flags, this variable is set
    to 'UNKNOWN'. If the connected UPS does not use this
    variable, it is set to 'NOT SUPPORTED'.

    The flags are numbered from 1 to 64, and read from left
    to right. The bits are defined as follows:

    Flag 1: Peak Current Limiter Active
    Flag 2: Bypass Power Supply Fault
    Flag 3: Delta Current Limiter Active
    Flag 4: Fan Fault

    Flag 5: High DC warning
    Flag 6: Inverter Voltage Error
    Flag 7: Parallel Synchronization Error
    Flag 8: Second Power Supply Fault

    Flag 9: Internal Power Supply Fault
    Flag 10:
    Flag 11:
    Flag 12:

    Flag 13:
    Flag 14: Bypass Static Switch High Temperature
    Flag 15: High Battery Temperature
    Flag 16: Battery Weak

    Flag 17:
    Flag 18: System Locked in Operation Mode
    Flag 19: RAM1 Memory Write Error
    Flag 20: Memory Write Error

    Flag 21: Communication to VQ Bypass Lost
    Flag 22: Communication to VQ Output Lost
    Flag 23: Communication to DMU Lost
    Flag 24: Communication to Controller Lost

    Flag 25: Communication to Parallel IF Lost
    Flag 26: External Shutdown Accepted
    Flag 27: DC Capacitor Charge Error
    Flag 28: Communication to VQ Mains Lost

    Flag 29: Bypass Synchronization Error
    Flag 30: Charge Error
    Flag 31: SII Aux Input Activiated
    Flag 32:

    Flag 33: Blown Inverter Fuse
    Flag 34: Blown Rectifier Fuse
    Flag 35: Auxilliary 1 Fault
    Flag 36:

    Flag 37:
    Flag 38:
    Flag 39:
    Flag 40:

    Flag 41:
    Flag 42:
    Flag 43:
    Flag 44:

    Flag 45:
    Flag 46: High Temperature Charger Magnetic
    Flag 47:
    Flag 48: Battery Monitor Warning

    Flag 49: Battery Monitor Alarm
    Flag 50:
    Flag 51:
    Flag 52:

    Flag 53: TSM 1/2/3 Temperature Shutdown
    Flag 54: Charger 0/30 Temperature Warning
    Flag 55: Charger 0/30 Temperature Shutdown
    Flag 56: High Output Voltage

    Flag 57: SSW Temperature Over 90
    Flag 58:
    Flag 59: Low Current Failure In AC Capacitors
    Flag 60:

    Flag 61: Advanced Battery Management Not Installed
    Flag 62:
    Flag 63:
    Flag 64:

    Parsed from file powernet.mib.txt
    Company: None
    Module: PowerNet-MIB

    Description by circitor

    An ASCII string containing the 64 flags representing
    the current active UPS specific faults for the Silcon
    DP300E UPS models. If the Network Card is unable to
    determine the values of the flags, this variable is set
    to 'UNKNOWN'. If the connected UPS does not use this
    variable, it is set to 'NOT SUPPORTED'.

    The flags are numbered from 1 to 64, and read from left
    to right. The bits are defined as follows:

    Flag 1: Peak Current Limiter Active
    Flag 2: Bypass Power Supply Fault
    Flag 3: Delta Current Limiter Active
    Flag 4: Fan Fault

    Flag 5: High DC warning
    Flag 6: Inverter Voltage Error
    Flag 7: Parallel Synchronization Error
    Flag 8: Second Power Supply Fault

    Flag 9: Internal Power Supply Fault
    Flag 10:
    Flag 11:
    Flag 12:

    Flag 13:
    Flag 14: Bypass Static Switch High Temperature
    Flag 15: High Battery Temperature
    Flag 16: Battery Weak

    Flag 17:
    Flag 18: System Locked in Operation Mode
    Flag 19: RAM1 Memory Write Error
    Flag 20: Memory Write Error

    Flag 21: Communication to VQ Bypass Lost
    Flag 22: Communication to VQ Output Lost
    Flag 23: Communication to DMU Lost
    Flag 24: Communication to Controller Lost

    Flag 25: Communication to Parallel IF Lost
    Flag 26: External Shutdown Accepted
    Flag 27: DC Capacitor Charge Error
    Flag 28: Communication to VQ Mains Lost

    Flag 29: Bypass Synchronization Error
    Flag 30: Charge Error
    Flag 31: SII Aux Input Activiated
    Flag 32:

    Flag 33: Blown Inverter Fuse
    Flag 34: Blown Rectifier Fuse
    Flag 35: Auxilliary 1 Fault
    Flag 36:

    Flag 37:
    Flag 38:
    Flag 39:
    Flag 40:

    Flag 41:
    Flag 42:
    Flag 43:
    Flag 44:

    Flag 45:
    Flag 46: High Temperature Charger Magnetic
    Flag 47:
    Flag 48: Battery Monitor Warning

    Flag 49: Battery Monitor Alarm
    Flag 50:
    Flag 51:
    Flag 52:

    Flag 53: TSM 1/2/3 Temperature Shutdown
    Flag 54: Charger 0/30 Temperature Warning
    Flag 55: Charger 0/30 Temperature Shutdown
    Flag 56: High Output Voltage

    Flag 57: SSW Temperature Over 90
    Flag 58:
    Flag 59: Low Current Failure In AC Capacitors
    Flag 60:

    Flag 61: Advanced Battery Management Not Installed
    Flag 62:
    Flag 63:
    Flag 64:

    Parsed from file PowerNet-MIB.mib
    Module: PowerNet-MIB

    Information by mibdepot

    upsAdvStateDP300ESpecificFaults OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "An ASCII string containing the 64 flags representing the current active UPS specific faults for the Silcon DP300E UPS models. If the Network Card is unable to determine the values of the flags, this variable is set to 'UNKNOWN'. If the connected UPS does not use this variable, it is set to 'NOT SUPPORTED'. The flags are numbered from 1 to 64, and read from left to right. The bits are defined as follows: Flag 1: Peak Current Limiter Active Flag 2: Bypass Power Supply Fault Flag 3: Delta Current Limiter Active Flag 4: Fan Fault Flag 5: High DC warning Flag 6: Inverter Voltage Error Flag 7: Parallel Synchronization Error Flag 8: Second Power Supply Fault Flag 9: Internal Power Supply Fault Flag 10: Flag 11: Flag 12: Flag 13: Flag 14: Bypass Static Switch High Temperature Flag 15: High Battery Temperature Flag 16: Battery Weak Flag 17: Flag 18: System Locked in Operation Mode Flag 19: RAM1 Memory Write Error Flag 20: Memory Write Error Flag 21: Communication to VQ Bypass Lost Flag 22: Communication to VQ Output Lost Flag 23: Communication to DMU Lost Flag 24: Communication to Controller Lost Flag 25: Communication to Parallel IF Lost Flag 26: External Shutdown Accepted Flag 27: DC Capacitor Charge Error Flag 28: Communication to VQ Mains Lost Flag 29: Bypass Synchronization Error Flag 30: Charge Error Flag 31: SII Aux Input Activiated Flag 32: Flag 33: Blown Inverter Fuse Flag 34: Blown Rectifier Fuse Flag 35: Auxilliary 1 Fault Flag 36: Flag 37: Flag 38: Flag 39: Flag 40: Flag 41: Flag 42: Flag 43: Flag 44: Flag 45: Flag 46: High Temperature Charger Magnetic Flag 47: Flag 48: Battery Monitor Warning Flag 49: Battery Monitor Alarm Flag 50: Flag 51: Flag 52: Flag 53: TSM 1/2/3 Temperature Shutdown Flag 54: Charger 0/30 Temperature Warning Flag 55: Charger 0/30 Temperature Shutdown Flag 56: High Output Voltage Flag 57: SSW Temperature Over 90 Flag 58: Flag 59: Low Current Failure In AC Capacitors Flag 60: Flag 61: Advanced Battery Management Not Installed Flag 62: Flag 63: Flag 64: " ::= { upsAdvState 3 }

    Information by oid_info

    Vendor: American Power Conversion Corp.
    Module: PowerNet-MIB

    [Automatically extracted from oidview.com]

    Information by circitor

    upsAdvStateDP300ESpecificFaults OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "An ASCII string containing the 64 flags representing the current active UPS specific faults for the Silcon DP300E UPS models. If the Network Card is unable to determine the values of the flags, this variable is set to 'UNKNOWN'. If the connected UPS does not use this variable, it is set to 'NOT SUPPORTED'. The flags are numbered from 1 to 64, and read from left to right. The bits are defined as follows: Flag 1: Peak Current Limiter Active Flag 2: Bypass Power Supply Fault Flag 3: Delta Current Limiter Active Flag 4: Fan Fault Flag 5: High DC warning Flag 6: Inverter Voltage Error Flag 7: Parallel Synchronization Error Flag 8: Second Power Supply Fault Flag 9: Internal Power Supply Fault Flag 10: Flag 11: Flag 12: Flag 13: Flag 14: Bypass Static Switch High Temperature Flag 15: High Battery Temperature Flag 16: Battery Weak Flag 17: Flag 18: System Locked in Operation Mode Flag 19: RAM1 Memory Write Error Flag 20: Memory Write Error Flag 21: Communication to VQ Bypass Lost Flag 22: Communication to VQ Output Lost Flag 23: Communication to DMU Lost Flag 24: Communication to Controller Lost Flag 25: Communication to Parallel IF Lost Flag 26: External Shutdown Accepted Flag 27: DC Capacitor Charge Error Flag 28: Communication to VQ Mains Lost Flag 29: Bypass Synchronization Error Flag 30: Charge Error Flag 31: SII Aux Input Activiated Flag 32: Flag 33: Blown Inverter Fuse Flag 34: Blown Rectifier Fuse Flag 35: Auxilliary 1 Fault Flag 36: Flag 37: Flag 38: Flag 39: Flag 40: Flag 41: Flag 42: Flag 43: Flag 44: Flag 45: Flag 46: High Temperature Charger Magnetic Flag 47: Flag 48: Battery Monitor Warning Flag 49: Battery Monitor Alarm Flag 50: Flag 51: Flag 52: Flag 53: TSM 1/2/3 Temperature Shutdown Flag 54: Charger 0/30 Temperature Warning Flag 55: Charger 0/30 Temperature Shutdown Flag 56: High Output Voltage Flag 57: SSW Temperature Over 90 Flag 58: Flag 59: Low Current Failure In AC Capacitors Flag 60: Flag 61: Advanced Battery Management Not Installed Flag 62: Flag 63: Flag 64: " ::= { upsAdvState 3 }

    First Registration Authority (recovered by parent 1.3.6.1.4.1.318)

    Yoest Peter C.

    Children (1)

    OIDNameSub childrenSub Nodes TotalDescription
    1.3.6.1.4.1.318.1.1.1.11.2.3.0 upsAdvStateDP300ESpecificFaults 0 0 None

    Brothers (12)

    OIDNameSub childrenSub Nodes TotalDescription
    1.3.6.1.4.1.318.1.1.1.11.2.1 upsAdvStateAbnormalConditions 1 1 An ASCII string containing the 32 flags representing
    the current active UPS faults. If the Network Card
    is unable to determine th…
    1.3.6.1.4.1.318.1.1.1.11.2.2 upsAdvStateSymmetra3PhaseSpecificFaults 1 1 An ASCII string containing the 64 flags representing
    the current active UPS specific faults for the Symmetra
    3-Phase UPS models. …
    1.3.6.1.4.1.318.1.1.1.11.2.4 upsAdvStateSymmetraSpecificFaults 1 1 An ASCII string containing the 64 flags representing
    the current active UPS specific faults for the Symmetra
    UPS models. If the N…
    1.3.6.1.4.1.318.1.1.1.11.2.5 upsAdvStateSmartUPSSpecificFaults 1 1 An ASCII string containing the 64 flags representing
    the current active UPS specific faults for the Smart-UPS
    UPS models. If the …
    1.3.6.1.4.1.318.1.1.1.11.2.6 upsAdvStateSystemMessages 1 1 An ASCII string containing the 3 digit Decimal code
    representing the current active message from the
    System Message Register. Eac…
    1.3.6.1.4.1.318.1.1.1.11.2.7 upsAdvStateTotaltimeonbattery 0 0 Total time the UPS has been in battery operation.
    1.3.6.1.4.1.318.1.1.1.11.2.8 upsAdvStateTotaltimeonbypass 0 0 Total time the UPS has been in bypass operation.
    1.3.6.1.4.1.318.1.1.1.11.2.9 upsAdvStateTotaltimeonNormal 0 0 Total time the UPS has been in normal operation.
    1.3.6.1.4.1.318.1.1.1.11.2.10 upsAdvStateNumberoftimesonbattery 0 0 Number of times the UPS was on battery.
    Since the last reset of statistical data.
    1.3.6.1.4.1.318.1.1.1.11.2.11 upsAdvStateNumberoftimesbypass 0 0 Number of times the UPS was in bypass.
    Since the last reset of statistical data.
    1.3.6.1.4.1.318.1.1.1.11.2.12 upsAdvStateNumberoftimesNormal 0 0 Number of times the UPS was in normal operation.
    Since the last reset of statistical data.
    1.3.6.1.4.1.318.1.1.1.11.2.13 upsAdvStateEcomode 0 0 Eco mode status.
    1: UPS is on Eco-mode
    2: UPS is not on Eco-mode.