The temperature range that controls output when the
selected control sensor temperature is above the
setpoint. At the top of this range, the cool mode
outputs at 100%. The deadband does not apply to PID-
controlled modes. Measured in tenths of degrees
Celsius.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Parsed from file powernet.mib.txt
Company: None
Module: PowerNet-MIB
The temperature range that controls output when the
selected control sensor temperature is above the
setpoint. At the top of this range, the cool mode
outputs at 100%. The deadband does not apply to PID-
controlled modes. Measured in tenths of degrees
Celsius.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration.
Parsed from file PowerNet-MIB.mib
Module: PowerNet-MIB
airFMSysCoolDeadbandC OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The temperature range that controls output when the selected control sensor temperature is above the setpoint. At the top of this range, the cool mode outputs at 100%. The deadband does not apply to PID- controlled modes. Measured in tenths of degrees Celsius. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration." ::= { airFMSysCooling 12 }
Vendor: American Power Conversion Corp.
Module: PowerNet-MIB
[Automatically extracted from oidview.com]
airFMSysCoolDeadbandC OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The temperature range that controls output when the selected control sensor temperature is above the setpoint. At the top of this range, the cool mode outputs at 100%. The deadband does not apply to PID- controlled modes. Measured in tenths of degrees Celsius. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration." ::= { airFMSysCooling 12 }
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.13.1.4.5.12.0 | airFMSysCoolDeadbandC | 0 | 0 | None |
OID | Name | Sub children | Sub Nodes Total | Description |
---|---|---|---|---|
1.3.6.1.4.1.318.1.1.13.1.4.5.1 | airFMSysCompMinOnTime | 1 | 1 | Set the minimum time the compressor continues to operate after it is started. The delay protects the compressor from damage. Caut… |
1.3.6.1.4.1.318.1.1.13.1.4.5.2 | airFMSysCompMinOffTime | 1 | 1 | airFMSysCompMinOfftime |
1.3.6.1.4.1.318.1.1.13.1.4.5.3 | airFMSysCompRotPeriod | 1 | 1 | Set how often to perform compressor runtime balancing. Measured in hours. A value of -2147483648 indicates that this OID does not… |
1.3.6.1.4.1.318.1.1.13.1.4.5.4 | airFMSysEconIsolVlvOpenDelay | 1 | 1 | Set the delay between opening the Economizer Isolator output relay and engaging the compressors. Measured in seconds. A value of … |
1.3.6.1.4.1.318.1.1.13.1.4.5.5 | airFMSysEconIsolVlvCloseDelay | 1 | 1 | Set the delay between disengaging the compressor and closing the Economizer Isolator output relay. Measured in seconds. A value of… |
1.3.6.1.4.1.318.1.1.13.1.4.5.6 | airFMSysCndsrFluidVlvCloseDelay | 1 | 1 | Set the time the condenser valve remains open after the compressors disengage. Measured in seconds. A value of -2147483648 indic… |
1.3.6.1.4.1.318.1.1.13.1.4.5.7 | airFMSysInterstageDelay | 1 | 1 | The DX interstage delay allows the first compressor's cooling to take effect before engaging the second compressor. This prevents… |
1.3.6.1.4.1.318.1.1.13.1.4.5.8 | airFMSysCoolState | 1 | 1 | Set the mode to enabled or disabled. Disabled modes will not operate, and you cannot make changes to their settings while they ar… |
1.3.6.1.4.1.318.1.1.13.1.4.5.9 | airFMSysCoolEssFunction | 1 | 1 | Set the priority of the mode for alarms and events with the nonessential stop behavior. Nonessential modes are disabled during no… |
1.3.6.1.4.1.318.1.1.13.1.4.5.10 | airFMSysCoolSetpointC | 1 | 1 | The target value for the selected control sensor air for this mode. It must be at least 1.0 C above the reheat setpoint if a heat… |
1.3.6.1.4.1.318.1.1.13.1.4.5.11 | airFMSysCoolSetpointF | 1 | 1 | The target value for the selected control sensor air for this mode. It must be at least 1.0 C above the reheat setpoint if a heat… |
1.3.6.1.4.1.318.1.1.13.1.4.5.13 | airFMSysCoolDeadbandF | 1 | 1 | The temperature range that controls output when the selected control sensor temperature is above the setpoint. At the top of this… |
1.3.6.1.4.1.318.1.1.13.1.4.5.14 | airFMSysCoolEconIsolFunction | 1 | 1 | Set the Economizer Automatic Coolant Isolation valve to enabled or disabled. This valve anticipates a cooling demand and opens th… |
1.3.6.1.4.1.318.1.1.13.1.4.5.15 | airFMSysSuctPresCompensation | 1 | 1 | Set the Suction Pressure Compensation to enabled or disabled. This function attempts to keep the suction pressure from exceeding … |
1.3.6.1.4.1.318.1.1.13.1.4.5.16 | airFMSysCoilFluidActivThreshC | 1 | 1 | The minimum coolant temperature required to use the optional MultiCool or Economizer coil. Measured in tenths of degrees Celsius… |
1.3.6.1.4.1.318.1.1.13.1.4.5.17 | airFMSysCoilFluidActivThreshF | 1 | 1 | The minimum coolant temperature required to use the optional MultiCool or Economizer coil. Measured in tenths of degrees Fahrenh… |
1.3.6.1.4.1.318.1.1.13.1.4.5.18 | airFMSysCoilFluidActivDeadbandC | 1 | 1 | The controller will disengage the MultiCool or Economizer coil when the coolant temperature reaches the coil fluid temperature ac… |
1.3.6.1.4.1.318.1.1.13.1.4.5.19 | airFMSysCoilFluidActivDeadbandF | 1 | 1 | The controller will disengage the MultiCool or Economizer coil when the coolant temperature reaches the coil fluid temperature ac… |
1.3.6.1.4.1.318.1.1.13.1.4.5.20 | airFMSysCoolPIDMethod | 1 | 1 | Set the multipliers that the PID algorithm will use to calculate the cool output. Proportional, Proportional + Integral, or Propo… |
1.3.6.1.4.1.318.1.1.13.1.4.5.21 | airFMSysCoolPIDGainP | 1 | 1 | Set the proportional multiplier to correct for differences between the selected control sensor actual temperature and the setpoin… |
1.3.6.1.4.1.318.1.1.13.1.4.5.22 | airFMSysCoolPIDResetRateI | 1 | 1 | Set the integral multiplier to correct for the proportional offset. Measured in %/(C * min). A value of -2147483648 indicates th… |
1.3.6.1.4.1.318.1.1.13.1.4.5.23 | airFMSysCoolPIDDerivativeD | 1 | 1 | Set the derivative multiplier to counteract overshoot and droop during changes in the room load. Measured in %/(C / min). A value… |