Reference record for OID 1.3.6.1.4.1.318.1.1.13.1.4.5



parent
1.3.6.1.4.1.318.1.1.13.1.4 (airFMSystem)
node code
5
node name
airFMSysCooling
dot oid
1.3.6.1.4.1.318.1.1.13.1.4.5
type
OBJECT IDENTIFIER
asn1 oid
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) airConditioners(13) airFM(1) airFMSystem(4) airFMSysCooling(5)}
  • {iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) airConditioners(13) airFM(1) airFMSystem(4) airFMSysCooling(5)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) airConditioners(13) airFM(1) airFMSystem(4) airFMSysCooling(5)}
  • {iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) airConditioners(13) airFM(1) airFMSystem(4) airFMSysCooling(5)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprise(1) apc(318) products(1) hardware(1) airConditioners(13) airFM(1) airFMSystem(4) airFMSysCooling(5)}
  • {iso(1) iso-identified-organization(3) dod(6) internet(1) private(4) enterprises(1) apc(318) products(1) hardware(1) airConditioners(13) airFM(1) airFMSystem(4) airFMSysCooling(5)}
  • iri oid
  • /iso/identified-organization/dod/internet/private/enterprise/apc/products/hardware/airConditioners/airFM/airFMSystem/airFMSysCooling
  • /iso/identified-organization/dod/internet/private/enterprises/apc/products/hardware/airConditioners/airFM/airFMSystem/airFMSysCooling
  • /iso/org/dod/internet/private/enterprise/apc/products/hardware/airConditioners/airFM/airFMSystem/airFMSysCooling
  • /iso/org/dod/internet/private/enterprises/apc/products/hardware/airConditioners/airFM/airFMSystem/airFMSysCooling
  • /iso/iso-identified-organization/dod/internet/private/enterprise/apc/products/hardware/airConditioners/airFM/airFMSystem/airFMSysCooling
  • /iso/iso-identified-organization/dod/internet/private/enterprises/apc/products/hardware/airConditioners/airFM/airFMSystem/airFMSysCooling
  • iri by oid_info
    /ISO/Identified-Organization/6/1/4/1/318/1/1/13/1/4/5

    Information by mibdepot

    airFMSysCooling OBJECT IDENTIFIER ::= { airFMSystem 5 }

    Information by oid_info

    Vendor: American Power Conversion Corp.
    Module: PowerNet-MIB

    [Automatically extracted from oidview.com]

    Information by circitor

    airFMSysCooling OBJECT IDENTIFIER ::= { airFMSystem 5 }

    First Registration Authority (recovered by parent 1.3.6.1.4.1.318)

    Yoest Peter C.

    Children (23)

    OIDNameSub childrenSub Nodes TotalDescription
    1.3.6.1.4.1.318.1.1.13.1.4.5.1 airFMSysCompMinOnTime 1 1 Set the minimum time the compressor continues to
    operate after it is started. The delay protects the
    compressor from damage. Caut…
    1.3.6.1.4.1.318.1.1.13.1.4.5.2 airFMSysCompMinOffTime 1 1 airFMSysCompMinOfftime
    1.3.6.1.4.1.318.1.1.13.1.4.5.3 airFMSysCompRotPeriod 1 1 Set how often to perform compressor runtime
    balancing. Measured in hours.
    A value of -2147483648 indicates that this OID does
    not…
    1.3.6.1.4.1.318.1.1.13.1.4.5.4 airFMSysEconIsolVlvOpenDelay 1 1 Set the delay between opening the Economizer Isolator
    output relay and engaging the compressors. Measured
    in seconds.
    A value of …
    1.3.6.1.4.1.318.1.1.13.1.4.5.5 airFMSysEconIsolVlvCloseDelay 1 1 Set the delay between disengaging the compressor and
    closing the Economizer Isolator output relay.
    Measured in seconds.
    A value of…
    1.3.6.1.4.1.318.1.1.13.1.4.5.6 airFMSysCndsrFluidVlvCloseDelay 1 1 Set the time the condenser valve remains open after
    the compressors disengage. Measured in seconds.
    A value of -2147483648 indic…
    1.3.6.1.4.1.318.1.1.13.1.4.5.7 airFMSysInterstageDelay 1 1 The DX interstage delay allows the first compressor's
    cooling to take effect before engaging the second
    compressor. This prevents…
    1.3.6.1.4.1.318.1.1.13.1.4.5.8 airFMSysCoolState 1 1 Set the mode to enabled or disabled. Disabled modes
    will not operate, and you cannot make changes to
    their settings while they ar…
    1.3.6.1.4.1.318.1.1.13.1.4.5.9 airFMSysCoolEssFunction 1 1 Set the priority of the mode for alarms and events
    with the nonessential stop behavior. Nonessential
    modes are disabled during no…
    1.3.6.1.4.1.318.1.1.13.1.4.5.10 airFMSysCoolSetpointC 1 1 The target value for the selected control sensor air
    for this mode. It must be at least 1.0 C above the
    reheat setpoint if a heat…
    1.3.6.1.4.1.318.1.1.13.1.4.5.11 airFMSysCoolSetpointF 1 1 The target value for the selected control sensor air
    for this mode. It must be at least 1.0 C above the
    reheat setpoint if a heat…
    1.3.6.1.4.1.318.1.1.13.1.4.5.12 airFMSysCoolDeadbandC 1 1 The temperature range that controls output when the
    selected control sensor temperature is above the
    setpoint. At the top of this…
    1.3.6.1.4.1.318.1.1.13.1.4.5.13 airFMSysCoolDeadbandF 1 1 The temperature range that controls output when the
    selected control sensor temperature is above the
    setpoint. At the top of this…
    1.3.6.1.4.1.318.1.1.13.1.4.5.14 airFMSysCoolEconIsolFunction 1 1 Set the Economizer Automatic Coolant Isolation valve
    to enabled or disabled. This valve anticipates a
    cooling demand and opens th…
    1.3.6.1.4.1.318.1.1.13.1.4.5.15 airFMSysSuctPresCompensation 1 1 Set the Suction Pressure Compensation to enabled or
    disabled. This function attempts to keep the suction
    pressure from exceeding …
    1.3.6.1.4.1.318.1.1.13.1.4.5.16 airFMSysCoilFluidActivThreshC 1 1 The minimum coolant temperature required to use the
    optional MultiCool or Economizer coil. Measured in
    tenths of degrees Celsius…
    1.3.6.1.4.1.318.1.1.13.1.4.5.17 airFMSysCoilFluidActivThreshF 1 1 The minimum coolant temperature required to use the
    optional MultiCool or Economizer coil. Measured in
    tenths of degrees Fahrenh…
    1.3.6.1.4.1.318.1.1.13.1.4.5.18 airFMSysCoilFluidActivDeadbandC 1 1 The controller will disengage the MultiCool or
    Economizer coil when the coolant temperature reaches
    the coil fluid temperature ac…
    1.3.6.1.4.1.318.1.1.13.1.4.5.19 airFMSysCoilFluidActivDeadbandF 1 1 The controller will disengage the MultiCool or
    Economizer coil when the coolant temperature reaches
    the coil fluid temperature ac…
    1.3.6.1.4.1.318.1.1.13.1.4.5.20 airFMSysCoolPIDMethod 1 1 Set the multipliers that the PID algorithm will use
    to calculate the cool output. Proportional,
    Proportional + Integral, or Propo…
    1.3.6.1.4.1.318.1.1.13.1.4.5.21 airFMSysCoolPIDGainP 1 1 Set the proportional multiplier to correct for
    differences between the selected control sensor
    actual temperature and the setpoin…
    1.3.6.1.4.1.318.1.1.13.1.4.5.22 airFMSysCoolPIDResetRateI 1 1 Set the integral multiplier to correct for the
    proportional offset. Measured in %/(C * min).
    A value of -2147483648 indicates th…
    1.3.6.1.4.1.318.1.1.13.1.4.5.23 airFMSysCoolPIDDerivativeD 1 1 Set the derivative multiplier to counteract overshoot
    and droop during changes in the room load. Measured
    in %/(C / min).
    A value…

    Brothers (11)

    OIDNameSub childrenSub Nodes TotalDescription
    1.3.6.1.4.1.318.1.1.13.1.4.1 airFMSysStatus 25 50 None
    1.3.6.1.4.1.318.1.1.13.1.4.2 airFMSysDemands 14 28 None
    1.3.6.1.4.1.318.1.1.13.1.4.3 airFMSysSetup 16 32 None
    1.3.6.1.4.1.318.1.1.13.1.4.4 airFMSysConfig 10 20 None
    1.3.6.1.4.1.318.1.1.13.1.4.6 airFMSysHumidify 7 14 None
    1.3.6.1.4.1.318.1.1.13.1.4.7 airFMSysDehumidify 9 18 None
    1.3.6.1.4.1.318.1.1.13.1.4.8 airFMSysReheat 10 20 None
    1.3.6.1.4.1.318.1.1.13.1.4.9 airFMSysThresholds 16 32 None
    1.3.6.1.4.1.318.1.1.13.1.4.10 airFMSysInputs 2 10 None
    1.3.6.1.4.1.318.1.1.13.1.4.11 airFMSysOutputs 2 7 None
    1.3.6.1.4.1.318.1.1.13.1.4.12 airFMSysAlarmMap 6 126 None